Conduit Fill Examples: 3 Hand Calcs + 12 Comparisons
Residential and commercial conduit fill examples: three hand calculations plus 12 application fill geometry comparisons, with area budgets and Note 7 checks.
These are geometry results, not equipment, wire-size or grounding recommendations. Areas come from the site's transcribed tables; final-edition source cells remain unverified (U). Each section changes one stated input or boundary and retains its hypothetical conductor list.
Read the column definitions and Note 7 rule, reproduce a row in the fill calculator, or check the source status. RHH means without outer covering; LFNC means Type B only.
- Worked by hand: an assumed multi-circuit run
- A/C fill geometry: the narrow EMT versus LFNC-B boundary
- Garage fill geometry: remaining room for additional #12 conductors
- Range fill geometry: replace one conductor at a time without changing count
- EV fill geometry: two vs three conductors plus an assumed EGC
- Hot-tub fill geometry: change PVC schedule while holding trade size fixed
- Mini-split fill geometry: same gauge, shared or different insulation areas
- Service-entry fill geometry: adding a smaller wire removes equal-area rounding
- PV fill geometry: add conductor pairs while one fixed conductor remains
- Sub-panel fill geometry: enlarge three conductors while the fourth stays fixed
- Pool fill geometry: check the smallest section instead of averaging sizes
- Water-heater fill geometry: one, two or three repeated conductor groups
- Pump fill geometry: one, two and three conductors use different budgets
Worked by hand: sizing conduit for an assumed multi-circuit run
For residential conduit sizing examples, sum Table 5 areas, select the Table 1 tier by conductor count, and compare with each Table 4 interior area multiplied by that tier. Take the smallest supported size that passes, including eligible Note 7 rounding for equal-area conductors.
Use the stored Table 5 envelopes and Table 4 interiors. The rule guide explains the procedure and its separate five-conductor example.
Residential: two lighting/receptacle-style circuits in EMT
Assumed conductor list — assumed, not a design: two circuits sharing EMT, each with one hot, one neutral, one switched hot and one insulated equipment grounding conductor (EGC), all #12 THHN. That is eight physical conductors, not an ampacity-adjustment count.
Step 1 — areas:
- Hots: 2 × 0.0133 = 0.0266 in².
- Neutrals: 2 × 0.0133 = 0.0266 in².
- Switched hots: 2 × 0.0133 = 0.0266 in².
- EGCs: 2 × 0.0133 = 0.0266 in².
Step 2 — total and tier: 0.0266 + 0.0266 + 0.0266 + 0.0266 = 0.1064 in²; 2 + 2 + 2 + 2 = 8 conductors → 40%.
Step 3 — candidate budgets: start at the smallest stored size.
- 1/2-inch EMT: 0.3040 × 0.40 = 0.1216 in² budget; 0.1064 ÷ 0.3040 × 100 = 35.00% fill; passes; Note 7 used: no.
Step 4 — answer: smallest supported size = 1/2-inch EMT. See adjacent sizes in the EMT chart.
One conductor added: one #12 THHN gives 9 conductors, 0.1197 in² and 39.38% fill in 1/2-inch EMT; still passes the 40% budget of 0.1216 in²; Note 7 used: no.
Residential: mixed-size assumed list in PVC Schedule 40
Assumed conductor list — assumed, not a design: 4 × #14, 4 × #12 and 3 × #10 THHN. This complete list includes any grounds; no appliance assignments are implied.
Step 1 — areas:
- #14 THHN: 4 × 0.0097 = 0.0388 in².
- #12 THHN: 4 × 0.0133 = 0.0532 in².
- #10 THHN: 3 × 0.0211 = 0.0633 in².
Step 2 — total and tier: 0.0388 + 0.0532 + 0.0633 = 0.1553 in²; 4 + 4 + 3 = 11 conductors → 40%.
Step 3 — candidate budgets: unequal areas require strict comparison; a count chart or Note 7 cannot replace the sum.
- 1/2-inch PVC Schedule 40: 0.2850 × 0.40 = 0.1140 in² budget; 0.1553 ÷ 0.2850 × 100 = 54.49% fill; fails; Note 7 used: no.
- 3/4-inch PVC Schedule 40: 0.5080 × 0.40 = 0.2032 in² budget; 0.1553 ÷ 0.5080 × 100 = 30.57% fill; passes; Note 7 used: no.
Step 4 — answer: smallest supported size = 3/4-inch PVC Schedule 40. The THHN chart supplies individual-gauge comparisons.
One conductor added: one #12 THHN gives 12 conductors, 0.1686 in² and 33.19% fill in 3/4-inch PVC Schedule 40; still passes the 40% budget of 0.2032 in²; Note 7 used: no.
Commercial: three four-wire groups at a rounding boundary
Assumed conductor list — assumed, not a design: three circuit groups, each containing three circuit conductors and one separately counted insulated EGC, all #6 THHN. The complete list is 9 circuit conductors + 3 EGCs. Equal EGC size is assumed to expose rounding, not selected for grounding.
Step 1 — areas:
- Circuit conductors: 9 × 0.0507 = 0.4563 in².
- EGCs: 3 × 0.0507 = 0.1521 in².
Step 2 — total and tier: 0.4563 + 0.1521 = 0.6084 in²; 9 + 3 = 12 conductors → 40%.
Step 3 — candidate budgets: test every stored size until acceptance, including Note 7.
- 1/2-inch EMT: 0.3040 × 0.40 = 0.1216 in² budget; 0.6084 ÷ 0.3040 × 100 = 200.13% fill; fails; Note 7 used: no.
- 3/4-inch EMT: 0.5330 × 0.40 = 0.2132 in² budget; 0.6084 ÷ 0.5330 × 100 = 114.15% fill; fails; Note 7 used: no.
- 1-inch EMT: 0.8640 × 0.40 = 0.3456 in² budget; 0.6084 ÷ 0.8640 × 100 = 70.42% fill; fails; Note 7 used: no.
- 1-1/4-inch EMT: 1.4960 × 0.40 = 0.5984 in² budget; 0.6084 ÷ 1.4960 × 100 = 40.67% fill; passes; Note 7 used: yes.
Here 0.5984 ÷ 0.0507 ≈ 11.80276; its fractional part is at least 0.8, so Note 7 permits 12 equal-area conductors despite the 0.0100 in² budget excess.
Step 4 — answer: smallest supported size = 1-1/4-inch EMT, accepted through Note 7. Reproduce it in the fill calculator.
One conductor added: one #6 THHN gives 13 conductors and 0.6591 in²; at 40%, 1-1/4-inch EMT still has a 0.5984 in² budget (44.06% fill; fails), while 1-1/2-inch EMT has 2.0360 × 0.40 = 0.8144 in² (32.37% fill; passes); Note 7 used: no in either check.
Shortcut checks readers can do mentally
- Fill % = total conductor area ÷ full conduit area × 100; use the full area, not the budget.
- Above the tier, check equal-area Note 7 eligibility before moving to the next size; mixed areas have no rounding allowance here.
- Adding one #12 THHN consumes 0.0133 in². Recount conductors too.
Where this stops
Sizes here are fill geometry only; they do not select conductor size, ampacity, derating, voltage drop, box fill or grounding size. Local amendments and the adopted edition are not checked. See source limits.
Frequently asked questions
Does the grounding conductor count?
Yes. Include each physical grounding conductor and its area. Ampacity-adjustment counting is separate.
Can I mix cable and individual wire in this calculation?
Cable needs its exterior envelope and applicable counting rules, not just internal-wire areas. These individual-wire examples do not establish permission to mix them.
Can the same list pass in EMT but fail in PVC?
Yes: nominal sizes can have different interior areas. Use the actual material and schedule when comparing budgets.
What if the pull is long?
Fill is one check; pulling tension, bends and clearance need separate assessment. An area pass does not establish an acceptable pull.
A/C fill geometry: the narrow EMT versus LFNC-B boundary
Can a small difference in raceway interior area change a fill result at the same nominal size? Compare an assumed two #6 plus one #10 THHN in 1/2-inch EMT and LFNC-B. The wire list stays fixed; this calculation does not select a raceway for an air conditioner.
A 0.0040 in² budget difference
The stored interior areas are 0.3040 in² for EMT and 0.3140 in² for LFNC-B. Their 40% budgets are 0.1216 and 0.1256 in². Any mixed-area list above the first budget and at or below the second falls inside a narrow interval where these two results differ.
Place a list inside the interval
Two #6 plus one #10 occupy 0.1225 in². That is 0.0009 in² above the EMT budget and 0.0031 in² below the LFNC-B budget. Actual fill is approximately 40.30% versus 39.01%. The first accepted supported sizes therefore differ: 3/4-inch EMT and 1/2-inch LFNC-B.
Reproducible boundary rows
| Conductors | Insulation | Conduit | Size (in) | Wire area (in²) | Raceway area (in²) | Tier (%) | Budget (in²) | Fill (%) | Result | Note 7 | Smallest size (in) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 2×#8 + 1×#10 | THHN | EMT | 1/2 | 0.0943 | 0.3040 | 40 | 0.12160 | 31.02 | accepted | no | 1/2 |
| 2×#8 + 1×#10 | THHN | LFNC | 1/2 | 0.0943 | 0.3140 | 40 | 0.12560 | 30.03 | accepted | no | 1/2 |
| 2×#6 + 1×#10 | THHN | EMT | 1/2 | 0.1225 | 0.3040 | 40 | 0.12160 | 40.30 | exceeds | no | 3/4 |
| 2×#6 + 1×#10 | THHN | LFNC | 1/2 | 0.1225 | 0.3140 | 40 | 0.12560 | 39.01 | accepted | no | 1/2 |
| 2×#4 + 1×#10 | THHN | EMT | 1/2 | 0.1859 | 0.3040 | 40 | 0.12160 | 61.15 | exceeds | no | 3/4 |
| 2×#4 + 1×#10 | THHN | LFNC | 1/2 | 0.1859 | 0.3140 | 40 | 0.12560 | 59.20 | exceeds | no | 3/4 |
Check both sides of the interval
Replacing the two #6 with #8 lowers the total to 0.0943 in², so both 1/2-inch rows pass. Replacing them with #4 raises it to 0.1859 in², so neither passes at that size. These controls distinguish an actual boundary from a claim that LFNC always permits a smaller nominal size. LFNC here means the stored Type B table only.
Garage fill geometry: remaining room for additional #12 conductors
How many additional #12 THHN conductors fit after an assumed mixed list is already counted? Start with three #3 plus one #8 THHN in PVC Schedule 40. This asks about unused area, not spare circuits or future electrical capacity.
Subtract before dividing
The fixed list occupies 3 × 0.0973 + 0.0366 = 0.3285 in². In 1-inch PVC40 the 0.3328 in² budget leaves only 0.0043 in², less than one #12 at 0.0133 in². A displayed fill below 40% therefore does not guarantee room for even one additional conductor of the selected size.
An exact boundary at the next size
The 1-1/4-inch PVC40 budget is 0.5812 in². Subtracting the fixed list leaves 0.2527 in², exactly 19 × 0.0133 in². Nineteen additional #12 bring the total to 0.5812 in² and pass; twenty bring it to 0.5945 in² and exceed the budget. The twenty-conductor addition first passes at 1-1/2 inch.
Reproducible boundary rows
| Conductors | Insulation | Conduit | Size (in) | Wire area (in²) | Raceway area (in²) | Tier (%) | Budget (in²) | Fill (%) | Result | Note 7 | Smallest size (in) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 3×#3 + 1×#8 | THHN | PVC40 | 1 | 0.3285 | 0.8320 | 40 | 0.33280 | 39.48 | accepted | no | 1 |
| 3×#3 + 1×#8 + 1×#12 | THHN | PVC40 | 1 | 0.3418 | 0.8320 | 40 | 0.33280 | 41.08 | exceeds | no | 1-1/4 |
| 3×#3 + 1×#8 + 19×#12 | THHN | PVC40 | 1-1/4 | 0.5812 | 1.4530 | 40 | 0.58120 | 40.00 | accepted | no | 1-1/4 |
| 3×#3 + 1×#8 + 20×#12 | THHN | PVC40 | 1-1/4 | 0.5945 | 1.4530 | 40 | 0.58120 | 40.92 | exceeds | no | 1-1/2 |
| 3×#3 + 1×#8 + 20×#12 | THHN | PVC40 | 1-1/2 | 0.5945 | 1.9860 | 40 | 0.79440 | 29.93 | accepted | no | 1-1/2 |
Use the mixed-list rule
Do not apply equal-area rounding to the remainder: the complete list still contains different insulated areas. Enter all three sizes in the calculator, then vary only the #12 count. The accepted count is an area result for the stated additions, not permission to add conductors to an existing installation.
Range fill geometry: replace one conductor at a time without changing count
When four conductors remain four conductors, how many individual area substitutions cross the budget? Begin with three #6 and one #10 THHN. Replace one #6 at a time with #4, while holding 3/4-inch EMT and the #10 fixed. These are comparison inputs, not range wiring instructions.
Each substitution has the same area cost
A #4 occupies 0.0824 in² and a #6 occupies 0.0507 in², so each replacement adds 0.0317 in². The successive totals are 0.1732, 0.2049, 0.2366 and 0.2683 in². All lists contain four conductors and all use the same 40% base tier.
The second replacement crosses the line
The EMT budget is 0.2132 in². One replacement leaves 0.0083 in², but the second exceeds it by 0.0234 in². The first two lists have a minimum supported EMT size of 3/4 inch; the last two require 1 inch under the model. The final row checks the first failing list at that next size.
Reproducible boundary rows
| Conductors | Insulation | Conduit | Size (in) | Wire area (in²) | Raceway area (in²) | Tier (%) | Budget (in²) | Fill (%) | Result | Note 7 | Smallest size (in) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 3×#6 + 1×#10 | THHN | EMT | 3/4 | 0.1732 | 0.5330 | 40 | 0.21320 | 32.50 | accepted | no | 3/4 |
| 2×#6 + 1×#4 + 1×#10 | THHN | EMT | 3/4 | 0.2049 | 0.5330 | 40 | 0.21320 | 38.44 | accepted | no | 3/4 |
| 1×#6 + 2×#4 + 1×#10 | THHN | EMT | 3/4 | 0.2366 | 0.5330 | 40 | 0.21320 | 44.39 | exceeds | no | 1 |
| 3×#4 + 1×#10 | THHN | EMT | 3/4 | 0.2683 | 0.5330 | 40 | 0.21320 | 50.34 | exceeds | no | 1 |
| 1×#6 + 2×#4 + 1×#10 | THHN | EMT | 1 | 0.2366 | 0.8640 | 40 | 0.34560 | 27.38 | accepted | no | 1 |
Read sizes as geometry inputs
The comparison isolates which member of a fixed-length list changes. It does not assign the larger or smaller sizes to a particular electrical function. A blanket statement that four conductors fit would miss their different areas; likewise, keeping the conductor count constant does not keep fill constant.
EV fill geometry: two vs three conductors plus an assumed EGC
What changes when a third main conductor is added while an assumed insulated EGC stays the same size? Hold the two existing #4 THHN conductors and one #8 THHN fixed, then add one more #4. These are hypothetical inputs, not a conductor schedule for an EV model.
Isolate the added conductor
The three-conductor list occupies 2 × 0.0824 + 0.0366 = 0.2014 in². Adding one #4 contributes exactly 0.0824 in², giving 0.2838 in². Both lists already use the 40% base tier; the change is entirely occupied area, not a change from the two-conductor tier. The EGC label does not remove its area from the sum.
Boundary at 3/4-inch EMT
The 0.2132 in² budget accepts the shorter list, with 0.0118 in² remaining. The longer list exceeds it by 0.0706 in² and first passes at 1-inch EMT. In the second pair, #6 main conductors with a fixed #10 show why an extra conductor does not always change the minimum: both lists first pass at 3/4 inch.
Reproducible boundary rows
| Conductors | Insulation | Conduit | Size (in) | Wire area (in²) | Raceway area (in²) | Tier (%) | Budget (in²) | Fill (%) | Result | Note 7 | Smallest size (in) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 2×#4 + 1×#8 | THHN | EMT | 3/4 | 0.2014 | 0.5330 | 40 | 0.21320 | 37.79 | accepted | no | 3/4 |
| 2×#4 + 1×#8 | THHN | EMT | 1 | 0.2014 | 0.8640 | 40 | 0.34560 | 23.31 | accepted | no | 3/4 |
| 3×#4 + 1×#8 | THHN | EMT | 3/4 | 0.2838 | 0.5330 | 40 | 0.21320 | 53.25 | exceeds | no | 1 |
| 3×#4 + 1×#8 | THHN | EMT | 1 | 0.2838 | 0.8640 | 40 | 0.34560 | 32.85 | accepted | no | 1 |
| 2×#6 + 1×#10 | THHN | EMT | 3/4 | 0.1225 | 0.5330 | 40 | 0.21320 | 22.98 | accepted | no | 3/4 |
| 2×#6 + 1×#10 | THHN | EMT | 1 | 0.1225 | 0.8640 | 40 | 0.34560 | 14.18 | accepted | no | 3/4 |
| 3×#6 + 1×#10 | THHN | EMT | 3/4 | 0.1732 | 0.5330 | 40 | 0.21320 | 32.50 | accepted | no | 3/4 |
| 3×#6 + 1×#10 | THHN | EMT | 1 | 0.1732 | 0.8640 | 40 | 0.34560 | 20.05 | accepted | no | 3/4 |
Reproduce the comparison
Keep insulation, raceway type and the smaller conductor unchanged when switching between the paired rows. The mixed areas require strict comparison; Note 7 does not rescue the longer #4 list. No neutral requirement, EGC selection or charger rating is inferred from either result.
Hot-tub fill geometry: change PVC schedule while holding trade size fixed
Can the same nominal PVC size accept a list in Schedule 40 and reject it in Schedule 80? Hold three #6 plus one #10 THHN constant and compare the two stored area columns at 3/4 and 1 inch. No hot-tub model, environment or material requirement is assumed.
Separate nominal size from interior area
At 3/4 inch, PVC40 stores 0.5080 in² and PVC80 stores 0.4090 in². The corresponding 40% budgets are 0.2032 and 0.1636 in². The fixed wire area of 0.1732 in² lies between those budgets: the Schedule 40 row passes and the Schedule 80 row fails.
The next size changes the comparison
At 1 inch the budgets rise to 0.3328 and 0.2752 in², so both rows pass. The minimum accepted trade size is consequently 3/4 inch in Schedule 40 and 1 inch in Schedule 80. Comparing only the 1-inch percentages would hide the actual minimum-size difference.
Reproducible boundary rows
| Conductors | Insulation | Conduit | Size (in) | Wire area (in²) | Raceway area (in²) | Tier (%) | Budget (in²) | Fill (%) | Result | Note 7 | Smallest size (in) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 3×#6 + 1×#10 | THHN | PVC40 | 3/4 | 0.1732 | 0.5080 | 40 | 0.20320 | 34.09 | accepted | no | 3/4 |
| 3×#6 + 1×#10 | THHN | PVC40 | 1 | 0.1732 | 0.8320 | 40 | 0.33280 | 20.82 | accepted | no | 3/4 |
| 3×#6 + 1×#10 | THHN | PVC80 | 3/4 | 0.1732 | 0.4090 | 40 | 0.16360 | 42.35 | exceeds | no | 1 |
| 3×#6 + 1×#10 | THHN | PVC80 | 1 | 0.1732 | 0.6880 | 40 | 0.27520 | 25.17 | accepted | no | 1 |
| 3×#8 + 1×#10 | THHN | PVC40 | 3/4 | 0.1309 | 0.5080 | 40 | 0.20320 | 25.77 | accepted | no | 3/4 |
| 3×#8 + 1×#10 | THHN | PVC80 | 3/4 | 0.1309 | 0.4090 | 40 | 0.16360 | 32.00 | accepted | no | 3/4 |
A control list that does not change minimum
Three #8 plus one #10 occupy 0.1309 in². That list is below both 3/4-inch budgets, and its minimum is 3/4 inch in either schedule. A smaller interior area raises fill but does not automatically raise the required supported size. Change the schedule selector and retain every wire input to reproduce this distinction.
Mini-split fill geometry: same gauge, shared or different insulation areas
Does changing the insulation identifier change a three-conductor fill result? Compare three #8 conductors in the THHN, THWN-2 and RHH tables. Keep EMT size and conductor count fixed. The mini-split label does not make any of these assumed insulation choices suitable for a device.
Two identifiers with one area family
THHN and THWN-2 each use 0.0366 in² for #8 in this dataset. Three conductors total 0.1098 in², so both identifiers produce the same result in 1/2-inch EMT. The matching result follows from stored area equality, not from an assertion that their temperature or location ratings are interchangeable.
The same gauge can have a different envelope
RHH without outer covering uses 0.0556 in² for #8, giving 0.1668 in² for three. At 1/2 inch its 40% quotient is approximately 2.18705, below the 2.8 needed for three equal-area conductors under Note 7. Its first accepted EMT size is 3/4 inch, where the THHN-family lists also pass.
Reproducible boundary rows
| Conductors | Insulation | Conduit | Size (in) | Wire area (in²) | Raceway area (in²) | Tier (%) | Budget (in²) | Fill (%) | Result | Note 7 | Smallest size (in) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 3×#8 | THHN | EMT | 1/2 | 0.1098 | 0.3040 | 40 | 0.12160 | 36.12 | accepted | no | 1/2 |
| 3×#8 | THHN | EMT | 3/4 | 0.1098 | 0.5330 | 40 | 0.21320 | 20.60 | accepted | no | 1/2 |
| 3×#8 | THWN-2 | EMT | 1/2 | 0.1098 | 0.3040 | 40 | 0.12160 | 36.12 | accepted | no | 1/2 |
| 3×#8 | THWN-2 | EMT | 3/4 | 0.1098 | 0.5330 | 40 | 0.21320 | 20.60 | accepted | no | 1/2 |
| 3×#8 | RHH | EMT | 1/2 | 0.1668 | 0.3040 | 40 | 0.12160 | 54.87 | exceeds | no | 3/4 |
| 3×#8 | RHH | EMT | 3/4 | 0.1668 | 0.5330 | 40 | 0.21320 | 31.29 | accepted | no | 3/4 |
| 3×#6 | RHH | EMT | 3/4 | 0.2178 | 0.5330 | 40 | 0.21320 | 40.86 | accepted | yes | 3/4 |
A second boundary prevents percentage-only reasoning
Three #6 RHH without outer covering total 0.2178 in². In 3/4-inch EMT the budget quotient is approximately 2.93664, so Note 7 accepts three at approximately 40.86% actual fill. Changing the insulation table can therefore change both occupied area and whether rounding is used. RHH values here do not cover an additional outer covering.
Service-entry fill geometry: adding a smaller wire removes equal-area rounding
What happens to a Note 7 boundary when a smaller conductor is added? Start with three equal-area #2 THHN in 1-inch EMT, then append one #10. This assumed list has no assigned service rating or grounding function.
The equal-area starting point
Three #2 occupy 0.3474 in². The 1-inch EMT base budget is 0.3456 in², slightly smaller than that total. Dividing the budget by 0.1158 in² per wire gives approximately 2.98446; Note 7 rounds up to three. The engine accepts the list at approximately 40.21% actual fill.
Adding area also changes the comparison rule
The extra #10 adds 0.0211 in², producing 0.3685 in². The list now contains unequal insulated areas. The engine uses strict comparison with 0.3456 in², so it fails at 1 inch and first passes at 1-1/4 inch. Carrying the original rounded count allowance over to this changed list would ignore the new input structure.
Reproducible boundary rows
| Conductors | Insulation | Conduit | Size (in) | Wire area (in²) | Raceway area (in²) | Tier (%) | Budget (in²) | Fill (%) | Result | Note 7 | Smallest size (in) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 3×#2 | THHN | EMT | 1 | 0.3474 | 0.8640 | 40 | 0.34560 | 40.21 | accepted | yes | 1 |
| 3×#2 | THHN | EMT | 1-1/4 | 0.3474 | 1.4960 | 40 | 0.59840 | 23.22 | accepted | no | 1 |
| 3×#2 + 1×#10 | THHN | EMT | 1 | 0.3685 | 0.8640 | 40 | 0.34560 | 42.65 | exceeds | no | 1-1/4 |
| 3×#2 + 1×#10 | THHN | EMT | 1-1/4 | 0.3685 | 1.4960 | 40 | 0.59840 | 24.63 | accepted | no | 1-1/4 |
| 3×#1 | THHN | EMT | 1 | 0.4686 | 0.8640 | 40 | 0.34560 | 54.24 | exceeds | no | 1-1/4 |
| 3×#1 | THHN | EMT | 1-1/4 | 0.4686 | 1.4960 | 40 | 0.59840 | 31.32 | accepted | no | 1-1/4 |
| 3×#1 + 1×#10 | THHN | EMT | 1 | 0.4897 | 0.8640 | 40 | 0.34560 | 56.68 | exceeds | no | 1-1/4 |
| 3×#1 + 1×#10 | THHN | EMT | 1-1/4 | 0.4897 | 1.4960 | 40 | 0.59840 | 32.73 | accepted | no | 1-1/4 |
Contrast a larger conductor with no rounding benefit
Three #1 THHN already fail at 1-inch EMT: their 0.4686 in² total is too large even with equal-area rounding. Adding a #10 gives 0.4897 in²; both lists first pass at 1-1/4 inch. Losing Note 7 eligibility is a rule change, but it does not force an additional size increase in every case.
PV fill geometry: add conductor pairs while one fixed conductor remains
How many pairs fit when one additional conductor is always present? Use only hypothetical #10 THHN individual conductors: p pairs plus one gives a total count of 2p + 1. This is a count exercise, not a PV string design or a source of PV-wire dimensions.
The count advances in steps of two
With each #10 occupying 0.0211 in², adding a pair adds 0.0422 in². Two, three, four and five pairs plus the fixed conductor mean five, seven, nine and eleven conductors respectively. Their counts all use the 40% base tier. The odd-count restriction belongs to this example, not to the fill engine.
Two boundaries in the supported EMT sizes
In 1/2-inch EMT, five conductors occupy 0.1055 in² and pass; seven occupy 0.1477 in² and fail. In 3/4-inch EMT, nine occupy 0.1899 in² and pass; eleven occupy 0.2321 in² and fail. The budget quotient there is approximately 10.10427, so Note 7 does not raise the accepted count to eleven.
Reproducible boundary rows
| Conductors | Insulation | Conduit | Size (in) | Wire area (in²) | Raceway area (in²) | Tier (%) | Budget (in²) | Fill (%) | Result | Note 7 | Smallest size (in) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 5×#10 | THHN | EMT | 1/2 | 0.1055 | 0.3040 | 40 | 0.12160 | 34.70 | accepted | no | 1/2 |
| 5×#10 | THHN | EMT | 3/4 | 0.1055 | 0.5330 | 40 | 0.21320 | 19.79 | accepted | no | 1/2 |
| 7×#10 | THHN | EMT | 1/2 | 0.1477 | 0.3040 | 40 | 0.12160 | 48.59 | exceeds | no | 3/4 |
| 7×#10 | THHN | EMT | 3/4 | 0.1477 | 0.5330 | 40 | 0.21320 | 27.71 | accepted | no | 3/4 |
| 9×#10 | THHN | EMT | 3/4 | 0.1899 | 0.5330 | 40 | 0.21320 | 35.63 | accepted | no | 3/4 |
| 9×#10 | THHN | EMT | 1 | 0.1899 | 0.8640 | 40 | 0.34560 | 21.98 | accepted | no | 3/4 |
| 10×#10 | THHN | EMT | 3/4 | 0.2110 | 0.5330 | 40 | 0.21320 | 39.59 | accepted | no | 3/4 |
| 10×#10 | THHN | EMT | 1 | 0.2110 | 0.8640 | 40 | 0.34560 | 24.42 | accepted | no | 3/4 |
| 11×#10 | THHN | EMT | 3/4 | 0.2321 | 0.5330 | 40 | 0.21320 | 43.55 | exceeds | no | 1 |
| 11×#10 | THHN | EMT | 1 | 0.2321 | 0.8640 | 40 | 0.34560 | 26.86 | accepted | no | 1 |
Unused single-conductor room is not another pair
Ten #10 conductors fit in 3/4-inch EMT, but ten cannot be written as 2p + 1 with a whole-number pair count. Four pairs plus the fixed conductor are therefore the last accepted member of this particular sequence. Do not round the pair count independently or replace an unknown PV cable envelope with these THHN areas.
Sub-panel fill geometry: enlarge three conductors while the fourth stays fixed
How do minimum-size steps respond when three matching conductors change gauge together? Hold one #6 THHN fixed and compare three #1, #1/0, #2/0 or #3/0 THHN in EMT. No ampacity target selects these lists.
Three changes contribute to each area increase
The fixed #6 contributes 0.0507 in² throughout. The complete lists occupy 0.5193, 0.6072, 0.7176 and 0.8544 in². Moving from #1 to #1/0 adds 3 × (0.1855 − 0.1562) = 0.0879 in². This differs from replacing just one member of the list, as in the range example.
Read the two successive budget crossings
At 1-1/4-inch EMT the budget is 0.5984 in²: the #1 list passes, while the #1/0 list exceeds it by 0.0088 in². At 1-1/2 inch the budget is 0.8144 in²: both the #1/0 and #2/0 lists pass, but the #3/0 list exceeds it by 0.0400 in² and first passes at 2 inches.
Reproducible boundary rows
| Conductors | Insulation | Conduit | Size (in) | Wire area (in²) | Raceway area (in²) | Tier (%) | Budget (in²) | Fill (%) | Result | Note 7 | Smallest size (in) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 3×#1 + 1×#6 | THHN | EMT | 1 | 0.5193 | 0.8640 | 40 | 0.34560 | 60.10 | exceeds | no | 1-1/4 |
| 3×#1 + 1×#6 | THHN | EMT | 1-1/4 | 0.5193 | 1.4960 | 40 | 0.59840 | 34.71 | accepted | no | 1-1/4 |
| 3×#1/0 + 1×#6 | THHN | EMT | 1-1/4 | 0.6072 | 1.4960 | 40 | 0.59840 | 40.59 | exceeds | no | 1-1/2 |
| 3×#1/0 + 1×#6 | THHN | EMT | 1-1/2 | 0.6072 | 2.0360 | 40 | 0.81440 | 29.82 | accepted | no | 1-1/2 |
| 3×#2/0 + 1×#6 | THHN | EMT | 1-1/2 | 0.7176 | 2.0360 | 40 | 0.81440 | 35.25 | accepted | no | 1-1/2 |
| 3×#3/0 + 1×#6 | THHN | EMT | 1-1/2 | 0.8544 | 2.0360 | 40 | 0.81440 | 41.96 | exceeds | no | 2 |
| 3×#3/0 + 1×#6 | THHN | EMT | 2 | 0.8544 | 3.3560 | 40 | 1.34240 | 25.46 | accepted | no | 2 |
The unchanged fourth wire still matters
Every comparison includes the fixed #6. None of these full lists has equal insulated areas, so no Note 7 rounding is used. The separate ampacity lookup is available in the guide; it is not used to infer copper versus aluminum choices, panel ratings or terminal compatibility from these fill results.
Pool fill geometry: check the smallest section instead of averaging sizes
How should two different assumed raceway sections be compared geometrically? Use the same three #4 plus one #10 THHN in both PVC80 sections, one 1 inch and the other 3/4 inch. Evaluate each denominator separately; no pool installation layout or material requirement is prescribed.
A pass in one section does not describe the other
The wire total is 3 × 0.0824 + 0.0211 = 0.2683 in². A 1-inch PVC80 section has a 0.2752 in² budget and accepts it. The 3/4-inch section has a 0.1636 in² budget and rejects the same list. Combining interior areas, averaging nominal sizes or averaging the two percentages would describe neither section.
Change the section that fails
Changing only the larger section from 1 to 1-1/4 inches lowers its fill but leaves the 3/4-inch comparison unchanged. Changing the smaller section to 1 inch makes both area comparisons pass. The table includes 1-1/4 inch to show why extra area elsewhere cannot alter the failing denominator.
Reproducible boundary rows
| Conductors | Insulation | Conduit | Size (in) | Wire area (in²) | Raceway area (in²) | Tier (%) | Budget (in²) | Fill (%) | Result | Note 7 | Smallest size (in) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 3×#4 + 1×#10 | THHN | PVC80 | 3/4 | 0.2683 | 0.4090 | 40 | 0.16360 | 65.60 | exceeds | no | 1 |
| 3×#4 + 1×#10 | THHN | PVC80 | 1 | 0.2683 | 0.6880 | 40 | 0.27520 | 39.00 | accepted | no | 1 |
| 3×#4 + 1×#10 | THHN | PVC80 | 1-1/4 | 0.2683 | 1.2370 | 40 | 0.49480 | 21.69 | accepted | no | 1 |
| 3×#3 + 1×#8 | THHN | PVC80 | 3/4 | 0.3285 | 0.4090 | 40 | 0.16360 | 80.32 | exceeds | no | 1-1/4 |
| 3×#3 + 1×#8 | THHN | PVC80 | 1 | 0.3285 | 0.6880 | 40 | 0.27520 | 47.75 | exceeds | no | 1-1/4 |
| 3×#3 + 1×#8 | THHN | PVC80 | 1-1/4 | 0.3285 | 1.2370 | 40 | 0.49480 | 26.56 | accepted | no | 1-1/4 |
Use a second list to locate a different bottleneck
Three #3 plus one #8 total 0.3285 in². That list fails even in the 1-inch section and first passes at 1-1/4 inches. Recheck all declared sections whenever the wire list changes. These separate area checks do not model fittings, bend radius, transitions, pulling force or pool-specific electrical requirements.
Water-heater fill geometry: one, two or three repeated conductor groups
How does the minimum EMT size change when an entire assumed group is repeated? Use a group of two #6 THHN plus one #10 THHN. Repeat every member of the group, including the smaller conductor; no equipment count or wiring requirement is implied.
Scale the whole group
One group occupies 2 × 0.0507 + 0.0211 = 0.1225 in². Two groups occupy 0.2450 in² and three occupy 0.3675 in². All three cases have at least three conductors and therefore retain the 40% base tier. The totals scale linearly, but the first accepted trade size changes in discrete steps.
Three different boundaries
One group exceeds the 1/2-inch EMT budget of 0.1216 in² by 0.0009 in². Two groups exceed the 3/4-inch budget of 0.2132 in². Three groups exceed the 1-inch budget of 0.3456 in². Their first accepted EMT sizes are respectively 3/4, 1 and 1-1/4 inches, as the adjacent fail/pass rows show.
Reproducible boundary rows
| Conductors | Insulation | Conduit | Size (in) | Wire area (in²) | Raceway area (in²) | Tier (%) | Budget (in²) | Fill (%) | Result | Note 7 | Smallest size (in) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 2×#6 + 1×#10 | THHN | EMT | 1/2 | 0.1225 | 0.3040 | 40 | 0.12160 | 40.30 | exceeds | no | 3/4 |
| 2×#6 + 1×#10 | THHN | EMT | 3/4 | 0.1225 | 0.5330 | 40 | 0.21320 | 22.98 | accepted | no | 3/4 |
| 4×#6 + 2×#10 | THHN | EMT | 3/4 | 0.2450 | 0.5330 | 40 | 0.21320 | 45.97 | exceeds | no | 1 |
| 4×#6 + 2×#10 | THHN | EMT | 1 | 0.2450 | 0.8640 | 40 | 0.34560 | 28.36 | accepted | no | 1 |
| 6×#6 + 3×#10 | THHN | EMT | 1 | 0.3675 | 0.8640 | 40 | 0.34560 | 42.53 | exceeds | no | 1-1/4 |
| 6×#6 + 3×#10 | THHN | EMT | 1-1/4 | 0.3675 | 1.4960 | 40 | 0.59840 | 24.57 | accepted | no | 1-1/4 |
Why multiplying only the large wires is different
The third group adds two #6 and one #10, not just two #6. Leaving that last #10 out would remove 0.0211 in² from the declared input and answer a different question. This exercise only totals assumed individual conductors; it does not establish how many circuits may share a raceway or determine ampacity adjustments.
Pump fill geometry: one, two and three conductors use different budgets
Why does doubling the conductor count require a fresh budget calculation? Hold #6 THHN and PVC40 fixed, then evaluate one, two and three individual conductors. The pump label is only context for the arithmetic; no jacketed pump-cable dimensions are supplied.
The denominator stays fixed but the tier changes
In 1/2-inch PVC40, the interior area is 0.2850 in². One conductor uses a 53% base budget of 0.15105 in²; two use 31%, or 0.08835 in²; three use 40%, or 0.11400 in². A first-conductor pass cannot be multiplied into a two-conductor allowance.
The two-conductor boundary needs the quotient
Two #6 occupy 0.1014 in². Their 31% budget quotient is approximately 1.74260, below the 1.8 needed to accept two under Note 7. They first pass at 3/4-inch PVC40. Three #6 total 0.1521 in² and also first pass at 3/4 inch, despite having a different base tier.
Reproducible boundary rows
| Conductors | Insulation | Conduit | Size (in) | Wire area (in²) | Raceway area (in²) | Tier (%) | Budget (in²) | Fill (%) | Result | Note 7 | Smallest size (in) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1×#6 | THHN | PVC40 | 1/2 | 0.0507 | 0.2850 | 53 | 0.15105 | 17.79 | accepted | no | 1/2 |
| 1×#6 | THHN | PVC40 | 3/4 | 0.0507 | 0.5080 | 53 | 0.26924 | 9.98 | accepted | no | 1/2 |
| 2×#6 | THHN | PVC40 | 1/2 | 0.1014 | 0.2850 | 31 | 0.08835 | 35.58 | exceeds | no | 3/4 |
| 2×#6 | THHN | PVC40 | 3/4 | 0.1014 | 0.5080 | 31 | 0.15748 | 19.96 | accepted | no | 3/4 |
| 3×#6 | THHN | PVC40 | 1/2 | 0.1521 | 0.2850 | 40 | 0.11400 | 53.37 | exceeds | no | 3/4 |
| 3×#6 | THHN | PVC40 | 3/4 | 0.1521 | 0.5080 | 40 | 0.20320 | 29.94 | accepted | no | 3/4 |
| 1×#1/0 | THHN | PVC40 | 1/2 | 0.1855 | 0.2850 | 53 | 0.15105 | 65.09 | accepted | yes | 1/2 |
| 2×#1/0 | THHN | PVC40 | 1 | 0.3710 | 0.8320 | 31 | 0.25792 | 44.59 | exceeds | no | 1-1/4 |
| 2×#1/0 | THHN | PVC40 | 1-1/4 | 0.3710 | 1.4530 | 31 | 0.45043 | 25.53 | accepted | no | 1-1/4 |
Single-conductor Note 7 is visible too
One #1/0 THHN occupies 0.1855 in². In 1/2-inch PVC40 the 53% quotient is approximately 0.814286, so the model accepts one despite actual fill above 53%. Two such conductors first pass at 1-1/4 inch. Count refers to the declared individual conductors; a complete cable would require its own exterior envelope and cable calculation.
RELATED TOOLS
Data is transcribed from NEC 2023 Chapter 9 into versioned tables, with calculations performed by code. Automated checks cover selected outputs and consistency; not every cell has been independently reviewed. WireFillChart is not affiliated with or endorsed by NFPA. Verify against the code adopted by your local AHJ.