5" PVC-40 Conduit Fill Chart
How many wires fit in 5" PVC-40 (PVC Schedule 40). Maximum conductor counts per AWG using the applicable Table 1 tier and documented Note 7 rule.
MAXIMUM CONDUCTORS BY WIRE GAUGE
Table 1 fill tiers (53% / 31% / 40%) and Note 7 count rounding. 5" PVC-40 interior area = 19.7610 in².
XHHW-2: — Data pending verification; no capacity values provided. RHH/RHW-2 values apply without outer covering. Counts use 53% for one, 31% for two, and 40% for three or more, with Note 7 rounding for identical conductors in every tier.
| AWG | THHN / THWN-2 | XHHW-2 | RHH / RHW-2 (without outer covering) |
|---|---|---|---|
| #14 | 815 | — | 378 |
| #12 | 594 | — | 304 |
| #10 | 374 | — | 237 |
| #8 | 216 | — | 142 |
| #6 | 156 | — | 109 |
| #4 | 96 | — | 81 |
| #3 | 81 | — | 69 |
| #2 | 68 | — | 59 |
| #1 | 50 | — | 41 |
| #1/0 | 42 | — | 35 |
| #2/0 | 35 | — | 30 |
| #4/0 | 24 | — | 21 |
WORKED EXAMPLE & NEC REFERENCES
The NEC numbers behind 5" PVC-40
NEC 2023 Chapter 9, Table 4 lists the interior cross-sectional area of every standard trade size for each conduit family. For 5" PVC-40 (Article 352), the total 100% area is 19.7610 in². The allowable conductor fill is then derived from Table 1: 53% for a single conductor (10.4733 in²), 31% for two (6.1259 in²), and 40% for three or more (7.9044 in²).
Capacity at this size
The 5" PVC-40 40% budget is 7.9044 in². THHN maximum counts are #12: 594; #10: 374; #8: 216. At the #12 maximum, actual fill is 39.98%, using the 40% tier; Note 7 is not applied.
Adjacent trade sizes
4" PVC-40 has a 40% budget of 5.0216 in², a change of -2.8828 in². Its THHN counts are #12: 377; #10: 238; #8: 137.
6" PVC-40 has a 40% budget of 11.4268 in², a change of 3.5224 in². Its THHN counts are #12: 859; #10: 541; #8: 312.
Note 7 boundaries for this conduit
#14: 815 conductors at the 40% tier, 40.01% actual fill; #8: 216 conductors at the 40% tier, 40.01% actual fill; #6: 156 conductors at the 40% tier, 40.02% actual fill; #4: 96 conductors at the 40% tier, 40.03% actual fill
These are area calculations. Physical clearance, bends, pulling tension and ampacity need separate checks. A larger size must be recalculated with the actual conductor mix; a single trade-size increase is not guaranteed to suffice.
Source citations
NFPA 70 (2023) — National Electrical Code. Chapter 9, Table 1: percent of cross section of conduit and tubing for conductors. Table 4: dimensions and percent area of conduit and tubing (Article 352). Table 5: dimensions of insulated conductors.
Calculation process — THHN counts and boundaries
Divide the allowed conduit area by one insulated conductor's area. The engine checks one conductor at 53%, two at 31%, and three or more at 40%. For identical conductors in any of these tiers, a fractional quotient of at least 0.8 rounds up under the documented Chapter 9 Note 7 rule.
The table shows the tier of the accepted maximum, its rounded display quotient, and actual fill. A Note 7 result can exceed its applicable percentage budget; actual fill is shown unchanged. Different conductor areas use strict area comparison; different IDs with equal insulated areas share the Note 7 group. Quotients are calculated from unrounded values; budgets and quotients display at least six significant digits, and ≈ marks rounded results. A zero means no count is accepted by this area-based rule; it is not a physical fit test.
| THHN AWG | One wire in² | Tier | Budget ÷ wire area | Maximum | Actual fill | One more | Max in 6" |
|---|---|---|---|---|---|---|---|
| #14 | 0.0097 | 40% | 7.9044000 ÷ 0.0097 ≈ 814.88660 | 815 (Note 7) | 40.01% | 816: 40.05% — exceeds allowance | 1178 |
| #12 | 0.0133 | 40% | 7.9044000 ÷ 0.0133 ≈ 594.31579 | 594 | 39.98% | 595: 40.05% — exceeds allowance | 859 |
| #10 | 0.0211 | 40% | 7.9044000 ÷ 0.0211 ≈ 374.61611 | 374 | 39.93% | 375: 40.04% — exceeds allowance | 541 |
| #8 | 0.0366 | 40% | 7.9044000 ÷ 0.0366 ≈ 215.96721 | 216 (Note 7) | 40.01% | 217: 40.19% — exceeds allowance | 312 |
| #6 | 0.0507 | 40% | 7.9044000 ÷ 0.0507 ≈ 155.90533 | 156 (Note 7) | 40.02% | 157: 40.28% — exceeds allowance | 225 |
| #4 | 0.0824 | 40% | 7.9044000 ÷ 0.0824 ≈ 95.927184 | 96 (Note 7) | 40.03% | 97: 40.45% — exceeds allowance | 138 |
| #3 | 0.0973 | 40% | 7.9044000 ÷ 0.0973 ≈ 81.237410 | 81 | 39.88% | 82: 40.38% — exceeds allowance | 117 |
| #2 | 0.1158 | 40% | 7.9044000 ÷ 0.1158 ≈ 68.259067 | 68 | 39.85% | 69: 40.43% — exceeds allowance | 98 |
| #1 | 0.1562 | 40% | 7.9044000 ÷ 0.1562 ≈ 50.604353 | 50 | 39.52% | 51: 40.31% — exceeds allowance | 73 |
| #1/0 | 0.1855 | 40% | 7.9044000 ÷ 0.1855 ≈ 42.611321 | 42 | 39.43% | 43: 40.36% — exceeds allowance | 61 |
| #2/0 | 0.2223 | 40% | 7.9044000 ÷ 0.2223 ≈ 35.557355 | 35 | 39.37% | 36: 40.50% — exceeds allowance | 51 |
| #4/0 | 0.3237 | 40% | 7.9044000 ÷ 0.3237 ≈ 24.418906 | 24 | 39.31% | 25: 40.95% — exceeds allowance | 35 |
Compare all gauges in 6" PVC-40.
Keep fill and ampacity checks separate
Include all conductors present in the fill calculation, including equipment grounding conductors. Current-carrying conductor counts for ampacity adjustment follow different rules. Check terminal temperature limits, ambient correction, grounding, cable suitability and pulling conditions separately; a fill pass is not installation approval.
THWN-2 shares the supported THHN-family areas. RHH/RHW-2 values apply without outer covering; compare the table above. XHHW data remains withheld. For another insulation or a mixed pull, use the calculator below and the Table 5 guide.
TRY IT — 5" PVC-40 LIVE
Preloaded with this conduit. Change the conductor gauge, insulation, or count and read the fill in real time.
- CONDUCTORS
- 594
- WIRE AREA
- 7.900in²
- CONDUIT AREA
- 19.761in²
- GEOMETRIC JAM HINT
- —
Table 1 tier: 40%. Note 7: not applied. The displayed percentage is actual fill; acceptance concerns area only.
An accepted result is within the NEC fill limit (Chapter 9 Table 1, per this site's calculation), including Note 7 where applicable. This assesses supported conductor areas only, not ampacity, product suitability, pulling feasibility or installation approval. A confirmed over-limit result means the supported equal-area count also fails the Note 7 check.
Geometric jamming risk hint only: assumes exactly three identical round conductors and infers diameters from area. The 2.8–3.2 ratio is a screening band, not a measured probability. Bends, tolerances, friction and pulling tension are not modeled; other configurations are not assessed.
- Three or more conductors — 40% Table 1 tier; Note 7 may apply.