1-1/4" PVC-40 Conduit Fill Chart

How many wires fit in 1-1/4" PVC-40 (PVC Schedule 40). Maximum conductor counts per AWG using the applicable Table 1 tier and documented Note 7 rule.

FIG. 02

MAXIMUM CONDUCTORS BY WIRE GAUGE

Table 1 fill tiers (53% / 31% / 40%) and Note 7 count rounding. 1-1/4" PVC-40 interior area = 1.4530 in².

XHHW-2: — Data pending verification; no capacity values provided. RHH/RHW-2 values apply without outer covering. Counts use 53% for one, 31% for two, and 40% for three or more, with Note 7 rounding for identical conductors in every tier.

AWGTHHN / THWN-2XHHW-2RHH / RHW-2 (without outer covering)
#1460—28
#1243—22
#1027—17
#816—10
#611—8
#47—6
#36—5
#25—4
#13—3
#1/03—2
#2/02—1
#4/01—1
FIG. 03

WORKED EXAMPLE & NEC REFERENCES

The NEC numbers behind 1-1/4" PVC-40

NEC 2023 Chapter 9, Table 4 lists the interior cross-sectional area of every standard trade size for each conduit family. For 1-1/4" PVC-40 (Article 352), the total 100% area is 1.4530 in². The allowable conductor fill is then derived from Table 1: 53% for a single conductor (0.7701 in²), 31% for two (0.4504 in²), and 40% for three or more (0.5812 in²).

Capacity at this size

The 1-1/4" PVC-40 40% budget is 0.5812 in². THHN maximum counts are #12: 43; #10: 27; #8: 16. At the #12 maximum, actual fill is 39.36%, using the 40% tier; Note 7 is not applied.

Adjacent trade sizes

1" PVC-40 has a 40% budget of 0.3328 in², a change of -0.2484 in². Its THHN counts are #12: 25; #10: 15; #8: 9.

1-1/2" PVC-40 has a 40% budget of 0.7944 in², a change of 0.2132 in². Its THHN counts are #12: 59; #10: 37; #8: 21.

Note 7 boundaries for this conduit

#14: 60 conductors at the 40% tier, 40.06% actual fill; #8: 16 conductors at the 40% tier, 40.30% actual fill; #3: 6 conductors at the 40% tier, 40.18% actual fill

These are area calculations. Physical clearance, bends, pulling tension and ampacity need separate checks. A larger size must be recalculated with the actual conductor mix; a single trade-size increase is not guaranteed to suffice.

Source citations

NFPA 70 (2023) — National Electrical Code. Chapter 9, Table 1: percent of cross section of conduit and tubing for conductors. Table 4: dimensions and percent area of conduit and tubing (Article 352). Table 5: dimensions of insulated conductors.

Calculation process — THHN counts and boundaries

Divide the allowed conduit area by one insulated conductor's area. The engine checks one conductor at 53%, two at 31%, and three or more at 40%. For identical conductors in any of these tiers, a fractional quotient of at least 0.8 rounds up under the documented Chapter 9 Note 7 rule.

The table shows the tier of the accepted maximum, its rounded display quotient, and actual fill. A Note 7 result can exceed its applicable percentage budget; actual fill is shown unchanged. Different conductor areas use strict area comparison; different IDs with equal insulated areas share the Note 7 group. Quotients are calculated from unrounded values; budgets and quotients display at least six significant digits, and ≈ marks rounded results. A zero means no count is accepted by this area-based rule; it is not a physical fit test.

1-1/4" PVC-40: 1.4530 in² interior. All values calculated from the current Table 4/5 data and fill engine.
THHN AWGOne wire in²TierBudget ÷ wire areaMaximumActual fillOne moreMax in 1-1/2"
#140.009740%0.58120000 ÷ 0.0097 ≈ 59.91752660 (Note 7)40.06%61: 40.72% — exceeds allowance82
#120.013340%0.58120000 ÷ 0.0133 ≈ 43.6992484339.36%44: 40.28% — exceeds allowance59
#100.021140%0.58120000 ÷ 0.0211 ≈ 27.5450242739.21%28: 40.66% — exceeds allowance37
#80.036640%0.58120000 ÷ 0.0366 ≈ 15.87978116 (Note 7)40.30%17: 42.82% — exceeds allowance21
#60.050740%0.58120000 ÷ 0.0507 ≈ 11.4635111138.38%12: 41.87% — exceeds allowance15
#40.082440%0.58120000 ÷ 0.0824 ≈ 7.0533981739.70%8: 45.37% — exceeds allowance9
#30.097340%0.58120000 ÷ 0.0973 ≈ 5.97327856 (Note 7)40.18%7: 46.88% — exceeds allowance8
#20.115840%0.58120000 ÷ 0.1158 ≈ 5.0189983539.85%6: 47.82% — exceeds allowance7
#10.156240%0.58120000 ÷ 0.1562 ≈ 3.7208707332.25%4: 43.00% — exceeds allowance5
#1/00.185540%0.58120000 ÷ 0.1855 ≈ 3.1331536338.30%4: 51.07% — exceeds allowance4
#2/00.222331%0.45043000 ÷ 0.2223 ≈ 2.0262258230.60%3: 45.90% — exceeds allowance3
#4/00.323753%0.77009000 ÷ 0.3237 ≈ 2.3790238122.28%2: 44.56% — exceeds allowance2

Compare all gauges in 1-1/2" PVC-40.

Keep fill and ampacity checks separate

Include all conductors present in the fill calculation, including equipment grounding conductors. Current-carrying conductor counts for ampacity adjustment follow different rules. Check terminal temperature limits, ambient correction, grounding, cable suitability and pulling conditions separately; a fill pass is not installation approval.

THWN-2 shares the supported THHN-family areas. RHH/RHW-2 values apply without outer covering; compare the table above. XHHW data remains withheld. For another insulation or a mixed pull, use the calculator below and the Table 5 guide.

FIG. 04

TRY IT — 1-1/4" PVC-40 LIVE

Preloaded with this conduit. Change the conductor gauge, insulation, or count and read the fill in real time.

NEC 2023 · CH.9
A · CONDUIT TYPE
B · TRADE SIZE
DESCRIPTION
PVC Schedule 40
C · CONDUCTORS
01
RESULT · FILL %
◆ APPROACHING LIMIT
39.4%
40% TIER
BASE BUDGET
025↑4075100
CONDUCTORS
43
WIRE AREA
0.572in²
CONDUIT AREA
1.453in²
GEOMETRIC JAM HINT
—

Table 1 tier: 40%. Note 7: not applied. The displayed percentage is actual fill; acceptance concerns area only.

An accepted result is within the NEC fill limit (Chapter 9 Table 1, per this site's calculation), including Note 7 where applicable. This assesses supported conductor areas only, not ampacity, product suitability, pulling feasibility or installation approval. A confirmed over-limit result means the supported equal-area count also fails the Note 7 check.

Geometric jamming risk hint only: assumes exactly three identical round conductors and infers diameters from area. The 2.8–3.2 ratio is a screening band, not a measured probability. Bends, tolerances, friction and pulling tension are not modeled; other configurations are not assessed.

  • Three or more conductors — 40% Table 1 tier; Note 7 may apply.
+19
CONDUIT
PVC40 · 1-1/4"
CONDUCTOR
12 AWG · THHN (90°C dry)
FIG. 05

FREQUENTLY ASKED QUESTIONS

What is the total cross-sectional area of 1-1/4" PVC-40 conduit?
1.4530 in² (100% area), per NEC 2023 Chapter 9, Table 4 — Article 352. The allowable conductor fill is 0.5812 in² at 40% (3+ conductors), 0.4504 in² at 31% (2 conductors), and 0.7701 in² at 53% (1 conductor).
How many #12 THHN can I pull in 1-1/4" PVC-40?
The area-rule maximum is 43 #12 THHN, using the 40% tier; actual fill is 39.36%. Note 7 is not applied. This does not establish ampacity or pulling feasibility.
Does the NEC 40% fill cap apply for two conductors?
No. NEC Chapter 9, Table 1 specifies 53% for one conductor, 31% for two conductors, and 40% for three or more.
Is 1-1/4" PVC-40 the same as 1-1/4" EMT?
No — trade size is the same nominal value, but the actual interior diameters differ across conduit types. Use NEC Ch.9 Table 4 for your specific conduit family. 1-1/4" PVC-40 is 1.4530 in² (Article 352).