Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · NEC GUIDE

NEC Table 310.16 Ampacity Explained

Base copper ampacity columns and the previously checked 75°C copper/aluminum subset; no installation or breaker sizing approval.

·3 MIN READ·EDITORIAL

This reference lists the base ampacity values used by the site’s examples. It does not choose conductors or overcurrent protection for an installation. Read the temperature column together with the actual conductor, terminal and installation conditions.

Copper base ampacity lookup

Size (AWG/kcmil) 60C (TW, UF) 75C (THW, THWN, XHHW wet) 90C (THHN, THWN-2, XHHW-2, RHH)
14 15 20 25
12 20 25 30
10 30 35 40
8 40 50 55
6 55 65 75
4 70 85 95
3 85 100 115
2 95 115 130
1 110 130 145
1/0 125 150 170
2/0 145 175 195
3/0 165 200 225
4/0 195 230 260
250 215 255 290
300 240 285 320
350 260 310 350
500 320 380 430
750 400 475 535
1000 455 545 615

Verified 75°C feeder comparison

The following subset is the ampacity source used by our sub-panel application page. Copper values agree with the copper table above and Southwire SPEC10000, Table 2. Aluminum values were checked against Southwire SPEC10012, Table 2 on 2026-10-18; the manufacturer identifies its ampacities as based on 2023 NEC Table 310.16. Missing sizes are not estimated from a percentage of copper.

Size (AWG/kcmil) Copper 75°C (A) Aluminum 75°C (A)
6 65 50
4 85 65
3 100 —
2 115 90
1 130 100
1/0 150 120
2/0 175 135
3/0 200 155
4/0 230 180
250 255 205

These are base ampacities with 75°C-compatible conductors and terminals, not automatically permitted breaker ratings. Apply temperature correction and conductor-count adjustment separately. For 240.4(B), 240.4(D) and dwelling exceptions, use the official NFPA 70 access page. No next-standard-breaker exception is applied in our feeder comparison.

The table is not a breaker recommendation

For #12 copper, the displayed columns are 20A at 60°C, 25A at 75°C and 30A at 90°C. A column value alone does not approve that breaker rating. A 90°C insulation marking does not establish the terminal rating of connected equipment.

For #3 copper, the 75°C column is 100A; #1 copper is 130A. The sub-panel comparison varies assumed conductor areas; it does not select conductors by ampacity.

Scope

Temperature correction, conductor-count adjustment, protection, load calculations and special exceptions require separate assessment under the actual adopted rules and equipment instructions. No adjustment-factor table or exception interpretation is supplied here. Source comparison already recorded above is not a claim that the final 2023 edition has been independently checked cell by cell.

The fill calculator uses conductor and raceway areas; it does not calculate ampacity.

What is ampacity? · Sub-panel examples · Conduit fill calculator · Table 1 · Table 4 · Table 5

METHODOLOGY & SOURCES

Data is transcribed from NEC 2023 Chapter 9 into versioned tables, with calculations performed by code. Automated checks cover selected outputs and consistency; not every cell has been independently reviewed. WireFillChart is not affiliated with or endorsed by NFPA. Verify against the code adopted by your local AHJ.

Hommer Zhao·EDITORIAL·