Conduit Trade Size to Metric Converter
Convert either nominal label
Trade size 1/2 ↔ metric designator 16.
Identification labels only; neither is a measured inside diameter.
Complete conversion table with area references
| Trade size (inch label) | Metric designator | Existing conduit area / fill pages |
|---|---|---|
| 1/2 | 16 | EMT 1/2 · PVC 1/2 · RMC 1/2 |
| 3/4 | 21 | EMT 3/4 · PVC 3/4 · RMC 3/4 |
| 1 | 27 | EMT 1 · PVC 1 · RMC 1 |
| 1-1/4 | 35 | EMT 1-1/4 · PVC 1-1/4 · RMC 1-1/4 |
| 1-1/2 | 41 | EMT 1-1/2 · PVC 1-1/2 · RMC 1-1/2 |
| 2 | 53 | EMT 2 · PVC 2 · RMC 2 |
| 2-1/2 | 63 | EMT 2-1/2 · PVC 2-1/2 · RMC 2-1/2 |
| 3 | 78 | EMT 3 · PVC 3 · RMC 3 |
| 3-1/2 | 91 | EMT 3-1/2 · PVC 3-1/2 · RMC 3-1/2 |
| 4 | 103 | EMT 4 · PVC 4 · RMC 4 |
| 5 | 129 | PVC 5 · RMC 5 |
| 6 | 155 | PVC 6 · RMC 6 |
Nominal labels versus physical dimensions
Trade size 1-1/4 corresponds to metric designator 35; trade size 2-1/2 corresponds to 63. These are exact lookup pairs. A measured 35 mm bore does not automatically establish trade size 1-1/4.
For fill calculations, select the conduit type and its stored interior area. EMT, IMC, RMC, PVC Schedule 40, PVC Schedule 80, FMC, LFNC-B and ENT have separate area tables. The same trade-size label is not a guarantee of equal usable area.
Worked examples
Trade to metric: look up 3/4 in the left column → metric designator 21. Do not calculate 0.75 × 25.4 = 19.05 mm and use that as the designation.
Metric to trade: look up metric designator 103 → trade size 4. Then use the specific conduit family’s area table for fill; 103 is not a measured bore.
Frequently asked questions
Does 1/2-inch conduit have a 16 mm inside diameter?
Can I multiply trade size by 25.4 to find the metric designator?
Why are there no EMT links for trade sizes 5 and 6?
Methodology & sources
Reference: NEC Table 300.1(C). The 12 pairs below and the identification-only note appear in NFPA public development material, Table 300.1(C). That document is not represented as a newly acquired final adopted edition. This converter covers only the requested 1/2 through 6 trade sizes.
Linked interior areas reuse the existing site dataset attributed to Chapter 9 Table 4. Their original final-edition cell verification remains incomplete; see data-source limitations. The nominal mapping does not certify those area cells.
Hommer Zhao · Updated