Flex Conduit Fill Chart (FMC, LFNC, ENT)

Maximum conductors for flexible raceway types per NEC 2023.

Flexible raceway types use the same NEC Chapter 9 fill percentages as rigid conduit (53/31/40), but their interior areas differ from the rigid equivalents. Switch types below to compare FMC, LFNC-B, and ENT. For mixed-conductor jobs use the conduit fill calculator.

TABLE · FMC × THHN
NEC 2023 · CH. 9
  • 1/2" FMC9 wires
  • 3/4" FMC16 wires
  • 1" FMC24 wires
  • 1-1/4" FMC38 wires
  • 1-1/2" FMC56 wires
  • 2" FMC98 wires
  • 2-1/2" FMC147 wires
  • 3" FMC212 wires
  • 3-1/2" FMC289 wires
  • 4" FMC378 wires

FMC — Flexible Metal Conduit × THHN (90°C dry) · NEC 2023 Ch.9 Tables 4 & 5 · 40% (3+), 31% (2), 53% (1)

FIG. 02

NOTES & CONTEXT

FMC — Flexible Metal Conduit (Article 348)

Greenfield. Used for short whip drops to motors, transformers, and luminaires where rigid conduit can't flex. Note: FMC over 6 ft long can't be used as the equipment ground — pull a separate EGC.

LFNC — Liquidtight Flexible Nonmetallic (Article 356)

LFNC-B (the smooth-bore variety) is rated for direct sunlight, oil, and wet locations — the go-to for outdoor HVAC condensers and submersible pump whips. LFNC sizes only go up to 2" trade size; for larger flex needs use LFMC (Article 350).

ENT — Electrical Nonmetallic Tubing (Article 362)

Smurf tube. Lightweight blue plastic for inside walls of buildings up to 3 stories. ENT's interior area matches PVC Schedule 40 — easy to remember. Restricted to dry locations and concealed work in most occupancies.

Common flex conduit fill scenarios

  • HVAC condenser whip, 4 × 10 AWG THHN: 3/4" LFNC fits with room to spare.
  • Motor connection, 3 × 4 AWG THHN + ground: 1" FMC.
  • Residential rough-in, 6 circuits of 12-2 NM through ENT: NM cable counts differently — use bundling rules (NEC 334.80), not conduit fill.
FIG. 03

FAQ

FMC (Article 348) is interlocked galvanized steel — for short dry whips to motors and luminaires. LFNC-B (Article 356) is liquidtight smooth-bore plastic — UV and oil-rated for outdoor HVAC and pump connections. ENT (Article 362) is lightweight blue corrugated plastic for concealed dry indoor work up to three stories.