Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
FIG. 01 — SIZE-SPECIFIC FILL

4" FMC Conduit Fill Chart

How many wires fit in 4" FMC (Flexible Metal Conduit). Maximum conductor counts per AWG at the NEC 2023 40% fill cap for three or more conductors.

FIG. 02

MAXIMUM CONDUCTORS BY WIRE GAUGE

40% fill (3+ conductors per NEC 2023 Ch.9 Table 1). 4" FMC interior area = 12.5660 in².

AWGTHHN / THWN-2XHHW-2RHH / RHW-2
#145180240
#123780193
#102380151
#8137090
#699069
#461051
#351044
#243037
#132026
#1/027022
#2/022019
#4/015013
FIG. 03

WORKED EXAMPLE & NEC REFERENCES

The NEC numbers behind 4" FMC

NEC 2023 Chapter 9, Table 4 lists the interior cross-sectional area of every standard trade size for each conduit family. For 4" FMC (Article 348), the total 100% area is 12.5660 in². The allowable conductor fill is then derived from Table 1: 53% for a single conductor (6.6600 in²), 31% for two (3.8955 in²), and 40% for three or more (5.0264 in²) — covering nearly all real-world raceway pulls.

Worked example — four #12 THHN conductors

Each #12 THHN conductor occupies 0.0133 in² (NEC Ch.9 Table 5). Four conductors fill 4 × 0.0133 = 0.0532 in², which is 0.0532 ÷ 12.5660 = 0.4% of total area. Because that is well below the 40% NEC limit for 5.0264 in², the pull is compliant — and you can keep adding conductors up to 378× #12 THHN before exceeding the cap.

If you exceed the fill cap

Step up one trade size. Increase a 4" FMC to the next available trade size when the calculated fill crosses 40%. Reducing one trade size is rarely worth the labor: pull tension climbs fast, jam probability spikes (NEC Ch.9 Informational Note re: 2.8–3.2 conduit-ID to wire-OD ratio), and you lose room for de-rating or future moves.

Source citations

NFPA 70 (2023) — National Electrical Code. Chapter 9, Table 1: percent of cross section of conduit and tubing for conductors. Table 4: dimensions and percent area of conduit and tubing (Article 348). Table 5: dimensions of insulated conductors.

FIG. 04

TRY IT — 4" FMC LIVE

Preloaded with this conduit. Change the conductor gauge, insulation, or count and read the fill in real time.

NEC 2023 · CH.9
A · CONDUIT TYPE
B · TRADE SIZE
DESCRIPTION
FMC — Flexible Metal Conduit
C · CONDUCTORS
01
RESULT · FILL %
OVER NEC LIMIT
40.0%
OF 40%
ALLOWED
0254075100
CONDUCTORS
378
WIRE AREA
5.027in²
CONDUIT AREA
12.566in²
JAM RISK
LOW
  • Three or more conductors — NEC allows 40% fill.
  • Fill exceeds NEC limit of 40%. Increase conduit size.
+354
CONDUIT
FMC · 4"
CONDUCTOR
12 AWG · THHN
FIG. 05

FREQUENTLY ASKED QUESTIONS

12.5660 in² (100% area), per NEC 2023 Chapter 9, Table 4 — Article 348. The allowable conductor fill is 5.0264 in² at 40% (3+ conductors), 3.8955 in² at 31% (2 conductors), and 6.6600 in² at 53% (1 conductor).