WIRE·FILL·CHARTNEC 2023 · CH. 9
FIG. 01 — BOX FILL REFERENCE

NEC 314.16(B) Box Fill Chart

Per-conductor cubic-inch allowances from NEC Table 314.16(B), and the maximum conductor count each standard metal box accepts (conductors only — clamps, yokes, EGCs and supports add their own allowances on top).

FIG. 02

PER-CONDUCTOR VOLUME ALLOWANCE

NEC 2023 Table 314.16(B) — Cubic inches per conductor by AWG.

Conductor size (AWG)Volume allowance (in³)
#181.50
#161.75
#142.00
#122.25
#102.50
#83.00
#65.00
FIG. 03

MAX CONDUCTORS PER STANDARD METAL BOX

Conductor-only count. Add allowances for clamps (1×), yokes (2×), EGC (1×) and supports (1×) — all in the largest AWG entering the box.

Box (NEC 314.16(A))in³#18#16#14#12#10#8#6
4" × 1-1/4" square18.0121098763
4" × 1-1/2" square21.01412109874
4" × 2-1/8" square30.32017151312106
4-11/16" × 1-1/4" square25.5171412111085
4-11/16" × 1-1/2" square29.5191614131195
4-11/16" × 2-1/8" square42.02824211816148
3" × 2" × 2" device10.06554432
3" × 2" × 2-1/2" device12.58765542
3" × 2" × 2-3/4" device14.09876542
3" × 2" × 3-1/2" device18.0121098763
4" × 2-1/8" × 1-1/2" device10.36554432
4" × 2-1/8" × 1-7/8" device13.08765542
4" × 2-1/8" × 2-1/8" device14.59876542
3-1/2" octagonal × 1-1/2"12.58765542
4" octagonal × 1-1/2"15.510876653
4" octagonal × 2-1/8"21.51412109874
FIG. 04

FREQUENTLY ASKED QUESTIONS

NEC Table 314.16(B) lists fixed cubic-inch allowances per conductor AWG, derived from typical insulated-conductor diameters plus working clearance: #14 = 2.0 in³, #12 = 2.25 in³, #10 = 2.5 in³, #8 = 3.0 in³, #6 = 5.0 in³. These values are used regardless of insulation type because box fill is about physical room to bend and terminate, not heat dissipation.