1-1/4" FMC Conduit Fill Chart

How many wires fit in 1-1/4" FMC (Flexible Metal Conduit). Maximum conductor counts per AWG at the NEC 2023 40% fill cap for three or more conductors.

FIG. 02

MAXIMUM CONDUCTORS BY WIRE GAUGE

40% fill (3+ conductors per NEC 2023 Ch.9 Table 1). 1-1/4" FMC interior area = 1.2770 in².

AWGTHHN / THWN-2XHHW-2RHH / RHW-2
#1452024
#1238019
#1024015
#81409
#61007
#4605
#3504
#2404
#1302
#1/0200
FIG. 03

WORKED EXAMPLE & NEC REFERENCES

The NEC numbers behind 1-1/4" FMC

NEC 2023 Chapter 9, Table 4 lists the interior cross-sectional area of every standard trade size for each conduit family. For 1-1/4" FMC (Article 348), the total 100% area is 1.2770 in². The allowable conductor fill is then derived from Table 1: 53% for a single conductor (0.6768 in²), 31% for two (0.3959 in²), and 40% for three or more (0.5108 in²) — covering nearly all real-world raceway pulls.

Worked example — four #12 THHN conductors

Each #12 THHN conductor occupies 0.0133 in² (NEC Ch.9 Table 5). Four conductors fill 4 × 0.0133 = 0.0532 in², which is 0.0532 ÷ 1.2770 = 4.2% of total area. Because that is well below the 40% NEC limit for 0.5108 in², the pull is compliant — and you can keep adding conductors up to 38× #12 THHN before exceeding the cap.

If you exceed the fill cap

Step up one trade size. Increase a 1-1/4" FMC to 1-1/2" when the calculated fill crosses 40%. Reducing one trade size is rarely worth the labor: pull tension climbs fast, jam probability spikes (NEC Ch.9 Informational Note re: 2.8–3.2 conduit-ID to wire-OD ratio), and you lose room for de-rating or future moves.

Source citations

NFPA 70 (2023) — National Electrical Code. Chapter 9, Table 1: percent of cross section of conduit and tubing for conductors. Table 4: dimensions and percent area of conduit and tubing (Article 348). Table 5: dimensions of insulated conductors.

FIG. 04

TRY IT — 1-1/4" FMC LIVE

Preloaded with this conduit. Change the conductor gauge, insulation, or count and read the fill in real time.

NEC 2023 · CH.9
A · CONDUIT TYPE
B · TRADE SIZE
DESCRIPTION
FMC — Flexible Metal Conduit
C · CONDUCTORS
01
RESULT · FILL %
APPROACHING LIMIT
39.6%
OF 40%
ALLOWED
0254075100
CONDUCTORS
38
WIRE AREA
0.505in²
CONDUIT AREA
1.277in²
JAM RISK
LOW
  • Three or more conductors — NEC allows 40% fill.
+14
CONDUIT
FMC · 1-1/4"
CONDUCTOR
12 AWG · THHN
FIG. 05

FREQUENTLY ASKED QUESTIONS

1.2770 in² (100% area), per NEC 2023 Chapter 9, Table 4 — Article 348. The allowable conductor fill is 0.5108 in² at 40% (3+ conductors), 0.3959 in² at 31% (2 conductors), and 0.6768 in² at 53% (1 conductor).