Flex Conduit Fill Chart (FMC, LFNC, ENT)

Maximum conductors for flexible raceway types per NEC 2023.

Flexible raceway types use the same NEC Chapter 9 fill percentages as rigid conduit (53/31/40), but their interior areas differ from the rigid equivalents. Switch types below to compare FMC, LFNC-B, and ENT. For mixed-conductor jobs use the conduit fill calculator.

TABLE · FMC × THHN
NEC 2023 · CH. 9
Maximum number of THHN (90°C dry) conductors per FMC — Flexible Metal Conduit trade size at NEC fill limits.
TRADE →
WIRE ↓
1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG1321335276134202291396518
12 AWG91624385598147212289377
10 AWG6101524356193134182238
8 AWG3581320355377105137
6 AWG14610142538557599
4 AWG123691523344661
3 AWG113571320293951
2 AWG112461116243343
1 AWG11134812182432
1/01124710152027
2/0111358121722
3/0111247101418
4/01114681115
250111347912
30011246810
3501113579
4001113468
500112357
600111345
70011235
75011234
80011134
90011134
100011123

FMC — Flexible Metal Conduit × THHN (90°C dry) · NEC 2023 Ch.9 Tables 4 & 5 · 40% (3+), 31% (2), 53% (1)

FIG. 02

NOTES & CONTEXT

FMC — Flexible Metal Conduit (Article 348)

Greenfield. Used for short whip drops to motors, transformers, and luminaires where rigid conduit can't flex. Note: FMC over 6 ft long can't be used as the equipment ground — pull a separate EGC.

LFNC — Liquidtight Flexible Nonmetallic (Article 356)

LFNC-B (the smooth-bore variety) is rated for direct sunlight, oil, and wet locations — the go-to for outdoor HVAC condensers and submersible pump whips. LFNC sizes only go up to 2" trade size; for larger flex needs use LFMC (Article 350).

ENT — Electrical Nonmetallic Tubing (Article 362)

Smurf tube. Lightweight blue plastic for inside walls of buildings up to 3 stories. ENT's interior area matches PVC Schedule 40 — easy to remember. Restricted to dry locations and concealed work in most occupancies.

Common flex conduit fill scenarios

  • HVAC condenser whip, 4 × 10 AWG THHN: 3/4" LFNC fits with room to spare.
  • Motor connection, 3 × 4 AWG THHN + ground: 1" FMC.
  • Residential rough-in, 6 circuits of 12-2 NM through ENT: NM cable counts differently — use bundling rules (NEC 334.80), not conduit fill.
FIG. 03

FAQ

FMC (Article 348) is interlocked galvanized steel — for short dry whips to motors and luminaires. LFNC-B (Article 356) is liquidtight smooth-bore plastic — UV and oil-rated for outdoor HVAC and pump connections. ENT (Article 362) is lightweight blue corrugated plastic for concealed dry indoor work up to three stories.