Box Fill Calculator
Cubic-inch box-fill computation per NEC 314.16(B). Counts conductors, internal clamps, device yokes, equipment-grounding conductors, and support fittings — all in the largest-AWG terms NEC requires.
FIG. 02 — INPUTS
FIG. 03 — RESULT
Per-conductor allowance (NEC Table 314.16(B))
- #18 = 1.5 in³
- #16 = 1.75 in³
- #14 = 2 in³
- #12 = 2.25 in³
- #10 = 2.5 in³
- #8 = 3 in³
- #6 = 5 in³
HOW NEC 314.16(B) COUNTS CONDUCTORS
(B)(1) — Conductor fill
Each conductor that originates outside the box and terminates or passes through the box counts as one. Conductors that originate and terminate inside (pigtails) do not count.
(B)(2) — Cable clamps
All internal cable clamps together count as a single conductor of the largest AWG entering the box. External connectors mounting through a knockout do not count.
(B)(3) — Support fittings
Each luminaire stud, fixture hickey, or similar support fitting counts as a single conductor of the largest AWG entering the box.
(B)(4) — Device yokes (straps)
Each device yoke counts as TWO conductors of the largest AWG connected to that device. A duplex receptacle on one yoke = 2×.
(B)(5) — Equipment grounding conductors
All EGCs together count as a single conductor of the largest EGC AWG. One additional isolated EGC counts as one more.
Multiply by the right AWG allowance
Convert each conductor count into cubic inches using NEC Table 314.16(B): #14 = 2.0 in³, #12 = 2.25 in³, #10 = 2.5 in³, #8 = 3.0 in³, #6 = 5.0 in³. Sum everything. Pick a box that meets or exceeds the result.