This index describes the tables used by the conduit fill calculator and their supported subsets. The final NEC 2023 source tables have not been checked cell by cell against an acquired original.

Data sources and verification status

The final NEC 2023 original has not been obtained for a cell-by-cell comparison. The checks below distinguish internal arithmetic from the external source facts actually read.

DatasetEvidence and coverageUnsupported data
Conduit areas78 stored total-area entries across eight types. The area reference rows and 40% budgets are checked against these entries; final-edition source cells remain unverified.LFMC, LFNC-A/C, FMC 3/8 inch and sizes absent from each table.
Insulated wire areasThe Table 5 guide and engine are checked both ways: numerical cells match supported values; dashes mean unsupported. UL temperature markings do not verify area values.TW 600/750/1000 kcmil; XHHW/XHHW-2; TFE; outer-covered RHH; bare and compact conductor areas.
NM-B cable presetsSouthwire SPEC10028, Table 1: stock 639478 (0.524 × 0.190 in), 639485 (0.630 × 0.220 in), 639500 (0.672 in round). Manufacturer nominal dimensions, not site measurements.No estimated diameter presets for other products.
kcmil conversionNIST SP 811 Appendix B.9, circular mil area conversion. Formula: 1000 × π × 0.0254² / 4 mm² per kcmil.Conversion does not provide insulated or stranded wire outside diameter.

Markings: UL Wire and Cable Marking and Application Guide, September 2019, pages 11, 14 and 30. The PVC threshold citation uses NFPA public revision material, PDF page 161, 352.44; that document is not presented as the final adopted edition.

FIG. 01

CONDUIT FILL BASICS

  • 01CH.9 TABLE 1

    Percent of Cross-Section of Conduit and Tubing for Conductors

    The engine implements the 53 / 31 / 40 percent count tiers, with Note 7 for equal insulated areas.

  • 02CH.9 TABLE 4

    Dimensions and Percent Area of Conduit and Tubing

    Interior areas for eight supported types; coverage varies by trade size.

  • 03CH.9 TABLE 5

    Dimensions of Insulated Conductors and Fixture Wires

    Cross-sectional areas for supported insulation and gauge combinations — THHN, THWN, THWN-2, RHH, RHW, RHW-2, TW.

FIG. 02

ADJUSTMENTS OUTSIDE FILL

  • 01310.15(B)(1)

    Ambient Temperature Correction

    Correction factors when raceway ambient differs from 30 °C — independent of fill %.

  • 02310.15(C)(1)

    More Than Three Current-Carrying Conductors

    Ampacity adjustment is not calculated by the fill engine.

  • 03310.16

    Ampacity Table for 0–2000 V Insulated Conductors

    Baseline ampacity by gauge and insulation temperature rating.

  • 04ANNEX C

    Conduit and Tubing Fill Tables

    Precomputed same-size conductor counts. Chapter 9 Note 7 can round a quotient up when its fractional part is at least 0.8.

FIG. 03

RACEWAY ARTICLES

  • 01ART. 358

    Electrical Metallic Tubing (EMT)

    Installation rules, supports, bends, and permitted uses.

  • 02ART. 344

    Rigid Metal Conduit (RMC)

    RMC area data: 12 trade sizes, 1/2 through 6 inches.

  • 03ART. 342

    Intermediate Metal Conduit (IMC)

    IMC area data: 10 trade sizes, 1/2 through 4 inches.

  • 04ART. 352

    Rigid PVC Conduit

    Schedule 40 and Schedule 80, including expansion fittings (352.44).

  • 05ART. 348

    Flexible Metal Conduit (FMC)

    FMC area data: 10 trade sizes; LFMC is not included.

  • 06ART. 356

    Liquidtight Flexible Nonmetallic Conduit (LFNC)

    The dataset covers LFNC-B only, at six trade sizes.

  • 07ART. 362

    Electrical Nonmetallic Tubing (ENT)

    ENT area data: six trade sizes, matching the shared PVC40 rows.