3/4" PVC-40 Conduit Fill Chart
How many wires fit in 3/4" PVC-40 (PVC Schedule 40). Maximum conductor counts per AWG using the applicable Table 1 tier and documented Note 7 rule.
MAXIMUM CONDUCTORS BY WIRE GAUGE
Table 1 fill tiers (53% / 31% / 40%) and Note 7 count rounding. 3/4" PVC-40 interior area = 0.5080 in².
XHHW-2: — Data pending verification; no capacity values provided. RHH/RHW-2 values apply without outer covering. Counts use 53% for one, 31% for two, and 40% for three or more, with Note 7 rounding for identical conductors in every tier.
| AWG | THHN / THWN-2 | XHHW-2 | RHH / RHW-2 (without outer covering) |
|---|---|---|---|
| #14 | 21 | — | 9 |
| #12 | 15 | — | 8 |
| #10 | 9 | — | 6 |
| #8 | 5 | — | 3 |
| #6 | 4 | — | 2 |
| #4 | 2 | — | 1 |
| #3 | 1 | — | 1 |
| #2 | 1 | — | 1 |
| #1 | 1 | — | 1 |
| #1/0 | 1 | — | 1 |
| #2/0 | 1 | — | 1 |
| #4/0 | 1 | — | 0 |
WORKED EXAMPLE & NEC REFERENCES
The NEC numbers behind 3/4" PVC-40
NEC 2023 Chapter 9, Table 4 lists the interior cross-sectional area of every standard trade size for each conduit family. For 3/4" PVC-40 (Article 352), the total 100% area is 0.5080 in². The allowable conductor fill is then derived from Table 1: 53% for a single conductor (0.2692 in²), 31% for two (0.1575 in²), and 40% for three or more (0.2032 in²).
Capacity at this size
The 3/4" PVC-40 40% budget is 0.2032 in². THHN maximum counts are #12: 15; #10: 9; #8: 5. At the #12 maximum, actual fill is 39.27%, using the 40% tier; Note 7 is not applied.
Adjacent trade sizes
1/2" PVC-40 has a 40% budget of 0.1140 in², a change of -0.0892 in². Its THHN counts are #12: 8; #10: 5; #8: 3.
1" PVC-40 has a 40% budget of 0.3328 in², a change of 0.1296 in². Its THHN counts are #12: 25; #10: 15; #8: 9.
Note 7 boundaries for this conduit
#14: 21 conductors at the 40% tier, 40.10% actual fill; #4: 2 conductors at the 31% tier, 32.44% actual fill; #4/0: 1 conductors at the 53% tier, 63.72% actual fill
These are area calculations. Physical clearance, bends, pulling tension and ampacity need separate checks. A larger size must be recalculated with the actual conductor mix; a single trade-size increase is not guaranteed to suffice.
Source citations
NFPA 70 (2023) — National Electrical Code. Chapter 9, Table 1: percent of cross section of conduit and tubing for conductors. Table 4: dimensions and percent area of conduit and tubing (Article 352). Table 5: dimensions of insulated conductors.
Calculation process — THHN counts and boundaries
Divide the allowed conduit area by one insulated conductor's area. The engine checks one conductor at 53%, two at 31%, and three or more at 40%. For identical conductors in any of these tiers, a fractional quotient of at least 0.8 rounds up under the documented Chapter 9 Note 7 rule.
The table shows the tier of the accepted maximum, its rounded display quotient, and actual fill. A Note 7 result can exceed its applicable percentage budget; actual fill is shown unchanged. Different conductor areas use strict area comparison; different IDs with equal insulated areas share the Note 7 group. Quotients are calculated from unrounded values; budgets and quotients display at least six significant digits, and ≈ marks rounded results. A zero means no count is accepted by this area-based rule; it is not a physical fit test.
| THHN AWG | One wire in² | Tier | Budget ÷ wire area | Maximum | Actual fill | One more | Max in 1" |
|---|---|---|---|---|---|---|---|
| #14 | 0.0097 | 40% | 0.20320000 ÷ 0.0097 ≈ 20.948454 | 21 (Note 7) | 40.10% | 22: 42.01% — exceeds allowance | 34 |
| #12 | 0.0133 | 40% | 0.20320000 ÷ 0.0133 ≈ 15.278195 | 15 | 39.27% | 16: 41.89% — exceeds allowance | 25 |
| #10 | 0.0211 | 40% | 0.20320000 ÷ 0.0211 ≈ 9.6303318 | 9 | 37.38% | 10: 41.54% — exceeds allowance | 15 |
| #8 | 0.0366 | 40% | 0.20320000 ÷ 0.0366 ≈ 5.5519126 | 5 | 36.02% | 6: 43.23% — exceeds allowance | 9 |
| #6 | 0.0507 | 40% | 0.20320000 ÷ 0.0507 ≈ 4.0078895 | 4 | 39.92% | 5: 49.90% — exceeds allowance | 6 |
| #4 | 0.0824 | 31% | 0.15748000 ÷ 0.0824 ≈ 1.9111650 | 2 (Note 7) | 32.44% | 3: 48.66% — exceeds allowance | 4 |
| #3 | 0.0973 | 53% | 0.26924000 ÷ 0.0973 ≈ 2.7671120 | 1 | 19.15% | 2: 38.31% — exceeds allowance | 3 |
| #2 | 0.1158 | 53% | 0.26924000 ÷ 0.1158 ≈ 2.3250432 | 1 | 22.80% | 2: 45.59% — exceeds allowance | 3 |
| #1 | 0.1562 | 53% | 0.26924000 ÷ 0.1562 ≈ 1.7236876 | 1 | 30.75% | 2: 61.50% — exceeds allowance | 1 |
| #1/0 | 0.1855 | 53% | 0.26924000 ÷ 0.1855 ≈ 1.4514286 | 1 | 36.52% | 2: 73.03% — exceeds allowance | 1 |
| #2/0 | 0.2223 | 53% | 0.26924000 ÷ 0.2223 ≈ 1.2111561 | 1 | 43.76% | 2: 87.52% — exceeds allowance | 1 |
| #4/0 | 0.3237 | 53% | 0.26924000 ÷ 0.3237 ≈ 0.83175780 | 1 (Note 7) | 63.72% | 2: 127.44% — exceeds allowance | 1 |
Compare all gauges in 1" PVC-40.
Keep fill and ampacity checks separate
Include all conductors present in the fill calculation, including equipment grounding conductors. Current-carrying conductor counts for ampacity adjustment follow different rules. Check terminal temperature limits, ambient correction, grounding, cable suitability and pulling conditions separately; a fill pass is not installation approval.
THWN-2 shares the supported THHN-family areas. RHH/RHW-2 values apply without outer covering; compare the table above. XHHW data remains withheld. For another insulation or a mixed pull, use the calculator below and the Table 5 guide.
TRY IT — 3/4" PVC-40 LIVE
Preloaded with this conduit. Change the conductor gauge, insulation, or count and read the fill in real time.
- CONDUCTORS
- 15
- WIRE AREA
- 0.200in²
- CONDUIT AREA
- 0.508in²
- GEOMETRIC JAM HINT
- —
Table 1 tier: 40%. Note 7: not applied. The displayed percentage is actual fill; acceptance concerns area only.
An accepted result is within the NEC fill limit (Chapter 9 Table 1, per this site's calculation), including Note 7 where applicable. This assesses supported conductor areas only, not ampacity, product suitability, pulling feasibility or installation approval. A confirmed over-limit result means the supported equal-area count also fails the Note 7 check.
Geometric jamming risk hint only: assumes exactly three identical round conductors and infers diameters from area. The 2.8–3.2 ratio is a screening band, not a measured probability. Bends, tolerances, friction and pulling tension are not modeled; other configurations are not assessed.
- Three or more conductors — 40% Table 1 tier; Note 7 may apply.