Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
FIG. 01 — SIZE-SPECIFIC FILL

5" PVC-40 Conduit Fill Chart

How many wires fit in 5" PVC-40 (PVC Schedule 40). Maximum conductor counts per AWG using the applicable Table 1 tier and documented Note 7 rule.

FIG. 02

MAXIMUM CONDUCTORS BY WIRE GAUGE

Table 1 fill tiers (53% / 31% / 40%) and Note 7 count rounding. 5" PVC-40 interior area = 19.7610 in².

XHHW-2: — Data pending verification; no capacity values provided. RHH/RHW-2 values apply without outer covering. Counts use 53% for one, 31% for two, and 40% for three or more, with Note 7 rounding for identical conductors in every tier.

AWGTHHN / THWN-2XHHW-2RHH / RHW-2 (without outer covering)
#14815—378
#12594—304
#10374—237
#8216—142
#6156—109
#496—81
#381—69
#268—59
#150—41
#1/042—35
#2/035—30
#4/024—21
FIG. 03

WORKED EXAMPLE & NEC REFERENCES

The NEC numbers behind 5" PVC-40

NEC 2023 Chapter 9, Table 4 lists the interior cross-sectional area of every standard trade size for each conduit family. For 5" PVC-40 (Article 352), the total 100% area is 19.7610 in². The allowable conductor fill is then derived from Table 1: 53% for a single conductor (10.4733 in²), 31% for two (6.1259 in²), and 40% for three or more (7.9044 in²).

Capacity at this size

The 5" PVC-40 40% budget is 7.9044 in². THHN maximum counts are #12: 594; #10: 374; #8: 216. At the #12 maximum, actual fill is 39.98%, using the 40% tier; Note 7 is not applied.

Adjacent trade sizes

4" PVC-40 has a 40% budget of 5.0216 in², a change of -2.8828 in². Its THHN counts are #12: 377; #10: 238; #8: 137.

6" PVC-40 has a 40% budget of 11.4268 in², a change of 3.5224 in². Its THHN counts are #12: 859; #10: 541; #8: 312.

Note 7 boundaries for this conduit

#14: 815 conductors at the 40% tier, 40.01% actual fill; #8: 216 conductors at the 40% tier, 40.01% actual fill; #6: 156 conductors at the 40% tier, 40.02% actual fill; #4: 96 conductors at the 40% tier, 40.03% actual fill

These are area calculations. Physical clearance, bends, pulling tension and ampacity need separate checks. A larger size must be recalculated with the actual conductor mix; a single trade-size increase is not guaranteed to suffice.

Source citations

NFPA 70 (2023) — National Electrical Code. Chapter 9, Table 1: percent of cross section of conduit and tubing for conductors. Table 4: dimensions and percent area of conduit and tubing (Article 352). Table 5: dimensions of insulated conductors.

Calculation process — THHN counts and boundaries

Divide the allowed conduit area by one insulated conductor's area. The engine checks one conductor at 53%, two at 31%, and three or more at 40%. For identical conductors in any of these tiers, a fractional quotient of at least 0.8 rounds up under the documented Chapter 9 Note 7 rule.

The table shows the tier of the accepted maximum, its rounded display quotient, and actual fill. A Note 7 result can exceed its applicable percentage budget; actual fill is shown unchanged. Different conductor areas use strict area comparison; different IDs with equal insulated areas share the Note 7 group. Quotients are calculated from unrounded values; budgets and quotients display at least six significant digits, and ≈ marks rounded results. A zero means no count is accepted by this area-based rule; it is not a physical fit test.

5" PVC-40: 19.7610 in² interior. All values calculated from the current Table 4/5 data and fill engine.
THHN AWGOne wire in²TierBudget ÷ wire areaMaximumActual fillOne moreMax in 6"
#140.009740%7.9044000 ÷ 0.0097 ≈ 814.88660815 (Note 7)40.01%816: 40.05% — exceeds allowance1178
#120.013340%7.9044000 ÷ 0.0133 ≈ 594.3157959439.98%595: 40.05% — exceeds allowance859
#100.021140%7.9044000 ÷ 0.0211 ≈ 374.6161137439.93%375: 40.04% — exceeds allowance541
#80.036640%7.9044000 ÷ 0.0366 ≈ 215.96721216 (Note 7)40.01%217: 40.19% — exceeds allowance312
#60.050740%7.9044000 ÷ 0.0507 ≈ 155.90533156 (Note 7)40.02%157: 40.28% — exceeds allowance225
#40.082440%7.9044000 ÷ 0.0824 ≈ 95.92718496 (Note 7)40.03%97: 40.45% — exceeds allowance138
#30.097340%7.9044000 ÷ 0.0973 ≈ 81.2374108139.88%82: 40.38% — exceeds allowance117
#20.115840%7.9044000 ÷ 0.1158 ≈ 68.2590676839.85%69: 40.43% — exceeds allowance98
#10.156240%7.9044000 ÷ 0.1562 ≈ 50.6043535039.52%51: 40.31% — exceeds allowance73
#1/00.185540%7.9044000 ÷ 0.1855 ≈ 42.6113214239.43%43: 40.36% — exceeds allowance61
#2/00.222340%7.9044000 ÷ 0.2223 ≈ 35.5573553539.37%36: 40.50% — exceeds allowance51
#4/00.323740%7.9044000 ÷ 0.3237 ≈ 24.4189062439.31%25: 40.95% — exceeds allowance35

Compare all gauges in 6" PVC-40.

Keep fill and ampacity checks separate

Include all conductors present in the fill calculation, including equipment grounding conductors. Current-carrying conductor counts for ampacity adjustment follow different rules. Check terminal temperature limits, ambient correction, grounding, cable suitability and pulling conditions separately; a fill pass is not installation approval.

THWN-2 shares the supported THHN-family areas. RHH/RHW-2 values apply without outer covering; compare the table above. XHHW data remains withheld. For another insulation or a mixed pull, use the calculator below and the Table 5 guide.

FIG. 04

TRY IT — 5" PVC-40 LIVE

Preloaded with this conduit. Change the conductor gauge, insulation, or count and read the fill in real time.

NEC 2023 · CH.9
A · CONDUIT TYPE
B · TRADE SIZE
DESCRIPTION
PVC Schedule 40
C · CONDUCTORS
01
RESULT · FILL %
◆ APPROACHING LIMIT
40.0%
40% TIER
BASE BUDGET
025↑4075100
CONDUCTORS
594
WIRE AREA
7.900in²
CONDUIT AREA
19.761in²
GEOMETRIC JAM HINT
—

Table 1 tier: 40%. Note 7: not applied. The displayed percentage is actual fill; acceptance concerns area only.

An accepted result is within the NEC fill limit (Chapter 9 Table 1, per this site's calculation), including Note 7 where applicable. This assesses supported conductor areas only, not ampacity, product suitability, pulling feasibility or installation approval. A confirmed over-limit result means the supported equal-area count also fails the Note 7 check.

Geometric jamming risk hint only: assumes exactly three identical round conductors and infers diameters from area. The 2.8–3.2 ratio is a screening band, not a measured probability. Bends, tolerances, friction and pulling tension are not modeled; other configurations are not assessed.

  • Three or more conductors — 40% Table 1 tier; Note 7 may apply.
+570
CONDUIT
PVC40 · 5"
CONDUCTOR
12 AWG · THHN (90°C dry)
FIG. 05

FREQUENTLY ASKED QUESTIONS

What is the total cross-sectional area of 5" PVC-40 conduit?
19.7610 in² (100% area), per NEC 2023 Chapter 9, Table 4 — Article 352. The allowable conductor fill is 7.9044 in² at 40% (3+ conductors), 6.1259 in² at 31% (2 conductors), and 10.4733 in² at 53% (1 conductor).
How many #12 THHN can I pull in 5" PVC-40?
The area-rule maximum is 594 #12 THHN, using the 40% tier; actual fill is 39.98%. Note 7 is not applied. This does not establish ampacity or pulling feasibility.
Does the NEC 40% fill cap apply for two conductors?
No. NEC Chapter 9, Table 1 specifies 53% for one conductor, 31% for two conductors, and 40% for three or more.
Is 5" PVC-40 the same as 5" EMT?
No — trade size is the same nominal value, but the actual interior diameters differ across conduit types. Use NEC Ch.9 Table 4 for your specific conduit family. 5" PVC-40 is 19.7610 in² (Article 352).