Data sources and verification status
The final NEC 2023 original has not been obtained for a cell-by-cell comparison. The checks below distinguish internal arithmetic from the external source facts actually read.
| Dataset | Evidence and coverage | Unsupported data |
|---|---|---|
| Conduit areas | 78 stored total-area entries across eight types. The area reference rows and 40% budgets are checked against these entries; final-edition source cells remain unverified. | LFMC, LFNC-A/C, FMC 3/8 inch and sizes absent from each table. |
| Insulated wire areas | The Table 5 guide and engine are checked both ways: numerical cells match supported values; dashes mean unsupported. UL temperature markings do not verify area values. | TW 600/750/1000 kcmil; XHHW/XHHW-2; TFE; outer-covered RHH; bare and compact conductor areas. |
| NM-B cable presets | Southwire SPEC10028, Table 1: stock 639478 (0.524 × 0.190 in), 639485 (0.630 × 0.220 in), 639500 (0.672 in round). Manufacturer nominal dimensions, not site measurements. | No estimated diameter presets for other products. |
| kcmil conversion | NIST SP 811 Appendix B.9, circular mil area conversion. Formula: 1000 × π × 0.0254² / 4 mm² per kcmil. | Conversion does not provide insulated or stranded wire outside diameter. |
Markings: UL Wire and Cable Marking and Application Guide, September 2019, pages 11, 14 and 30. The PVC threshold citation uses NFPA public revision material, PDF page 161, 352.44; that document is not presented as the final adopted edition.
CONDUIT FILL BASICS
- 01CH.9 TABLE 1
Percent of Cross-Section of Conduit and Tubing for Conductors
The engine implements the 53 / 31 / 40 percent count tiers, with Note 7 for equal insulated areas.
- 02CH.9 TABLE 4
Dimensions and Percent Area of Conduit and Tubing
Interior areas for eight supported types; coverage varies by trade size.
- 03CH.9 TABLE 5
Dimensions of Insulated Conductors and Fixture Wires
Cross-sectional areas for supported insulation and gauge combinations — THHN, THWN, THWN-2, RHH, RHW, RHW-2, TW.
ADJUSTMENTS OUTSIDE FILL
- 01310.15(B)(1)
Ambient Temperature Correction
Correction factors when raceway ambient differs from 30 °C — independent of fill %.
- 02310.15(C)(1)
More Than Three Current-Carrying Conductors
Ampacity adjustment is not calculated by the fill engine.
- 03310.16
Ampacity Table for 0–2000 V Insulated Conductors
Baseline ampacity by gauge and insulation temperature rating.
- 04ANNEX C
Conduit and Tubing Fill Tables
Precomputed same-size conductor counts. Chapter 9 Note 7 can round a quotient up when its fractional part is at least 0.8.
RACEWAY ARTICLES
- 01ART. 358
Electrical Metallic Tubing (EMT)
Installation rules, supports, bends, and permitted uses.
- 02ART. 344
Rigid Metal Conduit (RMC)
RMC area data: 12 trade sizes, 1/2 through 6 inches.
- 03ART. 342
Intermediate Metal Conduit (IMC)
IMC area data: 10 trade sizes, 1/2 through 4 inches.
- 04ART. 352
Rigid PVC Conduit
Schedule 40 and Schedule 80, including expansion fittings (352.44).
- 05ART. 348
Flexible Metal Conduit (FMC)
FMC area data: 10 trade sizes; LFMC is not included.
- 06ART. 356
Liquidtight Flexible Nonmetallic Conduit (LFNC)
The dataset covers LFNC-B only, at six trade sizes.
- 07ART. 362
Electrical Nonmetallic Tubing (ENT)
ENT area data: six trade sizes, matching the shared PVC40 rows.