WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · NEC GUIDE

NEC Chapter 9 Table 5 Conductor Dimensions

NEC Chapter 9 Table 5 gives cross-sectional area for every insulated conductor type. Includes THHN, THWN-2, XHHW, RHH/RHW, TW from 14 AWG through 1000 kcmil.

·4 MIN READ·EDITORIAL

NEC Chapter 9 Table 5 of NFPA 70 (2023) lists approximate cross-sectional area for every common insulated conductor type at every standard AWG and kcmil size. The table is the second half of the conduit fill calculation: multiply the count of each conductor by its Table 5 area, sum, and compare against Table 4 multiplied by the Table 1 fill percentage. Get Table 5 right and the rest is arithmetic.

How Table 5 Is Organized

The full table runs from 18 AWG fixture wire through 2000 kcmil power cable. Columns are grouped by insulation family:

  • TBS, SA, SIS, FEP, FEPB, PFA, RHH, RHW, RHW-2, THHW, THW, THW-2
  • TFE, PFAH, Z
  • TW
  • TFN, TFFN
  • THHN, THWN, THWN-2, MTW
  • XHHW, XHHW-2, ZW

For practical conduit work, the THHN/THWN-2 column and the XHHW column are by far the most-used. RHH/RHW comes up in older buildings and some industrial work; TW shows up in cord and direct-buried legacy systems.

Conductor Areas (in^2) - Most-Used Insulations

Size THHN / THWN-2 XHHW RHH / RHW (no jacket) TW
14 AWG 0.0097 0.0139 0.0209 0.0139
12 AWG 0.0133 0.0181 0.0260 0.0181
10 AWG 0.0211 0.0243 0.0333 0.0243
8 AWG 0.0366 0.0437 0.0556 0.0437
6 AWG 0.0507 0.0590 0.0726 0.0726
4 AWG 0.0824 0.0814 0.0973 0.0973
3 AWG 0.0973 0.0962 0.1134 0.1134
2 AWG 0.1158 0.1146 0.1333 0.1333
1 AWG 0.1562 0.1534 0.1901 0.1901
1/0 0.1855 0.1825 0.2223 0.2223
2/0 0.2223 0.2190 0.2624 0.2624
3/0 0.2679 0.2642 0.3117 0.3117
4/0 0.3237 0.3197 0.3718 0.3718
250 kcmil 0.3970 0.3904 0.4596 0.4596
300 kcmil 0.4608 0.4536 0.5281 0.5281
350 kcmil 0.5242 0.5166 0.5958 0.5958
400 kcmil 0.5863 0.5782 0.6619 0.6619
500 kcmil 0.7073 0.6984 0.7901 0.7901
600 kcmil 0.8676 0.8709 0.9729 -
750 kcmil 1.0496 1.0532 1.1882 -
1000 kcmil 1.3478 1.3478 1.5482 -

Values are from NEC 2023 Chapter 9 Table 5. Note that at small sizes (14 - 4 AWG) the THHN/THWN-2 column is the smallest of the four; at large sizes the differences narrow because the conductor metal dominates and the insulation jacket is a smaller percentage of overall diameter.

Why Insulation Type Matters

  • THHN / THWN-2 uses thin nylon jacket over PVC insulation - the most compact mainstream insulation
  • XHHW / XHHW-2 uses cross-linked polyethylene without a separate jacket - slightly bulkier than THHN at small sizes, equal at large
  • RHH / RHW uses thermoset rubber - heaviest insulation, common in legacy industrial
  • TW uses thick PVC without nylon jacket - rated only 60C

For modern installations, THHN/THWN-2 dominates because it lets you fit more conductors per conduit. See deep dives at THHN, THWN-2, XHHW, and RHH.

Worked Example

Goal: Fit 6 x 4/0 THHN + 1 x 2 AWG THHN EGC in EMT.

  • 6 x 4/0 THHN = 6 x 0.3237 = 1.9422 in^2
  • 1 x 2 AWG THHN = 0.1158 in^2
  • Total = 2.058 in^2

Need EMT interior area at 40% fill of at least 2.058 in^2. Table 4 EMT: 2" = 1.342 in^2, 2-1/2" = 2.343 in^2. 2-1/2" EMT is the minimum. (For RMC the answer changes - 2-1/2" RMC has only 1.946 in^2 at 40%, so you would need 3" RMC.)

Common Pitfalls

  • Looking up the wrong column. XHHW and THHN are not identical at every size - check the column header carefully.
  • Forgetting EGC area. The equipment grounding conductor is a conductor for fill purposes. A 6-circuit feeder with 6 hots, 6 neutrals, and 1 EGC has 13 conductors in the fill calculation.
  • Using bare conductor area. Table 5 is for insulated conductors. Bare conductors (for example, bare equipment grounding) use Table 8 dimensions.

Cross-References

  • NEC Chapter 9 Table 5A - compact aluminum dimensions
  • NEC Chapter 9 Table 8 - bare conductor dimensions (use for bare EGC)
  • Annex C - pre-computed fill counts for identical conductors
  • NEC Chapter 9 Table 1 - the fill percentages
  • NEC Chapter 9 Table 4 - conduit interior areas; see Table 4 guide

How WireFillChart Implements It

Our conduit fill calculator stores the full Table 5 dataset for every insulation type from 14 AWG to 1000 kcmil. Mix and match insulations - the calculator multiplies each conductor's individual area and sums correctly. Bare EGCs reference Table 8. For background, see AWG explained and kcmil explained.

Related

FIG. 99

FAQ

Yes - NEC Table 5 lists THHN, THWN-2, and MTW in the same column. Their nylon-jacketed PVC insulation has identical dimensions. XHHW and XHHW-2 share another column with very similar values.