3/4" PVC-40 Conduit Fill Chart

How many wires fit in 3/4" PVC-40 (PVC Schedule 40). Maximum conductor counts per AWG using the applicable Table 1 tier and documented Note 7 rule.

FIG. 02

MAXIMUM CONDUCTORS BY WIRE GAUGE

Table 1 fill tiers (53% / 31% / 40%) and Note 7 count rounding. 3/4" PVC-40 interior area = 0.5080 in².

XHHW-2: — Data pending verification; no capacity values provided. RHH/RHW-2 values apply without outer covering. Counts use 53% for one, 31% for two, and 40% for three or more, with Note 7 rounding for identical conductors in every tier.

AWGTHHN / THWN-2XHHW-2RHH / RHW-2 (without outer covering)
#1421—9
#1215—8
#109—6
#85—3
#64—2
#42—1
#31—1
#21—1
#11—1
#1/01—1
#2/01—1
#4/01—0
FIG. 03

WORKED EXAMPLE & NEC REFERENCES

The NEC numbers behind 3/4" PVC-40

NEC 2023 Chapter 9, Table 4 lists the interior cross-sectional area of every standard trade size for each conduit family. For 3/4" PVC-40 (Article 352), the total 100% area is 0.5080 in². The allowable conductor fill is then derived from Table 1: 53% for a single conductor (0.2692 in²), 31% for two (0.1575 in²), and 40% for three or more (0.2032 in²).

Capacity at this size

The 3/4" PVC-40 40% budget is 0.2032 in². THHN maximum counts are #12: 15; #10: 9; #8: 5. At the #12 maximum, actual fill is 39.27%, using the 40% tier; Note 7 is not applied.

Adjacent trade sizes

1/2" PVC-40 has a 40% budget of 0.1140 in², a change of -0.0892 in². Its THHN counts are #12: 8; #10: 5; #8: 3.

1" PVC-40 has a 40% budget of 0.3328 in², a change of 0.1296 in². Its THHN counts are #12: 25; #10: 15; #8: 9.

Note 7 boundaries for this conduit

#14: 21 conductors at the 40% tier, 40.10% actual fill; #4: 2 conductors at the 31% tier, 32.44% actual fill; #4/0: 1 conductors at the 53% tier, 63.72% actual fill

These are area calculations. Physical clearance, bends, pulling tension and ampacity need separate checks. A larger size must be recalculated with the actual conductor mix; a single trade-size increase is not guaranteed to suffice.

Source citations

NFPA 70 (2023) — National Electrical Code. Chapter 9, Table 1: percent of cross section of conduit and tubing for conductors. Table 4: dimensions and percent area of conduit and tubing (Article 352). Table 5: dimensions of insulated conductors.

Calculation process — THHN counts and boundaries

Divide the allowed conduit area by one insulated conductor's area. The engine checks one conductor at 53%, two at 31%, and three or more at 40%. For identical conductors in any of these tiers, a fractional quotient of at least 0.8 rounds up under the documented Chapter 9 Note 7 rule.

The table shows the tier of the accepted maximum, its rounded display quotient, and actual fill. A Note 7 result can exceed its applicable percentage budget; actual fill is shown unchanged. Different conductor areas use strict area comparison; different IDs with equal insulated areas share the Note 7 group. Quotients are calculated from unrounded values; budgets and quotients display at least six significant digits, and ≈ marks rounded results. A zero means no count is accepted by this area-based rule; it is not a physical fit test.

3/4" PVC-40: 0.5080 in² interior. All values calculated from the current Table 4/5 data and fill engine.
THHN AWGOne wire in²TierBudget ÷ wire areaMaximumActual fillOne moreMax in 1"
#140.009740%0.20320000 ÷ 0.0097 ≈ 20.94845421 (Note 7)40.10%22: 42.01% — exceeds allowance34
#120.013340%0.20320000 ÷ 0.0133 ≈ 15.2781951539.27%16: 41.89% — exceeds allowance25
#100.021140%0.20320000 ÷ 0.0211 ≈ 9.6303318937.38%10: 41.54% — exceeds allowance15
#80.036640%0.20320000 ÷ 0.0366 ≈ 5.5519126536.02%6: 43.23% — exceeds allowance9
#60.050740%0.20320000 ÷ 0.0507 ≈ 4.0078895439.92%5: 49.90% — exceeds allowance6
#40.082431%0.15748000 ÷ 0.0824 ≈ 1.91116502 (Note 7)32.44%3: 48.66% — exceeds allowance4
#30.097353%0.26924000 ÷ 0.0973 ≈ 2.7671120119.15%2: 38.31% — exceeds allowance3
#20.115853%0.26924000 ÷ 0.1158 ≈ 2.3250432122.80%2: 45.59% — exceeds allowance3
#10.156253%0.26924000 ÷ 0.1562 ≈ 1.7236876130.75%2: 61.50% — exceeds allowance1
#1/00.185553%0.26924000 ÷ 0.1855 ≈ 1.4514286136.52%2: 73.03% — exceeds allowance1
#2/00.222353%0.26924000 ÷ 0.2223 ≈ 1.2111561143.76%2: 87.52% — exceeds allowance1
#4/00.323753%0.26924000 ÷ 0.3237 ≈ 0.831757801 (Note 7)63.72%2: 127.44% — exceeds allowance1

Compare all gauges in 1" PVC-40.

Keep fill and ampacity checks separate

Include all conductors present in the fill calculation, including equipment grounding conductors. Current-carrying conductor counts for ampacity adjustment follow different rules. Check terminal temperature limits, ambient correction, grounding, cable suitability and pulling conditions separately; a fill pass is not installation approval.

THWN-2 shares the supported THHN-family areas. RHH/RHW-2 values apply without outer covering; compare the table above. XHHW data remains withheld. For another insulation or a mixed pull, use the calculator below and the Table 5 guide.

FIG. 04

TRY IT — 3/4" PVC-40 LIVE

Preloaded with this conduit. Change the conductor gauge, insulation, or count and read the fill in real time.

NEC 2023 · CH.9
A · CONDUIT TYPE
B · TRADE SIZE
DESCRIPTION
PVC Schedule 40
C · CONDUCTORS
01
RESULT · FILL %
◆ APPROACHING LIMIT
39.3%
40% TIER
BASE BUDGET
025↑4075100
CONDUCTORS
15
WIRE AREA
0.200in²
CONDUIT AREA
0.508in²
GEOMETRIC JAM HINT
—

Table 1 tier: 40%. Note 7: not applied. The displayed percentage is actual fill; acceptance concerns area only.

An accepted result is within the NEC fill limit (Chapter 9 Table 1, per this site's calculation), including Note 7 where applicable. This assesses supported conductor areas only, not ampacity, product suitability, pulling feasibility or installation approval. A confirmed over-limit result means the supported equal-area count also fails the Note 7 check.

Geometric jamming risk hint only: assumes exactly three identical round conductors and infers diameters from area. The 2.8–3.2 ratio is a screening band, not a measured probability. Bends, tolerances, friction and pulling tension are not modeled; other configurations are not assessed.

  • Three or more conductors — 40% Table 1 tier; Note 7 may apply.
CONDUIT
PVC40 · 3/4"
CONDUCTOR
12 AWG · THHN (90°C dry)
FIG. 05

FREQUENTLY ASKED QUESTIONS

What is the total cross-sectional area of 3/4" PVC-40 conduit?
0.5080 in² (100% area), per NEC 2023 Chapter 9, Table 4 — Article 352. The allowable conductor fill is 0.2032 in² at 40% (3+ conductors), 0.1575 in² at 31% (2 conductors), and 0.2692 in² at 53% (1 conductor).
How many #12 THHN can I pull in 3/4" PVC-40?
The area-rule maximum is 15 #12 THHN, using the 40% tier; actual fill is 39.27%. Note 7 is not applied. This does not establish ampacity or pulling feasibility.
Does the NEC 40% fill cap apply for two conductors?
No. NEC Chapter 9, Table 1 specifies 53% for one conductor, 31% for two conductors, and 40% for three or more.
Is 3/4" PVC-40 the same as 3/4" EMT?
No — trade size is the same nominal value, but the actual interior diameters differ across conduit types. Use NEC Ch.9 Table 4 for your specific conduit family. 3/4" PVC-40 is 0.5080 in² (Article 352).