1-1/2" PVC-40 Conduit Fill Chart
How many wires fit in 1-1/2" PVC-40 (PVC Schedule 40). Maximum conductor counts per AWG using the applicable Table 1 tier and documented Note 7 rule.
MAXIMUM CONDUCTORS BY WIRE GAUGE
Table 1 fill tiers (53% / 31% / 40%) and Note 7 count rounding. 1-1/2" PVC-40 interior area = 1.9860 in².
XHHW-2: — Data pending verification; no capacity values provided. RHH/RHW-2 values apply without outer covering. Counts use 53% for one, 31% for two, and 40% for three or more, with Note 7 rounding for identical conductors in every tier.
| AWG | THHN / THWN-2 | XHHW-2 | RHH / RHW-2 (without outer covering) |
|---|---|---|---|
| #14 | 82 | — | 38 |
| #12 | 59 | — | 30 |
| #10 | 37 | — | 24 |
| #8 | 21 | — | 14 |
| #6 | 15 | — | 11 |
| #4 | 9 | — | 8 |
| #3 | 8 | — | 7 |
| #2 | 7 | — | 6 |
| #1 | 5 | — | 4 |
| #1/0 | 4 | — | 3 |
| #2/0 | 3 | — | 3 |
| #4/0 | 2 | — | 1 |
WORKED EXAMPLE & NEC REFERENCES
The NEC numbers behind 1-1/2" PVC-40
NEC 2023 Chapter 9, Table 4 lists the interior cross-sectional area of every standard trade size for each conduit family. For 1-1/2" PVC-40 (Article 352), the total 100% area is 1.9860 in². The allowable conductor fill is then derived from Table 1: 53% for a single conductor (1.0526 in²), 31% for two (0.6157 in²), and 40% for three or more (0.7944 in²).
Capacity at this size
The 1-1/2" PVC-40 40% budget is 0.7944 in². THHN maximum counts are #12: 59; #10: 37; #8: 21. At the #12 maximum, actual fill is 39.51%, using the 40% tier; Note 7 is not applied.
Adjacent trade sizes
1-1/4" PVC-40 has a 40% budget of 0.5812 in², a change of -0.2132 in². Its THHN counts are #12: 43; #10: 27; #8: 16.
2" PVC-40 has a 40% budget of 1.3164 in², a change of 0.5220 in². Its THHN counts are #12: 99; #10: 62; #8: 36.
Note 7 boundaries for this conduit
#14: 82 conductors at the 40% tier, 40.05% actual fill; #2: 7 conductors at the 40% tier, 40.82% actual fill; #4/0: 2 conductors at the 31% tier, 32.60% actual fill
These are area calculations. Physical clearance, bends, pulling tension and ampacity need separate checks. A larger size must be recalculated with the actual conductor mix; a single trade-size increase is not guaranteed to suffice.
Source citations
NFPA 70 (2023) — National Electrical Code. Chapter 9, Table 1: percent of cross section of conduit and tubing for conductors. Table 4: dimensions and percent area of conduit and tubing (Article 352). Table 5: dimensions of insulated conductors.
Calculation process — THHN counts and boundaries
Divide the allowed conduit area by one insulated conductor's area. The engine checks one conductor at 53%, two at 31%, and three or more at 40%. For identical conductors in any of these tiers, a fractional quotient of at least 0.8 rounds up under the documented Chapter 9 Note 7 rule.
The table shows the tier of the accepted maximum, its rounded display quotient, and actual fill. A Note 7 result can exceed its applicable percentage budget; actual fill is shown unchanged. Different conductor areas use strict area comparison; different IDs with equal insulated areas share the Note 7 group. Quotients are calculated from unrounded values; budgets and quotients display at least six significant digits, and ≈ marks rounded results. A zero means no count is accepted by this area-based rule; it is not a physical fit test.
| THHN AWG | One wire in² | Tier | Budget ÷ wire area | Maximum | Actual fill | One more | Max in 2" |
|---|---|---|---|---|---|---|---|
| #14 | 0.0097 | 40% | 0.79440000 ÷ 0.0097 ≈ 81.896907 | 82 (Note 7) | 40.05% | 83: 40.54% — exceeds allowance | 135 |
| #12 | 0.0133 | 40% | 0.79440000 ÷ 0.0133 ≈ 59.729323 | 59 | 39.51% | 60: 40.18% — exceeds allowance | 99 |
| #10 | 0.0211 | 40% | 0.79440000 ÷ 0.0211 ≈ 37.649289 | 37 | 39.31% | 38: 40.37% — exceeds allowance | 62 |
| #8 | 0.0366 | 40% | 0.79440000 ÷ 0.0366 ≈ 21.704918 | 21 | 38.70% | 22: 40.54% — exceeds allowance | 36 |
| #6 | 0.0507 | 40% | 0.79440000 ÷ 0.0507 ≈ 15.668639 | 15 | 38.29% | 16: 40.85% — exceeds allowance | 26 |
| #4 | 0.0824 | 40% | 0.79440000 ÷ 0.0824 ≈ 9.6407767 | 9 | 37.34% | 10: 41.49% — exceeds allowance | 16 |
| #3 | 0.0973 | 40% | 0.79440000 ÷ 0.0973 ≈ 8.1644399 | 8 | 39.19% | 9: 44.09% — exceeds allowance | 13 |
| #2 | 0.1158 | 40% | 0.79440000 ÷ 0.1158 ≈ 6.8601036 | 7 (Note 7) | 40.82% | 8: 46.65% — exceeds allowance | 11 |
| #1 | 0.1562 | 40% | 0.79440000 ÷ 0.1562 ≈ 5.0857875 | 5 | 39.33% | 6: 47.19% — exceeds allowance | 8 |
| #1/0 | 0.1855 | 40% | 0.79440000 ÷ 0.1855 ≈ 4.2824798 | 4 | 37.36% | 5: 46.70% — exceeds allowance | 7 |
| #2/0 | 0.2223 | 40% | 0.79440000 ÷ 0.2223 ≈ 3.5735493 | 3 | 33.58% | 4: 44.77% — exceeds allowance | 6 |
| #4/0 | 0.3237 | 31% | 0.61566000 ÷ 0.3237 ≈ 1.9019462 | 2 (Note 7) | 32.60% | 3: 48.90% — exceeds allowance | 4 |
Compare all gauges in 2" PVC-40.
Keep fill and ampacity checks separate
Include all conductors present in the fill calculation, including equipment grounding conductors. Current-carrying conductor counts for ampacity adjustment follow different rules. Check terminal temperature limits, ambient correction, grounding, cable suitability and pulling conditions separately; a fill pass is not installation approval.
THWN-2 shares the supported THHN-family areas. RHH/RHW-2 values apply without outer covering; compare the table above. XHHW data remains withheld. For another insulation or a mixed pull, use the calculator below and the Table 5 guide.
TRY IT — 1-1/2" PVC-40 LIVE
Preloaded with this conduit. Change the conductor gauge, insulation, or count and read the fill in real time.
- CONDUCTORS
- 59
- WIRE AREA
- 0.785in²
- CONDUIT AREA
- 1.986in²
- GEOMETRIC JAM HINT
- —
Table 1 tier: 40%. Note 7: not applied. The displayed percentage is actual fill; acceptance concerns area only.
An accepted result is within the NEC fill limit (Chapter 9 Table 1, per this site's calculation), including Note 7 where applicable. This assesses supported conductor areas only, not ampacity, product suitability, pulling feasibility or installation approval. A confirmed over-limit result means the supported equal-area count also fails the Note 7 check.
Geometric jamming risk hint only: assumes exactly three identical round conductors and infers diameters from area. The 2.8–3.2 ratio is a screening band, not a measured probability. Bends, tolerances, friction and pulling tension are not modeled; other configurations are not assessed.
- Three or more conductors — 40% Table 1 tier; Note 7 may apply.