WIRE·FILL·CHARTNEC 2023 · CH. 9
FIG. 01 — SIZE-SPECIFIC FILL

1-1/2" RMC Conduit Fill Chart

How many wires fit in 1-1/2" RMC (Rigid Metal Conduit (galvanized steel)). Maximum conductor counts per AWG at the NEC 2023 40% fill cap for three or more conductors.

FIG. 02

MAXIMUM CONDUCTORS BY WIRE GAUGE

40% fill (3+ conductors per NEC 2023 Ch.9 Table 1). 1-1/2" RMC interior area = 2.0710 in².

AWGTHHN / THWN-2XHHW-2RHH / RHW-2
#14858539
#12626231
#10393924
#8222214
#6161611
#410108
#3887
#2776
#1554
#1/0443
#2/0333
#4/0222
FIG. 03

WORKED EXAMPLE & NEC REFERENCES

The NEC numbers behind 1-1/2" RMC

NEC 2023 Chapter 9, Table 4 lists the interior cross-sectional area of every standard trade size for each conduit family. For 1-1/2" RMC (Article 344), the total 100% area is 2.0710 in². The allowable conductor fill is then derived from Table 1: 53% for a single conductor (1.0976 in²), 31% for two (0.6420 in²), and 40% for three or more (0.8284 in²) — covering nearly all real-world raceway pulls.

Worked example — four #12 THHN conductors

Each #12 THHN conductor occupies 0.0133 in² (NEC Ch.9 Table 5). Four conductors fill 4 × 0.0133 = 0.0532 in², which is 0.0532 ÷ 2.0710 = 2.6% of total area. Because that is well below the 40% NEC limit for 0.8284 in², the pull is compliant — and you can keep adding conductors up to 62× #12 THHN before exceeding the cap.

If you exceed the fill cap

Step up one trade size. Increase a 1-1/2" RMC to 2" when the calculated fill crosses 40%. Reducing one trade size is rarely worth the labor: pull tension climbs fast, jam probability spikes (NEC Ch.9 Informational Note re: 2.8–3.2 conduit-ID to wire-OD ratio), and you lose room for de-rating or future moves.

Source citations

NFPA 70 (2023) — National Electrical Code. Chapter 9, Table 1: percent of cross section of conduit and tubing for conductors. Table 4: dimensions and percent area of conduit and tubing (Article 344). Table 5: dimensions of insulated conductors.

FIG. 04

FREQUENTLY ASKED QUESTIONS

2.0710 in² (100% area), per NEC 2023 Chapter 9, Table 4 — Article 344. The allowable conductor fill is 0.8284 in² at 40% (3+ conductors), 0.6420 in² at 31% (2 conductors), and 1.0976 in² at 53% (1 conductor).