3/4" RMC Conduit Fill Chart

How many wires fit in 3/4" RMC (Rigid Metal Conduit (galvanized steel)). Maximum conductor counts per AWG at the NEC 2023 40% fill cap for three or more conductors.

FIG. 02

MAXIMUM CONDUCTORS BY WIRE GAUGE

40% fill (3+ conductors per NEC 2023 Ch.9 Table 1). 3/4" RMC interior area = 0.5490 in².

AWGTHHN / THWN-2XHHW-2RHH / RHW-2
#1422010
#121608
#101006
#8604
#6403
#4200
#1001
#1/0101
#2/0101
#4/0100
FIG. 03

WORKED EXAMPLE & NEC REFERENCES

The NEC numbers behind 3/4" RMC

NEC 2023 Chapter 9, Table 4 lists the interior cross-sectional area of every standard trade size for each conduit family. For 3/4" RMC (Article 344), the total 100% area is 0.5490 in². The allowable conductor fill is then derived from Table 1: 53% for a single conductor (0.2910 in²), 31% for two (0.1702 in²), and 40% for three or more (0.2196 in²) — covering nearly all real-world raceway pulls.

Worked example — four #12 THHN conductors

Each #12 THHN conductor occupies 0.0133 in² (NEC Ch.9 Table 5). Four conductors fill 4 × 0.0133 = 0.0532 in², which is 0.0532 ÷ 0.5490 = 9.7% of total area. Because that is well below the 40% NEC limit for 0.2196 in², the pull is compliant — and you can keep adding conductors up to 16× #12 THHN before exceeding the cap.

If you exceed the fill cap

Step up one trade size. Increase a 3/4" RMC to 1" when the calculated fill crosses 40%. Reducing one trade size is rarely worth the labor: pull tension climbs fast, jam probability spikes (NEC Ch.9 Informational Note re: 2.8–3.2 conduit-ID to wire-OD ratio), and you lose room for de-rating or future moves.

Source citations

NFPA 70 (2023) — National Electrical Code. Chapter 9, Table 1: percent of cross section of conduit and tubing for conductors. Table 4: dimensions and percent area of conduit and tubing (Article 344). Table 5: dimensions of insulated conductors.

FIG. 04

TRY IT — 3/4" RMC LIVE

Preloaded with this conduit. Change the conductor gauge, insulation, or count and read the fill in real time.

NEC 2023 · CH.9
A · CONDUIT TYPE
B · TRADE SIZE
DESCRIPTION
RMC — Rigid Metal Conduit
C · CONDUCTORS
01
RESULT · FILL %
APPROACHING LIMIT
38.8%
OF 40%
ALLOWED
0254075100
CONDUCTORS
16
WIRE AREA
0.213in²
CONDUIT AREA
0.549in²
JAM RISK
LOW
  • Three or more conductors — NEC allows 40% fill.
CONDUIT
RMC · 3/4"
CONDUCTOR
12 AWG · THHN
FIG. 05

FREQUENTLY ASKED QUESTIONS

0.5490 in² (100% area), per NEC 2023 Chapter 9, Table 4 — Article 344. The allowable conductor fill is 0.2196 in² at 40% (3+ conductors), 0.1702 in² at 31% (2 conductors), and 0.2910 in² at 53% (1 conductor).