NEC 314.16(B) Box Fill Chart

Per-conductor cubic-inch allowances from NEC Table 314.16(B), and the maximum conductor count each standard metal box accepts (conductors only — clamps, yokes, EGCs and supports add their own allowances on top).

FIG. 02

PER-CONDUCTOR VOLUME ALLOWANCE

NEC 2023 Table 314.16(B) — Cubic inches per conductor by AWG.

Conductor size (AWG)Volume allowance (in³)
#181.50
#161.75
#142.00
#122.25
#102.50
#83.00
#65.00
FIG. 03

MAX CONDUCTORS PER STANDARD METAL BOX

Conductor-only count. Add allowances for clamps (1×), yokes (2×), EGC (1×) and supports (1×) — all in the largest AWG entering the box.

Box (NEC 314.16(A))in³#18#16#14#12#10#8#6
4" × 1-1/4" square18.0121098763
4" × 1-1/2" square21.01412109874
4" × 2-1/8" square30.32017151312106
4-11/16" × 1-1/4" square25.5171412111085
4-11/16" × 1-1/2" square29.5191614131195
4-11/16" × 2-1/8" square42.02824211816148
3" × 2" × 2" device10.06554432
3" × 2" × 2-1/2" device12.58765542
3" × 2" × 2-3/4" device14.09876542
3" × 2" × 3-1/2" device18.0121098763
4" × 2-1/8" × 1-1/2" device10.36554432
4" × 2-1/8" × 1-7/8" device13.08765542
4" × 2-1/8" × 2-1/8" device14.59876542
3-1/2" octagonal × 1-1/2"12.58765542
4" octagonal × 1-1/2"15.510876653
4" octagonal × 2-1/8"21.51412109874
FIG. 04

FREQUENTLY ASKED QUESTIONS

Why does a #14 conductor count as 2.0 in³ in a box?
NEC Table 314.16(B) lists fixed cubic-inch allowances per conductor AWG, derived from typical insulated-conductor diameters plus working clearance: #14 = 2.0 in³, #12 = 2.25 in³, #10 = 2.5 in³, #8 = 3.0 in³, #6 = 5.0 in³. These values are used regardless of insulation type because box fill is about physical room to bend and terminate, not heat dissipation.
Which box is biggest in standard depth?
The 4-11/16" × 2-1/8" square (sometimes called 'super 1900') gives the largest stock metal-box volume at 42.0 in³ per NEC Table 314.16(A). For deeper handle-side wiring, raised plaster rings (mud rings) on a 4-11/16" or 4" box can add 3–5 in³ to the working volume.
Does the chart apply to plastic boxes?
NEC 314.16 applies to all box types. Nonmetallic (plastic) boxes are required by 314.16(A)(2) to be durably and legibly marked with their cubic-inch volume by the manufacturer. Use that marked value as the box capacity in the same way the chart shows standard metal boxes.