Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · DEFINITION

What is RHH and RHW Wire?

RHH, RHW, and RHW-2 are rubber-insulated building wires used in branch circuits and feeders. NEC Article 310 and Table 5 govern dimensions and ampacity.

·3 MIN READ·EDITORIAL

RHH and RHW are rubber-insulated single conductors used for branch-circuit and feeder wiring. RHH stands for Rubber, Heat-resistant (90°C dry). RHW adds water resistance — Rubber, Heat- and Water-resistant — rated 75°C wet and 90°C dry. The modern RHW-2 is rated 90°C in both wet and dry locations. All three are listed in NEC Table 310.4(A) and sized using NEC Chapter 9 Table 5.

Construction

  • Conductor: Soft-drawn copper, solid or stranded
  • Insulation: Cross-linked synthetic rubber (or thermoset elastomer)
  • Jacket: Optional moisture- and flame-resistant outer covering on the W variants
  • Temperature ratings:
    • RHH — 90°C dry only
    • RHW — 75°C wet / 90°C dry
    • RHW-2 — 90°C wet and dry

The defining feature of the RH family is its thick rubber insulation, which makes the finished conductor noticeably larger than a comparable THHN/THWN-2 of the same AWG.

Cross-sectional area (NEC Chapter 9 Table 5)

This is the practical takeaway for conduit fill calculations — RHW-2 takes up far more space:

AWG RHW-2 area in² THHN area in² Ratio
14 0.0209 0.0097 2.15×
12 0.0260 0.0133 1.96×
10 0.0333 0.0211 1.58×
8 0.0556 0.0366 1.52×
6 0.0726 0.0507 1.43×
4 0.0973 0.0824 1.18×
2 0.1333 0.1158 1.15×
1/0 0.2026 0.1825 1.11×

A 1" EMT (interior area 0.864 in²) holds 9 of 12 AWG THHN at 40% fill, but only 6 of 12 AWG RHW-2. Always cross-check on the wire fill chart when substituting insulations.

NEC code reference

  • NEC 310.4(A) — conductor insulation type listings
  • NEC Chapter 9 Table 5 — actual dimensions for fill math
  • NEC Chapter 9 Table 8 — conductor properties (DC resistance, area)
  • NEC Table 310.16 — ampacity at 60/75/90°C

Ampacity termination is still limited by the 75°C column for most equipment under 100 A (NEC 110.14(C)) — the 90°C rating is used only for ambient and derating corrections.

Common applications

  • Service entrance conductors (RHW, RHW-2)
  • Branch circuits and feeders in damp or wet locations
  • Industrial control wiring where rubber's flexibility helps in cold weather
  • Mining and quarry installations (rubber survives abrasion)
  • Replacement in older buildings already wired with rubber-insulated conductors

Trade-offs vs THHN/THWN-2

Property RHW-2 THHN/THWN-2
Insulation Thermoset rubber Thermoplastic (PVC + nylon)
Cold flexibility Excellent Stiffens below freezing
Outer diameter Large Compact
Cost per foot Higher Lower
Fill efficiency Poor Good

For most new commercial work, THHN/THWN-2 wins on cost and fill. RH-family wire is chosen when flexibility at low temperatures or specific listings (mine power cable, industrial heat exposure) are required.

Quick reference

Type Wet rating Dry rating Use
RHH 90°C Dry only
RHW 75°C 90°C Wet/dry, 75°C wet
RHW-2 90°C 90°C Wet/dry, full 90°C

Related

FIG. 99

FAQ

RHH is rated 90°C in dry locations only. RHW adds water resistance and is rated 75°C wet, 90°C dry. RHW-2 is rated 90°C in both wet and dry.

METHODOLOGY & SOURCES

This page's figures are transcribed from NEC 2023 (NFPA 70) Chapter 9, Tables 1, 4 and 5, and checked by a version-controlled automated test suite — they are not signed off by a licensed professional. WireFillChart is an independent reference, not affiliated with or endorsed by NFPA. Always verify against the code edition adopted by your local authority having jurisdiction (AHJ).

WireFillChart Editorial Team·EDITORIAL·