WIRE·FILL·CHARTNEC 2023 · CH. 9
FIG. 01 — BOX FILL CALCULATOR

Box Fill Calculator

Cubic-inch box-fill computation per NEC 314.16(B). Counts conductors, internal clamps, device yokes, equipment-grounding conductors, and support fittings — all in the largest-AWG terms NEC requires.

FIG. 02 — INPUTS

Conductors entering the box
Box-fill extras

FIG. 03 — RESULT

Required volume
22.50 in³
Box volume
21.00 in³
OVER — need 1.50 in³ more (use a larger box)

Per-conductor allowance (NEC Table 314.16(B))

  • #18 = 1.5 in³
  • #16 = 1.75 in³
  • #14 = 2 in³
  • #12 = 2.25 in³
  • #10 = 2.5 in³
  • #8 = 3 in³
  • #6 = 5 in³
FIG. 04

HOW NEC 314.16(B) COUNTS CONDUCTORS

(B)(1) — Conductor fill

Each conductor that originates outside the box and terminates or passes through the box counts as one. Conductors that originate and terminate inside (pigtails) do not count.

(B)(2) — Cable clamps

All internal cable clamps together count as a single conductor of the largest AWG entering the box. External connectors mounting through a knockout do not count.

(B)(3) — Support fittings

Each luminaire stud, fixture hickey, or similar support fitting counts as a single conductor of the largest AWG entering the box.

(B)(4) — Device yokes (straps)

Each device yoke counts as TWO conductors of the largest AWG connected to that device. A duplex receptacle on one yoke = 2×.

(B)(5) — Equipment grounding conductors

All EGCs together count as a single conductor of the largest EGC AWG. One additional isolated EGC counts as one more.

Multiply by the right AWG allowance

Convert each conductor count into cubic inches using NEC Table 314.16(B): #14 = 2.0 in³, #12 = 2.25 in³, #10 = 2.5 in³, #8 = 3.0 in³, #6 = 5.0 in³. Sum everything. Pick a box that meets or exceeds the result.

FIG. 05

FREQUENTLY ASKED QUESTIONS

Box fill (NEC 314.16) measures cubic-inch volume inside a junction box or device box, summing conductor allowances, clamps, yokes, EGCs and support fittings. Conduit fill (NEC Chapter 9) measures cross-sectional area in a raceway, capping conductor area at 53%/31%/40% by count. They use different units (in³ vs in²) and entirely different tables.