WIRE·FILL·CHARTNEC 2023 · CH. 9
FIG. 01 — SLEEVE SIZING

What Size Conduit for 10-2 Romex (NM-B)?

Smallest EMT, PVC Schedule 40, RMC and flex trade size for 1, 2, or 3 runs of 10-2 Romex (NM-B). Used for 30a water heaters and 240v a/c disconnects.

FIG. 02

SMALLEST CONDUIT BY CABLE COUNT

Each 10-2 Romex (NM-B) is sized as a single conductor with diameter = major OD (0.470"). Equivalent area = π·d²/4 = 0.1735 in².

Conduit family1 cable
53% fill
2 cables
31% fill
3 cables
40% fill
EMT (Article 358)3/4"
32.6% fill
1-1/4"
23.2% fill
1-1/4"
34.8% fill
RMC (Article 344)3/4"
31.6% fill
1-1/4"
22.7% fill
1-1/4"
34.1% fill
PVC-40 (Article 352)3/4"
34.2% fill
1-1/4"
23.9% fill
1-1/4"
35.8% fill
FMC (Article 348)3/4"
32.6% fill
1-1/4"
27.2% fill
1-1/2"
28.0% fill

Source: NFPA 70 (2023) Chapter 9 Table 1 Note 9 + Table 4 conduit interior areas. Cable OD reference: Southwire / Cerrowire spec sheets — verify ±5% with the cable manufacturer.

FIG. 03

WHY EACH CABLE COUNTS AS ONE CONDUCTOR

NEC Chapter 9, Table 1, Note 9 instructs that any multi-conductor cable (Romex, MC, UF-B, SO cord, etc.) be treated as a single conductor for the fill calculation. For cables whose cross-section is elliptical — which all jacketed building cables are — the area is computed as a circle whose diameter equals the major axis of the ellipse.

Why elliptical cables get the major-axis treatment

In a real pull, the cable can rotate inside the raceway. The major axis is what limits how much room it actually consumes. Using the major-axis as a circle diameter gives a conservative (slightly oversized) area that protects against tight rotations during the pull.

How NM-B in a sleeve is treated by the code

NEC 334.15(B) explicitly permits NM-B cable to pass through a raceway used as a sleeve, provided the conduit protects the cable end-to-end against the physical damage hazard. The conduit is sized using the fill rules above; the cable retains its NM-B identity inside the sleeve and is not converted into THHN.

Sleeve vs. raceway wiring method

NM-B is not a raceway-wiring conductor — you do not pull individual NM-B conductors through long conduit runs as if they were THHN. If your run benefits from being fully in conduit (length, exposure, geometry), pull individual THHN conductors of the same gauge and use NEC Annex C tables for capacity.

FIG. 04

FREQUENTLY ASKED QUESTIONS

Yes — but only when the conduit is properly sized and the cable is not subjected to physical damage that the cable assembly alone cannot withstand. NEC 334.15(B) requires that NM-B installed in a raceway (such as a section of conduit) be protected end to end; the cable itself remains NM-B, the conduit acts as sleeve. UF-B (NEC 340) and MC cable (NEC 330) follow analogous rules.