Pull Box Size Calculator
Minimum interior length & width
For 4 AWG and larger conductors; up to 600 V. Enter trade-size labels separated by commas. For angle/U pulls, separate each row on each wall with a semicolon. Leave unused fields blank. Length runs left–right; width runs top–bottom.
Supported labels: 1/2, 3/4, 1, 1-1/4, 1-1/2, 2, 2-1/2, 3, 3-1/2, 4, 5, 6.
Minimum interior length: 24 in
Minimum interior width: 13 in
Calculated spans only. Check depth, entry spacing and the actual enclosure layout separately.
Rules and how to enter the layout
Use inch trade-size labels, such as 1-1/4 or 2-1/2. For a straight pull, use the largest raceway in that direction; smaller raceways do not add to the 8× calculation. For angle/U pulls, count the largest entry once at 6× and add every other raceway in the same row, including another entry of the same largest size.
Left/right wall entries constrain length; top/bottom wall entries constrain width. Evaluate each row separately, then take the maximum for that direction. If straight and angle pulls share an axis, satisfy both. A blank axis is “not determined,” never zero inches.
Separately check spacing between entries enclosing the same conductor; the cited angle/U-pull text specifies 6× the larger raceway trade size. The span calculator does not locate openings or verify that spacing. Depth and cover-facing entries also need a separate layout review.
Worked examples
Example 1 — straight pull
Assume 3-inch and 2-inch straight-through raceways along the length. Minimum length = 8 × 3 = 24 in. There is no width input, so the width is not determined by this example.
Example 2 — angle pull, two independent dimensions
Assume one left-wall row of 3, 2 and 1 inches, and one top-wall row of 2 and 1 inches. Length = 6 × 3 + 2 + 1 = 21 in. Width = 6 × 2 + 1 = 13 in. These spans still require an entry-spacing and depth check.
Example 3 — mixed straight and U pulls
Assume a 3-inch straight pull along the length and a length-constraining angle row of 3, 2 and 1 inches. Length = max(8 × 3, 6 × 3 + 2 + 1) = 24 in. For width, a U-pull row of 2, 2 and 1 inches gives 6 × 2 + 2 + 1 = 15 in. A separate row with a 3-inch entry gives 6 × 3 = 18 in, so width = max(15, 18) = 18 in.
Pull-box spans and box-fill volume solve different questions. A dimensional result does not establish the number of conductors permitted in a raceway.
The additional examples below use assumed raceway lists, not installation designs or enclosure recommendations. Entries describe only the stated axes; a missing axis remains undetermined. All answers are calculated with the same function as the interactive tool.
U pull: the second same-size entry still counts
Assumed raceway list: a U pull through a single left-wall row with trade-size labels 2, 2. Both entries enclose the same conductor. No straight pulls or width inputs are assumed.
- Choose the anchor: the largest entry is 2 in; 6 × 2 = 12 in.
- Add the other entry: the second 2-inch entry contributes another 2 in; 12 + 2 = 14 in.
- Answer: calculated minimum interior length = 14 in; width is not determined.
The repeated size is still a separate opening. Counting only the anchor would omit that entry from the row calculation.
Angle pull: several smaller raceways in the same row
Assumed raceway list: left-wall angle row 3, 1-1/2, 1-1/4, 1; top-wall angle row 2. These are inch trade-size labels. No straight pulls or other rows are assumed.
- Convert the fractional labels: 1-1/2 = 1 + 1/2 = 1.5 in; 1-1/4 = 1 + 1/4 = 1.25 in.
- Calculate length: 6 × 3 = 18 in; the other entries total 1.5 + 1.25 + 1 = 3.75 in; 18 + 3.75 = 21.75 in.
- Calculate width separately: the top row has a single entry, so 6 × 2 = 12 in.
- Answer: calculated minimum interior length = 21.75 in; width = 12 in.
Include every smaller entry in that left-wall row. The top-wall entry controls a different dimension and is not an extra term in the length sum.
Different walls: compare completed rows, do not sum them
Assumed raceway list: left-wall angle row 3, 1-1/2, 1-1/4, 1; a separate right-wall U-pull row 2, 2, 1; top-wall angle row 2. No straight pulls are assumed.
- Evaluate the left wall: 6 × 3 + 1.5 + 1.25 + 1 = 21.75 in.
- Evaluate the right wall: 6 × 2 + 2 + 1 = 15 in.
- Compare along length: max(21.75, 15) = 21.75 in. The rows constrain the same span from different walls.
- Answer: calculated minimum interior length = 21.75 in; the unchanged top row gives width = 12 in.
In the tool’s length angle/U field, keep the walls separate with a semicolon: 3, 1-1/2, 1-1/4, 1; 2, 2, 1. This compares row requirements; it does not draw the conductor paths or position the openings.
Straight pull: use a fractional trade size as a number
Assumed raceway list: straight-through trade-size labels 2-1/2, 2 along length. No angle/U rows or width inputs are assumed.
- Read the largest label: 2-1/2 = 2 + 1/2 = 2.5 in.
- Multiply only the largest: 8 × 2.5 = 20 in. The smaller 2-inch entry is not added for a straight pull.
- Answer: calculated minimum interior length = 20 in; width is not determined.
Sensitivity: increase only the largest entry by one listed size
Assumed raceway list: repeat the smaller-raceway angle example, changing only the left-wall 3-inch entry to the next supported label, 3-1/2. The full left-wall row is now 3-1/2, 1-1/2, 1-1/4, 1; the top row remains 2. No other inputs change.
- Convert the changed label: 3-1/2 = 3 + 1/2 = 3.5 in.
- Recalculate the anchor: 6 × 3.5 = 21 in; the smaller entries still total 3.75 in; 21 + 3.75 = 24.75 in.
- Compare with the original: 24.75 − 21.75 = 3 in of additional calculated length. Equivalently, 6 × (3.5 − 3) = 3 in.
- Answer: calculated minimum interior length = 24.75 in; width stays 12 in.
This change affects the largest-entry multiplier. A change to a smaller entry would affect the added sum unless it became the largest; a separate controlling row can also leave the final span unchanged.
Entry-to-entry spacing
The cited angle/U-pull rule also calls for spacing between entries enclosing the same conductor of at least 6 × the larger raceway trade size. In the assumed same-size U pull above, 6 × 2 = 12 in between those entries. Its row calculation gives 14 in for the interior length, which answers a different question.
The tool does not locate openings, measure their separation, or evaluate depth and cover-facing entries. A calculated span alone cannot establish that the actual arrangement provides this spacing.
Inch trade size → 8× straight-pull minimum and 6× angle/U-pull anchor
These are the labels supported by the tool, using nominal inch trade sizes rather than measured diameters or metric designators. The angle/U column is only an anchor: add every other entry in the same row, then compare completed rows for each axis.
| Inch trade size | 8× straight-pull minimum (in) | 6× angle/U anchor (in) |
|---|---|---|
| 1/2 | 4 | 3 |
| 3/4 | 6 | 4.5 |
| 1 | 8 | 6 |
| 1-1/4 | 10 | 7.5 |
| 1-1/2 | 12 | 9 |
| 2 | 16 | 12 |
| 2-1/2 | 20 | 15 |
| 3 | 24 | 18 |
| 3-1/2 | 28 | 21 |
| 4 | 32 | 24 |
| 5 | 40 | 30 |
| 6 | 48 | 36 |
Common mistakes when calculating pull box size
- Using a metric designator in an inch formula. Select the inch trade-size label; a metric designation is an identification label, not a measured diameter to multiply here.
- Summing all raceways for a straight pull. Use the largest raceway in that direction for the straight-pull multiplier.
- Forgetting the second same-size entry. For angle/U pulls, only one largest entry supplies the anchor; every other entry in that row still adds its own size.
- Mixing rows from different walls. Keep each row on each wall separate, calculate it, and take the maximum for the relevant axis.
- Ignoring depth. Length and width do not resolve depth, cover-facing entries, fitting space or conductor bending space.
- Using the result as enclosure approval. The tool does not verify a stock box’s usable interior dimensions, listing conditions, openings or actual conductor layout.
- Applying the tool above 600 V. That is outside its implemented voltage scope. Check the applicable method and adopted edition separately.
Pull box vs box fill vs conduit fill: which tool answers which question?
| Tool or guide | Question answered | What it does not establish |
|---|---|---|
| Pull box size (this page) | What minimum interior spans follow from the declared raceway rows and pull directions? | Opening locations, depth or enclosure approval. |
| Box fill calculator | What box volume follows from the supported conductor and device allowances? | The pull-box spans calculated here. |
| Conduit fill calculator | How does the declared conductor area compare with the raceway’s fill allowance? | Pull-box dimensions or pulling suitability. |
| Conduit bend offset calculator | What ideal offset geometry follows from a rise and bend angle? | Pull-box dimensions or opening placement. |
| NEC conduit fill rule guide | How do the conductor-area tables and count-based fill rules work together? | An installation design or enclosure approval. |
Frequently asked questions
Do I use conduit trade size or actual inside diameter?
How do multiple rows and opposite walls affect the result?
Is the calculated length and width a complete box selection?
Does this calculator cover more than 600 V or small-wire box fill?
If both U-pull raceways are the same size, do I count the second entry?
Is the angle/U anchor in the lookup table the full row requirement?
Will increasing one raceway always increase both box dimensions?
Can I use the displayed length as the distance between openings?
Methodology & sources
Rule reference: NEC 314.28(A). The NFPA public development report, inputs 865 and 1328, reproduces the straight-pull and angle/U-pull text. It is development material, not a newly verified final adopted edition. The worked examples are arithmetic demonstrations, not field measurements or enclosure approvals.
Use the edition adopted by the local authority and the enclosure’s actual interior dimensions. This tool deliberately stops at 600 V and does not evaluate depth or exceptions.