CONDUIT FILL
CALCULATOR
NEC 2023 Wire Fill Charts & Conduit Fill Calculator. Pick conduit type and supported conductor areas to calculate fill. Results cover area only, not installation approval. All math runs in your browser — see the underlying wire fill chart for static lookups.
- CONDUCTORS
- 3
- WIRE AREA
- 0.040in²
- CONDUIT AREA
- 0.304in²
- GEOMETRIC JAM HINT
- LOW
Table 1 tier: 40%. Note 7: not applied. The displayed percentage is actual fill; acceptance concerns area only.
An accepted result is within the NEC fill limit (Chapter 9 Table 1, per this site's calculation), including Note 7 where applicable. This assesses supported conductor areas only, not ampacity, product suitability, pulling feasibility or installation approval. A confirmed over-limit result means the supported equal-area count also fails the Note 7 check.
Geometric jamming risk hint only: assumes exactly three identical round conductors and infers diameters from area. The 2.8–3.2 ratio is a screening band, not a measured probability. Bends, tolerances, friction and pulling tension are not modeled; other configurations are not assessed.
- Three or more conductors — 40% Table 1 tier; Note 7 may apply.
Mixed wire sizes: three worked examples
Short answer: when conductors differ in size, add up the Table 5 area of every conductor, then compare the total with the Table 4 area of the conduit multiplied by 53 %, 31 % or 40 % (one, two, or three or more conductors). There is no per-size count to look up, and equipment grounding conductors are entered as extra rows like any other conductor. All three examples use THHN in EMT and are the same sums you can enter in the calculator above.
The method in four steps
- For each size, multiply the Table 5 area of one conductor by the number of conductors of that size.
- Add the subtotals to get the total conductor area.
- Count all conductors, pick 53 % (one), 31 % (two) or 40 % (three or more), and multiply that percentage by the conduit's Table 4 area.
- The total area must not exceed that budget. Fill percent is total area divided by conduit area.
Example 1: six #10 and six #12 THHN in 3/4 in EMT
| Conductor | Count | Area each, in² | Subtotal, in² |
|---|---|---|---|
| #10 THHN | 6 | 0.0211 | 0.1266 |
| #12 THHN | 6 | 0.0133 | 0.0798 |
| Total | 12 | — | 0.2064 |
| 40 % budget | — | — | 0.2132 |
| Actual fill | 38.72 % · within the limit | ||
The twelve conductors total 0.2064 in², against a 40 % budget of 0.2132 in². It passes, with little room to spare: adding one more conductor of either size would exceed the budget.
Example 2: seven #10 and six #12 THHN: 3/4 in is too small, 1 in works
| Conductor | Count | Area each, in² | Subtotal, in² |
|---|---|---|---|
| #10 THHN | 7 | 0.0211 | 0.1477 |
| #12 THHN | 6 | 0.0133 | 0.0798 |
| Total | 13 | — | 0.2275 |
| 40 % budget | — | — | 0.2132 |
| Actual fill | 42.68 % · over the limit | ||
Swapping one #12 for a #10 raises the total to 0.2275 in², over the 0.2132 in² budget. Mixed sizes have no rounding allowance, so the answer is no. In 1 in EMT the same thirteen conductors use 26.33 % of 0.864 in², within the 40 % limit; the calculator's recommended next size is 1 in.
Example 3: why one different wire changes the answer (Note 7)
In 1 in EMT (0.864 in²) the 40 % budget is 0.3456 in². A #12 THHN is 0.0133 in², and 0.3456 ÷ 0.0133 = 25.98. Chapter 9 Note 7 lets a same-size fraction of 0.8 or more round up, so 26 conductors of #12 are accepted even though their area, 0.3458 in², is slightly over the budget (40.02 % fill).
| Set | Total area, in² | Fill | Result |
|---|---|---|---|
| 26 × #12 | 0.3458 | 40.02 % | accepted (Note 7) |
| 25 × #12 + 1 × #10 | 0.3536 | 40.93 % | over |
The rounding rule applies to a same-size set. Replace one #12 with a #10 and the set is no longer same-size, so the strict area comparison applies and the conduit is over its limit. This is why a table count for one size cannot be used as a shortcut for a mixed bundle.
Common mistakes with mixed sizes
- Averaging the wire size. Areas are not linear in gauge number; add the actual Table 5 areas.
- Leaving out the ground. Add the equipment grounding conductor as its own row so it is counted in the total.
- Mixing insulation families. THHN areas do not apply to other insulation types; pick the correct type for each row.
- Treating fill as the whole answer. Fill does not decide ampacity, derating or pulling; those are separate checks.
Single-size counts by conduit type are on the THHN wire fill chart, EMT chart and PVC chart. Areas are the site's transcription of NEC 2023 Chapter 9 Tables 4 and 5 and have not been compared cell by cell with the printed code; confirm with the edition your jurisdiction has adopted.
EMBED THIS CALCULATOR
Drop the live NEC conduit fill calculator into your own site — no signup. See our privacy policy for site-wide advertising and analytics.
<iframe src="https://wirefillchart.com/embed/conduit-fill-calculator" width="100%" height="760" style="border:1px solid #d6d8d2" title="NEC Conduit Fill Calculator" loading="lazy"></iframe>HOW TO USE THE CALCULATOR
- 01PICK THE CONDUIT TYPE
EMT, IMC, RMC, PVC Sch 40, PVC Sch 80, FMC, LFNC-B, or ENT. Each has its own NEC Chapter 9 Table 4 interior area.
- 02CHOOSE THE TRADE SIZE
The dropdown shows this dataset’s supported trade sizes: LFNC-B through 2 inches, RMC and PVC through 6 inches.
- 03ADD CONDUCTOR ROWS
Each row is one insulation + one gauge + a count. Use the stepper to bump the count quickly.
- 04READ THE RESULT
The instrument panel shows fill %, NEC status, geometric jamming risk hint, and a recommended next-size-up conduit when over fill.
NEC CODE REFERENCES
- NEC 2023 CH.9 TABLE 1Percent of cross-section of conduit and tubing for conductors (53/31/40).
- NEC 2023 CH.9 TABLE 4Dimensions and percent area of conduit and tubing.
- NEC 2023 CH.9 TABLE 5Dimensions of insulated conductors.
- NEC 2023, 310.15(C)(1)Adjustment factors for more than three current-carrying conductors (ampacity, separate from fill).