CONDUIT FILL BASICS
- 01CH.9 TABLE 1
Percent of Cross-Section of Conduit and Tubing for Conductors
Sets the 53 / 31 / 40 percent fill rule by conductor count, plus the 60% nipple allowance.
- 02CH.9 TABLE 4
Dimensions and Percent Area of Conduit and Tubing
Interior cross-sectional area for every conduit type at every trade size — Article 342 (IMC), 344 (RMC), 348 (FMC), 352 (PVC), 356 (LFNC), 358 (EMT), 362 (ENT).
- 03CH.9 TABLE 5
Dimensions of Insulated Conductors and Fixture Wires
Cross-sectional area of every common insulation × every gauge — THHN, THWN, THWN-2, XHHW, XHHW-2, RHH, RHW, RHW-2, TW, TFE.
ADJUSTMENTS OUTSIDE FILL
- 01310.15(B)(1)
Ambient Temperature Correction
Correction factors when raceway ambient differs from 30 °C — independent of fill %.
- 02310.15(C)(1)
More Than Three Current-Carrying Conductors
Ampacity adjustment factor: 80% for 4–6 CCCs, 70% for 7–9, 50% for 10–20, 45% for 21–30, 40% for 31–40, 35% for 41+. Applies independently of conduit fill %.
- 03310.16
Ampacity Table for 0–2000 V Insulated Conductors
Baseline ampacity by gauge and insulation temperature rating.
- 04ANNEX C
Conduit and Tubing Fill Tables
Precomputed max-conductor tables that occasionally round differently than the strict Table 4 × Table 5 calculation.
RACEWAY ARTICLES
- 01ART. 358
Electrical Metallic Tubing (EMT)
Installation rules, supports, bends, and permitted uses.
- 02ART. 344
Rigid Metal Conduit (RMC)
Hazardous-location applications, threaded fittings.
- 03ART. 342
Intermediate Metal Conduit (IMC)
Lighter-weight rigid alternative to RMC.
- 04ART. 352
Rigid PVC Conduit
Schedule 40 and Schedule 80, including expansion fittings (352.44).
- 05ART. 348
Flexible Metal Conduit (FMC)
Limits on use as equipment ground (over 6 ft requires separate EGC).
- 06ART. 356
Liquidtight Flexible Nonmetallic Conduit (LFNC)
Direct sunlight, oil, wet-location rating.
- 07ART. 362
Electrical Nonmetallic Tubing (ENT)
Dry/concealed indoor use, height-of-building limits.