FIG. 01 — SIZE-SPECIFIC FILL

4" PVC-40 Conduit Fill Chart

How many wires fit in 4" PVC-40 (PVC Schedule 40). Maximum conductor counts per AWG using the applicable Table 1 tier and documented Note 7 rule.

FIG. 02

MAXIMUM CONDUCTORS BY WIRE GAUGE

Table 1 fill tiers (53% / 31% / 40%) and Note 7 count rounding. 4" PVC-40 interior area = 12.5540 in².

XHHW-2: — Data pending verification; no capacity values provided. RHH/RHW-2 values apply without outer covering. Counts use 53% for one, 31% for two, and 40% for three or more, with Note 7 rounding for identical conductors in every tier.

AWGTHHN / THWN-2XHHW-2RHH / RHW-2 (without outer covering)
#14517—240
#12377—193
#10238—150
#8137—90
#699—69
#461—51
#351—44
#243—37
#132—26
#1/027—22
#2/022—19
#4/015—13
FIG. 03

WORKED EXAMPLE & NEC REFERENCES

The NEC numbers behind 4" PVC-40

NEC 2023 Chapter 9, Table 4 lists the interior cross-sectional area of every standard trade size for each conduit family. For 4" PVC-40 (Article 352), the total 100% area is 12.5540 in². The allowable conductor fill is then derived from Table 1: 53% for a single conductor (6.6536 in²), 31% for two (3.8917 in²), and 40% for three or more (5.0216 in²).

Capacity at this size

The 4" PVC-40 40% budget is 5.0216 in². THHN maximum counts are #12: 377; #10: 238; #8: 137. At the #12 maximum, actual fill is 39.94%, using the 40% tier; Note 7 is not applied.

Adjacent trade sizes

3-1/2" PVC-40 has a 40% budget of 3.8948 in², a change of -1.1268 in². Its THHN counts are #12: 293; #10: 184; #8: 106.

5" PVC-40 has a 40% budget of 7.9044 in², a change of 2.8828 in². Its THHN counts are #12: 594; #10: 374; #8: 216.

Note 7 boundaries for this conduit

#10: 238 conductors at the 40% tier, 40.00% actual fill; #4: 61 conductors at the 40% tier, 40.04% actual fill

These are area calculations. Physical clearance, bends, pulling tension and ampacity need separate checks. A larger size must be recalculated with the actual conductor mix; a single trade-size increase is not guaranteed to suffice.

Source citations

NFPA 70 (2023) — National Electrical Code. Chapter 9, Table 1: percent of cross section of conduit and tubing for conductors. Table 4: dimensions and percent area of conduit and tubing (Article 352). Table 5: dimensions of insulated conductors.

Calculation process — THHN counts and boundaries

Divide the allowed conduit area by one insulated conductor's area. The engine checks one conductor at 53%, two at 31%, and three or more at 40%. For identical conductors in any of these tiers, a fractional quotient of at least 0.8 rounds up under the documented Chapter 9 Note 7 rule.

The table shows the tier of the accepted maximum, its rounded display quotient, and actual fill. A Note 7 result can exceed its applicable percentage budget; actual fill is shown unchanged. Different conductor areas use strict area comparison; different IDs with equal insulated areas share the Note 7 group. Quotients are calculated from unrounded values; budgets and quotients display at least six significant digits, and ≈ marks rounded results. A zero means no count is accepted by this area-based rule; it is not a physical fit test.

4" PVC-40: 12.5540 in² interior. All values calculated from the current Table 4/5 data and fill engine.
THHN AWGOne wire in²TierBudget ÷ wire areaMaximumActual fillOne moreMax in 5"
#140.009740%5.0216000 ÷ 0.0097 ≈ 517.6907251739.95%518: 40.02% — exceeds allowance815
#120.013340%5.0216000 ÷ 0.0133 ≈ 377.5639137739.94%378: 40.05% — exceeds allowance594
#100.021140%5.0216000 ÷ 0.0211 ≈ 237.99052238 (Note 7)40.00%239: 40.17% — exceeds allowance374
#80.036640%5.0216000 ÷ 0.0366 ≈ 137.2021913739.94%138: 40.23% — exceeds allowance216
#60.050740%5.0216000 ÷ 0.0507 ≈ 99.0453659939.98%100: 40.39% — exceeds allowance156
#40.082440%5.0216000 ÷ 0.0824 ≈ 60.94174861 (Note 7)40.04%62: 40.69% — exceeds allowance96
#30.097340%5.0216000 ÷ 0.0973 ≈ 51.6094555139.53%52: 40.30% — exceeds allowance81
#20.115840%5.0216000 ÷ 0.1158 ≈ 43.3644214339.66%44: 40.59% — exceeds allowance68
#10.156240%5.0216000 ÷ 0.1562 ≈ 32.1485283239.82%33: 41.06% — exceeds allowance50
#1/00.185540%5.0216000 ÷ 0.1855 ≈ 27.0706202739.90%28: 41.37% — exceeds allowance42
#2/00.222340%5.0216000 ÷ 0.2223 ≈ 22.5892942238.96%23: 40.73% — exceeds allowance35
#4/00.323740%5.0216000 ÷ 0.3237 ≈ 15.5131291538.68%16: 41.26% — exceeds allowance24

Compare all gauges in 5" PVC-40.

Keep fill and ampacity checks separate

Include all conductors present in the fill calculation, including equipment grounding conductors. Current-carrying conductor counts for ampacity adjustment follow different rules. Check terminal temperature limits, ambient correction, grounding, cable suitability and pulling conditions separately; a fill pass is not installation approval.

THWN-2 shares the supported THHN-family areas. RHH/RHW-2 values apply without outer covering; compare the table above. XHHW data remains withheld. For another insulation or a mixed pull, use the calculator below and the Table 5 guide.

FIG. 04

TRY IT — 4" PVC-40 LIVE

Preloaded with this conduit. Change the conductor gauge, insulation, or count and read the fill in real time.

NEC 2023 · CH.9
A · CONDUIT TYPE
B · TRADE SIZE
DESCRIPTION
PVC Schedule 40
C · CONDUCTORS
01
RESULT · FILL %
◆ APPROACHING LIMIT
39.9%
40% TIER
BASE BUDGET
025↑4075100
CONDUCTORS
377
WIRE AREA
5.014in²
CONDUIT AREA
12.554in²
GEOMETRIC JAM HINT
—

Table 1 tier: 40%. Note 7: not applied. The displayed percentage is actual fill; acceptance concerns area only.

An accepted result is within the NEC fill limit (Chapter 9 Table 1, per this site's calculation), including Note 7 where applicable. This assesses supported conductor areas only, not ampacity, product suitability, pulling feasibility or installation approval. A confirmed over-limit result means the supported equal-area count also fails the Note 7 check.

Geometric jamming risk hint only: assumes exactly three identical round conductors and infers diameters from area. The 2.8–3.2 ratio is a screening band, not a measured probability. Bends, tolerances, friction and pulling tension are not modeled; other configurations are not assessed.

  • Three or more conductors — 40% Table 1 tier; Note 7 may apply.
+353
CONDUIT
PVC40 · 4"
CONDUCTOR
12 AWG · THHN (90°C dry)
FIG. 05

FREQUENTLY ASKED QUESTIONS

What is the total cross-sectional area of 4" PVC-40 conduit?
12.5540 in² (100% area), per NEC 2023 Chapter 9, Table 4 — Article 352. The allowable conductor fill is 5.0216 in² at 40% (3+ conductors), 3.8917 in² at 31% (2 conductors), and 6.6536 in² at 53% (1 conductor).
How many #12 THHN can I pull in 4" PVC-40?
The area-rule maximum is 377 #12 THHN, using the 40% tier; actual fill is 39.94%. Note 7 is not applied. This does not establish ampacity or pulling feasibility.
Does the NEC 40% fill cap apply for two conductors?
No. NEC Chapter 9, Table 1 specifies 53% for one conductor, 31% for two conductors, and 40% for three or more.
Is 4" PVC-40 the same as 4" EMT?
No — trade size is the same nominal value, but the actual interior diameters differ across conduit types. Use NEC Ch.9 Table 4 for your specific conduit family. 4" PVC-40 is 12.5540 in² (Article 352).