NEC Circular Mils Table (AWG & kcmil)

Circular-mil (CM / kcmil) area, conductor diameter, and metric mm² for every wire size from 14 AWG to 1000 kcmil, per NEC 2023 Chapter 9, Table 8 (solid copper).

TABLE · CIRCULAR MILS BY SIZE
NEC 2023 · CH.9 · TBL 8
Circular mils, diameter, and mm² by AWG / kcmil size per NEC Chapter 9 Table 8.
SizeDiameter (mil)Area (circular mils)Area (kcmil)Area (mm²)
14 AWG64.14,1074.112.08
12 AWG80.86,5306.533.31
10 AWG101.910,38010.45.26
8 AWG128.516,51016.58.37
6 AWG162.026,24026.213.30
4 AWG204.341,74041.721.15
3 AWG229.452,62052.626.67
2 AWG257.666,36066.433.62
1 AWG289.383,69083.742.41
1/0 AWG324.9105,600105.653.49
2/0 AWG364.8133,100133.167.43
3/0 AWG409.6167,800167.885.01
4/0 AWG460.0211,600211.6107.20
250 kcmil500.0250,000250.0126.70
300 kcmil547.7300,000300.0152.00
350 kcmil591.6350,000350.0177.40
400 kcmil632.5400,000400.0202.70
500 kcmil707.1500,000500.0253.40
600 kcmil774.6600,000600.0304.00
700 kcmil836.7700,000700.0354.70
750 kcmil866.0750,000750.0380.00
800 kcmil894.4800,000800.0405.40
900 kcmil948.7900,000900.0456.00
1000 kcmil1000.01,000,0001000.0506.70

NEC 2023 · Chapter 9, Table 8 · solid copper · CM = (diameter in mils)²

How to read the circular mils table

Find your wire size in the left column. The circular mils column is the bare copper cross-sectional area used in NEC Chapter 9, Table 8 — the value the code uses for resistance, voltage-drop, and (for the fine-print notes) parallel-conductor rules. For sizes above 4/0 AWG the industry switches from gauge numbers to kcmil (thousands of circular mils): a 250 kcmil conductor is simply 250,000 circular mils.

Circular mils vs square inches vs mm²

These three areas measure different things and are not interchangeable. Circular mils (this table) is the bare conductor metal area. mm² is the metric equivalent of that same copper area (1 CM = 0.0005067 mm²). The square-inch area used for conduit fill is different again — it is the insulated conductor's outside area from NEC Chapter 9, Table 5, which includes the insulation jacket. Never plug a circular-mil value into a conduit-fill calculation.

Why circular mils matter

Ampacity climbs with copper area, so circular mils are the cleanest way to compare conductors and to size parallel sets: two 250 kcmil conductors in parallel give 500,000 CM, matching a single 500 kcmil run for resistance. The measure also drives voltage-drop math — resistance is inversely proportional to circular-mil area. For the insulated dimensions that govern how many wires fit in a raceway, use the EMT fill chart or the live conduit fill calculator instead.

FIG. 02

FREQUENTLY ASKED QUESTIONS

A circular mil (CM) is the area of a circle exactly 1 mil (0.001 inch) in diameter. Because area scales with the square of diameter, the circular-mil area of a round conductor equals its diameter in mils, squared — no π needed. Example: 12 AWG copper is 80.8 mils in diameter, so 80.8² ≈ 6,530 CM (NEC Chapter 9, Table 8).

METHODOLOGY & SOURCES

Circular-mil and diameter values are transcribed from NEC 2023 (NFPA 70) Chapter 9, Table 8 (solid copper); mm² equivalents are the IEC conversions. WireFillChart is an independent reference, not affiliated with or endorsed by NFPA. Verify against the code edition adopted by your local authority having jurisdiction (AHJ).

WireFillChart Editorial Team·EDITORIAL··All NEC references →