THWN Wire Fill Chart

THWN and THWN-2 conductor counts using the site’s shared THHN-family area dataset.

THWN and THWN-2 have different temperature ratings but share this site’s area table. Read the THWN-2 marking reference for the distinction.

TABLE · EMT × THWN-2 (90°C wet/dry)
NEC 2023 · CH. 9
  • 1/2" EMT9 wires40% tier · Note 7 no
  • 3/4" EMT16 wires40% tier · Note 7 no
  • 1" EMT26 wires40% tier · Note 7 yes
  • 1-1/4" EMT45 wires40% tier · Note 7 yes
  • 1-1/2" EMT61 wires40% tier · Note 7 no
  • 2" EMT101 wires40% tier · Note 7 yes
  • 2-1/2" EMT176 wires40% tier · Note 7 no
  • 3" EMT266 wires40% tier · Note 7 no
  • 3-1/2" EMT347 wires40% tier · Note 7 no
  • 4" EMT443 wires40% tier · Note 7 no

EMT — Electrical Metallic Tubing × THWN-2 (90°C wet/dry) · NEC 2023 Ch.9 Tables 4 & 5 · 40% (3+), 31% (2), 53% (1); Note 7 for equal insulated conductor areas

FIG. 02

NOTES & CONTEXT

Separate the three markings

  • THWN: 75°C dry and wet.
  • THWN-2: 90°C dry and wet.
  • THHN: 90°C dry.

Source: UL Wire and Cable Marking and Application Guide, page 14. THHN’s dry rating does not change the standalone THWN rating.

Shared fill areas

The engine maps these three designations to the same insulated-area dataset. For #10, that area is 0.0211 in²; changing between these labels leaves the computed fill unchanged.

Combined markings

A conductor marked THHN/THWN-2 carries both designations. A THHN/THWN marking retains THWN’s 75°C wet rating. See the Table 310.16 guide for the separate ampacity calculation.

FIG. 03

FAQ

What is the difference between THWN and THWN-2?
Standalone THWN is 75°C dry and wet. THWN-2 is 90°C dry and wet. These are separate rows in the UL guide, page 14.
Does a THHN/THWN marking give THWN a 90°C wet rating?
No. THHN contributes its 90°C dry rating; THWN has a 75°C wet rating. THWN-2 is the designation with 90°C dry and wet ratings.
What is the area of #10 THWN-2 in this chart?
The supported area is 0.0211 in². In 1/2-inch EMT, the 40% budget is 0.1216 in²; the engine accepts five #10 THWN-2 conductors.
Where is ampacity explained?
See the Table 310.16 ampacity guide. This chart computes occupied area.