Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
CALCULATOR · FORMULAS & WORKED EXAMPLES

Voltage Drop Calculator: DC, Single-Phase & Three-Phase

Approximate resistive voltage drop

Estimated voltage drop: 7.902 V · 6.58%

CM = 6,530 · K ≈ 12.9 · circuit factor = 2.000000

Estimate only; no ampacity or code-compliance pass/fail is assigned.

Formula, units and approximation

Single-phase / DC: VD = 2·K·I·L/CM. Balanced three-phase: VD = √3·K·I·L/CM. Percentage drop = 100 × VD / supply voltage. In three-phase mode, use line-to-line supply voltage and line current.

I is current in amperes; L is the one-way length in feet; CM is conductor cross-sectional area in circular mils. K ≈ 12.9 for copper or 21.2 for aluminum, in Ω·cmil/ft. These are common approximate values (近似值); actual calculations should use NEC Chapter 9 Table 8 DC resistance with temperature correction. The calculator does not import an additional resistance or wire-gauge table.

The model assumes one conductor per path. It omits AC reactance, power factor, parallel conductors, unbalance and connection resistance. A material selection changes only K; it does not establish that a conductor size is permitted for that installation.

DC vs single-phase vs three-phase: what changes

Input conventions for this approximate resistance-only method
CircuitFactor in the formulaWhich voltage to useWhich lengthWhat is ignored
DC, two-wire2DC supply across the outgoing and return conductorsOne-way source to load, assuming equal outgoing and return lengthsConnection resistance, temperature correction and source-voltage changes
Single-phase, two-wire2Supply across the load: line-to-neutral or line-to-line as applicableOne-way source to load, assuming equal outgoing and return lengthsReactance, power factor, connection resistance and temperature correction
Balanced three-phase√3Line-to-line supply voltage; enter line currentOne-way source to load along the phase runUnbalance, neutral drop, reactance, power factor, connection resistance and temperature correction

These cases assume matching conductor material and area along each current path. A split run with different sizes or materials needs a segment calculation; a balanced three-phase result does not describe an unbalanced shared-neutral system.

Worked examples

All inputs below are assumed for arithmetic, not recommended conductor selections. Each example uses one conductor per path and the approximate K method. Results retain full precision internally; displayed volts and percentages are rounded independently. Comparisons with the informational figure do not establish compliance or equipment suitability.

Existing single-phase copper example

Single-phase copper: 12 AWG = 6,530 CM; I = 20 A; L = 100 ft; supply = 120 V. VD = 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.902 V. Percentage = 7.902 ÷ 120 × 100 ≈ 6.58%. DC with the same inputs gives the same resistive estimate.

This estimate is above the 3% informational figure; that comparison is not a compliance verdict.

Existing balanced three-phase aluminum example

Balanced three-phase aluminum: 1/0 AWG = 105,600 CM; I = 100 A; L = 200 ft; supply = 480 V line-to-line. VD = √3 × 21.2 × 100 × 200 ÷ 105,600 = 6.954 V, or 1.45%. This is an arithmetic example, not an ampacity recommendation.

Percentage = 6.954 ÷ 480 × 100 ≈ 1.45%. This estimate is below the 3% informational figure; that comparison is not a compliance verdict.

DC two-wire copper: a short run at low voltage

Assumed inputs: 12 AWG copper, 6,530 CM; 10 A; 20 ft one-way; 12 V DC. Approximate K = 12.9 Ω·cmil/ft.

  1. Substitute: VD = 2 × 12.9 × 10 × 20 ÷ 6,530 ≈ 0.790 V.
  2. Convert to percent: 0.790 ÷ 12 × 100 ≈ 6.58%.
  3. Read the comparison: the estimate is above the 3% informational figure. This is not a pass/fail or conductor-suitability conclusion.

The drop is less than a volt, yet it uses a large share of this low supply voltage. Short distance alone does not imply a small percentage drop.

Single-phase copper: a medium run

Assumed inputs: 10 AWG copper, 10,380 CM; 30 A; 150 ft one-way; 240 V single-phase. Approximate K = 12.9 Ω·cmil/ft.

  1. Substitute: VD = 2 × 12.9 × 30 × 150 ÷ 10,380 ≈ 11.185 V.
  2. Convert to percent: 11.185 ÷ 240 × 100 ≈ 4.66%.
  3. Read the comparison: the estimate is above the 3% informational figure. This is not a pass/fail or conductor-suitability conclusion.

Use the voltage across the supplied load. This is a two-wire line-to-line load example, not a calculation of separate line-to-neutral loads on a shared neutral.

Balanced three-phase copper: use line-to-line voltage

Assumed inputs: 6 AWG copper, 26,240 CM; 40 A line current; 150 ft one-way; 208 V line-to-line. Approximate K = 12.9 Ω·cmil/ft.

  1. Substitute: VD = √3 × 12.9 × 40 × 150 ÷ 26,240 ≈ 5.109 V.
  2. Convert to percent: 5.109 ÷ 208 × 100 ≈ 2.46%.
  3. Read the comparison: the estimate is below the 3% informational figure. This is not a pass/fail or conductor-suitability conclusion.

The entered current is line current. The square-root factor represents the balanced line-to-line relationship; it is not a count of the phase conductors.

Long-run aluminum: distance still matters with a larger conductor

Assumed inputs: 2/0 AWG aluminum, 133,100 CM; 60 A; 350 ft one-way; 240 V single-phase. Approximate K = 21.2 Ω·cmil/ft.

  1. Substitute: VD = 2 × 21.2 × 60 × 350 ÷ 133,100 ≈ 6.690 V.
  2. Convert to percent: 6.690 ÷ 240 × 100 ≈ 2.79%.
  3. Read the comparison: the estimate is below the 3% informational figure. This is not a pass/fail or conductor-suitability conclusion.

The larger circular-mil area reduces drop, while the long distance increases it. This assumed aluminum size is not selected from an ampacity table or checked for terminal compatibility.

Same load and distance: change only the circular-mil area

Assumed inputs: copper, single-phase, 120 V, 20 A and 100 ft one-way for both sizes. Approximate K = 12.9. The smaller size repeats the existing copper example so only CM changes.

Side-by-side size comparison at the same assumed load and distance
Step12 AWG copper10 AWG copper
Circular mils6,530 CM10,380 CM
Substitute and calculate drop2 × 12.9 × 20 × 100 ÷ 6,530 ≈ 7.902 V2 × 12.9 × 20 × 100 ÷ 10,380 ≈ 4.971 V
Percent of supply7.902 ÷ 120 × 100 ≈ 6.58%4.971 ÷ 120 × 100 ≈ 4.14%
Informational comparisonAbove 3%Above 3%

At fixed material, current, length and circuit type, VD is inversely proportional to CM. The larger wire has 6,530 ÷ 10,380 ≈ 0.629 times the smaller wire’s drop. Both comparisons are informational; neither selects a conductor for installation.

Reverse the formula: minimum circular mils for a target drop

Start with VD = factor × K × I × L ÷ CM. For a positive allowed drop, rearranging the drop criterion gives CM_min = factor × K × I × L ÷ VD_allowed. If the target is a percentage, first convert it to volts: VD_allowed = supply voltage × target percent ÷ 100.

Assumed inputs: the same 120 V single-phase copper run, 20 A and 100 ft one-way, with a chosen 3% target. The target is an assumption for this drop-only exercise, not a mandatory rule.

  1. Allowed volts: 120 × 3 ÷ 100 = 3.600 V.
  2. Minimum area: CM_min = 2 × 12.9 × 20 × 100 ÷ 3.600 = 51,600 ÷ 3.600 ≈ 14,333.33 CM.
  3. Read the table upward by area: 10 AWG has 10,380 CM, below the calculated minimum. The first supported area at or above that minimum is 8 AWG, 16,510 CM. Use the unrounded minimum for this lookup.
  4. Substitute back: 2 × 12.9 × 20 × 100 ÷ 16,510 ≈ 3.125 V; 3.125 ÷ 120 × 100 ≈ 2.60%, below the chosen 3% informational target.

This result is a minimum for the drop criterion only, not an ampacity or conduit-fill sizing result. If the calculated minimum exceeds every supported area, this table supplies no size; do not round down. Use the conduit fill calculator for the separate fill check with the complete conductor list and insulation areas. The ampacity-explanation guide describes why current-carrying capacity needs a separate assessment.

Long runs and low voltage: why the same wire behaves differently

With material, current, area and circuit type held fixed, drop in volts grows in direct proportion to one-way length. Supply voltage does not appear in that resistive drop equation; it enters when dividing VD by supply voltage to find the fraction lost. For the same percentage target, a lower-voltage circuit therefore has a smaller absolute drop budget.

The short DC example shows how a small drop in volts can consume a substantial share of a low supply voltage. The long aluminum example shows why distance remains relevant even with a larger conductor. Changing supply voltage while holding current fixed changes the percentage, not the calculated volts lost. If a real load instead holds power constant, its current can change too; that is a different input assumption and needs a fresh calculation.

Common mistakes

  • Entering round-trip length: the two-wire factor already includes the return path. Enter the one-way distance; doubling it again double counts that path.
  • Using phase-to-neutral voltage for a three-phase percentage: balanced three-phase mode calculates line-to-line drop. Divide by line-to-line supply voltage and enter line current.
  • Mixing copper and aluminum K: match the approximate material constant to the conductor. A material change does not check terminal compatibility or establish permission to use that wire.
  • Entering conduit trade size where CM is needed: CM describes conductive metal area, not raceway diameter or insulated-wire area. Read the circular-mils table; the AWG area converter explains the separate area units.
  • Treating 3% or 5% as mandatory by themselves: these are informational recommendations. Equipment needs, project specifications and adopted local rules require separate review.
  • Treating K as exact: the constants are approximate. Temperature changes resistance, and AC reactance and power factor can affect the drop; none is corrected by this tool. Use appropriate NEC Chapter 9 Table 8 DC resistance with temperature correction for an actual resistance calculation.
  • Using a small drop as an ampacity decision: a drop percentage does not establish permissible current, overcurrent protection or terminal ratings. See what ampacity means.
  • Entering total current as if each parallel conductor carries it: for identical parallel paths assumed to share current equally, the resistive arithmetic can divide total current by the number of conductors per path while retaining each conductor’s CM, or retain total current and multiply CM by that same count. Apply only one adjustment. This calculator itself assumes one conductor per path and has no parallel-count input; an equivalent-area calculation is a separate hand method. Unequal current sharing and permission to parallel are not assessed.

3% / 5%: informational recommendations

The familiar 3% individual branch/feeder and 5% combined feeder plus branch circuit recommendations associated with NEC 210.19 / 215.2 are Informational Notes, not mandatory requirements by themselves. The combined 5% refers to the entire feeder-plus-branch path, not an additional 5% for each segment. This calculator evaluates only the entered segment and does not certify the total path.

CM values used by this calculator

These are existing site values cross-checked against the manufacturer’s nominal CM column. 14 AWG uses 4,110 CM, matching that source; the former 4,107 value was the ideal-diameter formula result.

Supported existing conductor areas; no new wire sizes added
SizeCircular mils (CM)
14 AWG4,110
12 AWG6,530
10 AWG10,380
8 AWG16,510
6 AWG26,240
4 AWG41,740
3 AWG52,620
2 AWG66,360
1 AWG83,690
1/0 AWG105,600
2/0 AWG133,100
3/0 AWG167,800
4/0 AWG211,600
250 kcmil250,000
300 kcmil300,000
350 kcmil350,000
400 kcmil400,000
500 kcmil500,000
600 kcmil600,000
700 kcmil700,000
750 kcmil750,000
800 kcmil800,000
900 kcmil900,000
1000 kcmil1,000,000

Frequently asked questions

Is length one-way or round-trip?
Enter the one-way run length in feet. The factor 2 already accounts for the outgoing and return path in a two-wire single-phase or DC circuit. Do not double the entered length again.
Are the 3% and 5% figures mandatory NEC limits?
The commonly cited 3% individual branch/feeder and 5% combined feeder-plus-branch guidance in NEC 210.19 and 215.2 is in Informational Notes, not mandatory requirements by itself. Adopted local rules, project specifications or equipment needs may impose separate limits.
Are K = 12.9 and K = 21.2 exact material constants?
No. They are common approximate values in ohm-circular-mils per foot. Actual calculations should use the appropriate NEC Chapter 9 Table 8 DC resistance with temperature correction. The simplified AC estimate omits reactance and power-factor effects.
Why does 14 AWG use 4,110 CM instead of 4,107 CM?
4,107 CM is what the ideal AWG diameter formula gives (a diameter of about 64.08 mil, squared). The 4,110 CM value is the nominal 14 AWG area listed in the manufacturer’s table and in the commonly quoted NEC Chapter 9 Table 8 figure of 4.11 kcmil. This calculator uses 4,110 CM, the same as every other 14 AWG figure on this site. The difference is about 0.1%.
Does a low voltage-drop result prove the wire is suitable?
No. This is a resistive voltage-drop estimate for one conductor per path, not an ampacity, overcurrent protection, grounding, terminal rating or conduit-fill assessment. Three-phase mode assumes a balanced circuit and line-to-line supply voltage.
Does this calculator include power factor?
No. It uses a resistance-only approximation with an approximate material K. It does not accept power factor or model AC reactance. For an AC load where those effects matter, use an impedance calculation with appropriate conductor and load data; multiplying this result by power factor alone does not add the missing reactance term.
Can I use this calculator for DC solar wiring?
DC mode can illustrate the resistive drop of an assumed two-wire segment using a supported conductor size, the segment current and its operating voltage. Calculate segments separately when current or conductor size changes. It does not select PV design current, model changing array operating conditions, check equipment voltage windows, or establish cable, protection or installation suitability.
How do I adjust the result for conductor temperature?
This calculator has no temperature input and does not correct its approximate K values. For a temperature-specific calculation, use applicable conductor DC resistance and its documented temperature correction, then substitute the corrected resistance into the circuit calculation. Do not infer conductor temperature from the insulation label; for AC, resistance alone still omits reactance and power-factor effects.
Is three-phase length one-way or round-trip?
Use the one-way source-to-load distance along the run. The balanced three-phase factor already describes the line-to-line drop; do not double the length or add the lengths of all phase conductors. Use line current and line-to-line supply voltage for the percentage calculation.

Methodology & sources

CM inputs come directly from the site’s circular-mils table. Its 24 included cells were compared with Southwire SPEC10080, Table 1, Cond. Cmil column. This verifies the matching nominal CM values only, not a final NEC edition, resistance column, insulation diameter or ampacity. The 14 AWG cell is 4,110 CM; the earlier 4,107 value was the ideal-diameter formula result and has been replaced.

The NFPA public development report for Article 210 reproduces the informational 3%/5% guidance and its feeder reference. Public development material is not a newly verified final adopted code. Use the applicable NEC Chapter 9 Table 8 DC resistance and temperature correction for an actual resistance calculation.

Hommer Zhao · Updated