4" PVC-40 Conduit Fill Chart
How many wires fit in 4" PVC-40 (PVC Schedule 40). Maximum conductor counts per AWG using the applicable Table 1 tier and documented Note 7 rule.
MAXIMUM CONDUCTORS BY WIRE GAUGE
Table 1 fill tiers (53% / 31% / 40%) and Note 7 count rounding. 4" PVC-40 interior area = 12.5540 in².
XHHW-2: — Data pending verification; no capacity values provided. RHH/RHW-2 values apply without outer covering. Counts use 53% for one, 31% for two, and 40% for three or more, with Note 7 rounding for identical conductors in every tier.
| AWG | THHN / THWN-2 | XHHW-2 | RHH / RHW-2 (without outer covering) |
|---|---|---|---|
| #14 | 517 | — | 240 |
| #12 | 377 | — | 193 |
| #10 | 238 | — | 150 |
| #8 | 137 | — | 90 |
| #6 | 99 | — | 69 |
| #4 | 61 | — | 51 |
| #3 | 51 | — | 44 |
| #2 | 43 | — | 37 |
| #1 | 32 | — | 26 |
| #1/0 | 27 | — | 22 |
| #2/0 | 22 | — | 19 |
| #4/0 | 15 | — | 13 |
WORKED EXAMPLE & NEC REFERENCES
The NEC numbers behind 4" PVC-40
NEC 2023 Chapter 9, Table 4 lists the interior cross-sectional area of every standard trade size for each conduit family. For 4" PVC-40 (Article 352), the total 100% area is 12.5540 in². The allowable conductor fill is then derived from Table 1: 53% for a single conductor (6.6536 in²), 31% for two (3.8917 in²), and 40% for three or more (5.0216 in²).
Capacity at this size
The 4" PVC-40 40% budget is 5.0216 in². THHN maximum counts are #12: 377; #10: 238; #8: 137. At the #12 maximum, actual fill is 39.94%, using the 40% tier; Note 7 is not applied.
Adjacent trade sizes
3-1/2" PVC-40 has a 40% budget of 3.8948 in², a change of -1.1268 in². Its THHN counts are #12: 293; #10: 184; #8: 106.
5" PVC-40 has a 40% budget of 7.9044 in², a change of 2.8828 in². Its THHN counts are #12: 594; #10: 374; #8: 216.
Note 7 boundaries for this conduit
#10: 238 conductors at the 40% tier, 40.00% actual fill; #4: 61 conductors at the 40% tier, 40.04% actual fill
These are area calculations. Physical clearance, bends, pulling tension and ampacity need separate checks. A larger size must be recalculated with the actual conductor mix; a single trade-size increase is not guaranteed to suffice.
Source citations
NFPA 70 (2023) — National Electrical Code. Chapter 9, Table 1: percent of cross section of conduit and tubing for conductors. Table 4: dimensions and percent area of conduit and tubing (Article 352). Table 5: dimensions of insulated conductors.
Calculation process — THHN counts and boundaries
Divide the allowed conduit area by one insulated conductor's area. The engine checks one conductor at 53%, two at 31%, and three or more at 40%. For identical conductors in any of these tiers, a fractional quotient of at least 0.8 rounds up under the documented Chapter 9 Note 7 rule.
The table shows the tier of the accepted maximum, its rounded display quotient, and actual fill. A Note 7 result can exceed its applicable percentage budget; actual fill is shown unchanged. Different conductor areas use strict area comparison; different IDs with equal insulated areas share the Note 7 group. Quotients are calculated from unrounded values; budgets and quotients display at least six significant digits, and ≈ marks rounded results. A zero means no count is accepted by this area-based rule; it is not a physical fit test.
| THHN AWG | One wire in² | Tier | Budget ÷ wire area | Maximum | Actual fill | One more | Max in 5" |
|---|---|---|---|---|---|---|---|
| #14 | 0.0097 | 40% | 5.0216000 ÷ 0.0097 ≈ 517.69072 | 517 | 39.95% | 518: 40.02% — exceeds allowance | 815 |
| #12 | 0.0133 | 40% | 5.0216000 ÷ 0.0133 ≈ 377.56391 | 377 | 39.94% | 378: 40.05% — exceeds allowance | 594 |
| #10 | 0.0211 | 40% | 5.0216000 ÷ 0.0211 ≈ 237.99052 | 238 (Note 7) | 40.00% | 239: 40.17% — exceeds allowance | 374 |
| #8 | 0.0366 | 40% | 5.0216000 ÷ 0.0366 ≈ 137.20219 | 137 | 39.94% | 138: 40.23% — exceeds allowance | 216 |
| #6 | 0.0507 | 40% | 5.0216000 ÷ 0.0507 ≈ 99.045365 | 99 | 39.98% | 100: 40.39% — exceeds allowance | 156 |
| #4 | 0.0824 | 40% | 5.0216000 ÷ 0.0824 ≈ 60.941748 | 61 (Note 7) | 40.04% | 62: 40.69% — exceeds allowance | 96 |
| #3 | 0.0973 | 40% | 5.0216000 ÷ 0.0973 ≈ 51.609455 | 51 | 39.53% | 52: 40.30% — exceeds allowance | 81 |
| #2 | 0.1158 | 40% | 5.0216000 ÷ 0.1158 ≈ 43.364421 | 43 | 39.66% | 44: 40.59% — exceeds allowance | 68 |
| #1 | 0.1562 | 40% | 5.0216000 ÷ 0.1562 ≈ 32.148528 | 32 | 39.82% | 33: 41.06% — exceeds allowance | 50 |
| #1/0 | 0.1855 | 40% | 5.0216000 ÷ 0.1855 ≈ 27.070620 | 27 | 39.90% | 28: 41.37% — exceeds allowance | 42 |
| #2/0 | 0.2223 | 40% | 5.0216000 ÷ 0.2223 ≈ 22.589294 | 22 | 38.96% | 23: 40.73% — exceeds allowance | 35 |
| #4/0 | 0.3237 | 40% | 5.0216000 ÷ 0.3237 ≈ 15.513129 | 15 | 38.68% | 16: 41.26% — exceeds allowance | 24 |
Compare all gauges in 5" PVC-40.
Keep fill and ampacity checks separate
Include all conductors present in the fill calculation, including equipment grounding conductors. Current-carrying conductor counts for ampacity adjustment follow different rules. Check terminal temperature limits, ambient correction, grounding, cable suitability and pulling conditions separately; a fill pass is not installation approval.
THWN-2 shares the supported THHN-family areas. RHH/RHW-2 values apply without outer covering; compare the table above. XHHW data remains withheld. For another insulation or a mixed pull, use the calculator below and the Table 5 guide.
TRY IT — 4" PVC-40 LIVE
Preloaded with this conduit. Change the conductor gauge, insulation, or count and read the fill in real time.
- CONDUCTORS
- 377
- WIRE AREA
- 5.014in²
- CONDUIT AREA
- 12.554in²
- GEOMETRIC JAM HINT
- —
Table 1 tier: 40%. Note 7: not applied. The displayed percentage is actual fill; acceptance concerns area only.
An accepted result is within the NEC fill limit (Chapter 9 Table 1, per this site's calculation), including Note 7 where applicable. This assesses supported conductor areas only, not ampacity, product suitability, pulling feasibility or installation approval. A confirmed over-limit result means the supported equal-area count also fails the Note 7 check.
Geometric jamming risk hint only: assumes exactly three identical round conductors and infers diameters from area. The 2.8–3.2 ratio is a screening band, not a measured probability. Bends, tolerances, friction and pulling tension are not modeled; other configurations are not assessed.
- Three or more conductors — 40% Table 1 tier; Note 7 may apply.