Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
FIG. 01 — REFERENCE TABLE

PVC Conduit Fill Chart (Sch 40 & Sch 80)

Maximum conductors per PVC Schedule 40 and Schedule 80 trade size, NEC 2023 Chapter 9.

Compare the supported PVC Schedule 40 and Schedule 80 areas with the dropdown below. For mixed conductor sizes, use the conduit fill calculator.

PVC Schedule 40 vs Schedule 80: how much room you lose

Short answer: Schedule 80 PVC has a thicker wall, so for the same trade size it has less interior area than Schedule 40, and the NEC fill limits (53 % for one conductor, 31 % for two, 40 % for three or more) apply to that smaller area. The table below shows the loss by size, and the second table shows what it does to the number of conductors that fit. Use Schedule 40 values only for Schedule 40 conduit and Schedule 80 values only for Schedule 80.

Interior area, in² (100 %), and the 40 % fill budget for three or more conductors
Trade sizeSch 40 areaSch 80 areaSch 80 vs 40Sch 40 at 40 %Sch 80 at 40 %
1/2"0.2850.217−23.9 %0.11400.0868
3/4"0.5080.409−19.5 %0.20320.1636
1"0.8320.688−17.3 %0.33280.2752
1-1/4"1.4531.237−14.9 %0.58120.4948
1-1/2"1.9861.711−13.8 %0.79440.6844
2"3.2912.874−12.7 %1.31641.1496
2-1/2"4.6954.119−12.3 %1.87801.6476
3"7.2686.442−11.4 %2.90722.5768
3-1/2"9.7378.688−10.8 %3.89483.4752
4"12.55411.258−10.3 %5.02164.5032
5"19.76117.855−9.6 %7.90447.1420
6"28.56725.598−10.4 %11.426810.2392
Maximum THHN conductors of one size, Schedule 40 / Schedule 80
Conductor1/2"3/4"1"1-1/4"1-1/2"2"
#12 THHN8 / 615 / 1225 / 2043 / 3759 / 5199 / 86
#10 THHN5 / 49 / 715 / 1327 / 2337 / 3262 / 54

Check one size by hand

At 1 in, Schedule 40 has 0.832 in² and Schedule 80 has 0.688 in². One #12 THHN occupies 0.0133 in². The 40 % budget divided by that area gives 25.02 for Schedule 40 and 20.69 for Schedule 80. Chapter 9 Note 7 allows a fraction of 0.8 or more to round up, so these become 25 and 20 conductors: same trade size, 5 fewer wires in Schedule 80.

Does Schedule 80 force a bigger conduit?

Sometimes. For 12 #12 THHN conductors the smallest supported size is 3/4" in Schedule 40 and 3/4" in Schedule 80. Check your own conductor count and size in the chart below rather than assuming the two schedules are interchangeable; a trade size that passes in Schedule 40 can fail in Schedule 80.

What this comparison does not tell you

  • It is about fill only. Where each schedule may be used, support spacing, expansion fittings and bending are separate questions. See EMT vs PVC vs RMC conduit fill for the wider comparison.
  • Counts assume same-size conductors. Use the conduit fill calculator for mixed sizes and for equipment grounding conductors, or the Schedule 80 chart for that schedule alone.
  • Fill is not pulling. A count that passes may still be hard to pull around bends or over long runs; see pull box size for the box side.
  • Data status. Areas are the site's transcription of NEC 2023 Chapter 9 Table 4 and have not been compared cell by cell with the printed code. Confirm with the code edition your jurisdiction has adopted.
TABLE · PVC40 × THHN (90°C dry)
NEC 2023 · CH. 9
  • 1/2" PVC408 wires40% tier · Note 7 no
  • 3/4" PVC4015 wires40% tier · Note 7 no
  • 1" PVC4025 wires40% tier · Note 7 no
  • 1-1/4" PVC4043 wires40% tier · Note 7 no
  • 1-1/2" PVC4059 wires40% tier · Note 7 no
  • 2" PVC4099 wires40% tier · Note 7 yes
  • 2-1/2" PVC40141 wires40% tier · Note 7 no
  • 3" PVC40218 wires40% tier · Note 7 no
  • 3-1/2" PVC40293 wires40% tier · Note 7 yes
  • 4" PVC40377 wires40% tier · Note 7 no
  • 5" PVC40594 wires40% tier · Note 7 no
  • 6" PVC40859 wires40% tier · Note 7 no

PVC Schedule 40 × THHN (90°C dry) · NEC 2023 Ch.9 Tables 4 & 5 · 40% (3+), 31% (2), 53% (1); Note 7 for equal insulated conductor areas

What is PVC Schedule 40?

PVC Schedule 40 is the name attached to the PVC40 area selection in this site's Table 4 dataset. Its 12 supported sizes run from 1/2 through 6 inches.

The six PVC40 rows from 1/2 through 2 inches match the six ENT rows exactly. PVC40 then adds six sizes through 6 inches. At 2-1/2 inches, PVC40 has 4.6950 in² and a 1.8780 in² budget; there is no corresponding ENT entry. Equal areas over the shared range do not supply values for the missing ENT sizes.

NEC Article 352; Chapter 9 Table 4. These comparisons use this site's stored areas; final-edition cells remain unverified. See the Table 4 guide and source status.

FIG. 02

NOTES & CONTEXT

Compare the two area columns

At 1 inch, Schedule 80 has 0.1440 in² less interior area than Schedule 40: (0.8320 − 0.6880) ÷ 0.8320 = 17.31%. This is an area difference; integer conductor counts are calculated separately.

Fill example with assumed conductors

Three 4/0 THHN and one #2 THHN occupy 1.0869 in². In 2-inch Schedule 80, the area is 2.8740 in² and actual fill is 37.82%.

PVC expansion threshold in the cited material

The text of 352.44 in the NFPA public revision material, PDF page 161 specifies expansion fittings for expected thermal length change of 1/4 in or greater (≥ 0.25 in), using Table 352.44 for a straight run between securely mounted boxes, cabinets, elbows or other conduit terminations. Exactly 0.25 in meets that threshold.

FIG. 03

FAQ

How do Schedule 40 and Schedule 80 areas compare?
At 1 inch, Schedule 40 has 0.8320 in² and Schedule 80 has 0.6880 in² in the site’s dataset. Multiplying by 0.40 gives budgets of 0.3328 and 0.2752 in².
How many 4/0 THHN conductors fit in 2-inch PVC Schedule 40?
The 40% budget is 3.2910 × 0.40 = 1.3164 in². Dividing by 0.3237 in² per conductor gives 4.0667, so the chart accepts four conductors.
Does exactly 0.25 in meet the cited PVC expansion threshold?
The text of 352.44 in the NFPA public revision material, PDF page 161 specifies expansion fittings for expected thermal length change of 1/4 in or greater (≥ 0.25 in), using Table 352.44 for a straight run between securely mounted boxes, cabinets, elbows or other conduit terminations. Exactly 0.25 in meets that threshold.