Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · USE CASE

Wire Fill for Mini-Split Heat Pump

Mini-split wire fill: 9k-18k BTU uses 14-12 AWG on 15-20A breaker, 24k-36k BTU needs 10-8 AWG on 30-40A. NEC 440 with LFNC whip to outdoor unit.

·5 MIN READ·EDITORIAL

Wire fill for mini-split heat pump circuits is governed by NEC Article 440 (HVAC equipment) and NEC 430 for the motor compressor. A typical 12,000 BTU (1-ton) ductless mini-split uses a 15A 2-pole breaker, 14 AWG copper THHN to an outdoor disconnect, and a short LFNC whip to the condenser. Larger 24,000-36,000 BTU multi-zone systems need 30-40A breakers with 10 or 8 AWG copper. The interconnect cable between outdoor and indoor units is usually a 14/4 stranded shielded cable provided by the installer.

Load characteristics

Mini-splits are highly efficient inverter-driven systems with low FLA but inrush spikes:

Mini-split size Typical MCA MOCP Breaker
9,000 BTU (3/4-ton) 9-12A 15A 15A
12,000 BTU (1-ton) 10-15A 15-20A 15A or 20A
18,000 BTU (1.5-ton) 14-18A 20-25A 20A or 25A
24,000 BTU (2-ton) 18-22A 25-30A 25A or 30A
36,000 BTU (3-ton multi-zone) 22-28A 30-40A 30A or 40A
48,000 BTU (4-ton multi-zone) 25-32A 35-50A 40A or 50A

Always confirm with the unit nameplate — variable-speed inverter systems often have much lower MCA than equivalent-tonnage conventional split systems.

NEC code references

  • NEC 440.4 — nameplate markings (MCA, MOCP)
  • NEC 440.14 — disconnect within sight of outdoor unit
  • NEC 440.22 — branch-circuit overcurrent protection
  • NEC 440.32 — conductor sizing (125% of largest motor RLA)
  • NEC 350 — LFMC (liquidtight flexible metal conduit)
  • NEC 356 — LFNC (liquidtight flexible nonmetallic conduit)

Conductor sizing

Use 75°C column of NEC 310.16, size to MCA:

MCA Copper THHN Aluminum
up to 15A 14 AWG 12 AWG
up to 20A 12 AWG 10 AWG
up to 25A 10 AWG 8 AWG
up to 30A 10 AWG 8 AWG
up to 50A 6 AWG 4 AWG

EGC per NEC 250.122 based on MOCP:

MOCP Copper EGC
15A 14 AWG
20A 12 AWG
30A 10 AWG
40A 10 AWG
50A 10 AWG

Conduit sizing

Mini-split outdoor circuits are 2-wire 240V (no neutral) + EGC. Most installs use:

  • Home-run from panel to outdoor disconnect: EMT, PVC, or NM-B through framing
  • Whip from disconnect to condenser: 4-6 ft of LFNC (most common) or LFMC
Circuit Conductors Area 1/2" EMT 3/4" EMT 1/2" LFNC
15A (14 AWG) 2 × 14 + 1 × 14 EGC 0.0291 in² 14.8% 6.2% 16.7%
20A (12 AWG) 2 × 12 + 1 × 12 EGC 0.0399 in² 20.3% 8.4% 22.9%
30A (10 AWG) 2 × 10 + 1 × 10 EGC 0.0780 in² 39.6% (pass tight) 16.5% 44.7% — needs 3/4"
40A (8 AWG) 2 × 8 + 1 × 10 EGC 0.0855 in² over 40% — fails 18.1% over 40% — fails
50A (6 AWG) 2 × 6 + 1 × 10 EGC 0.1225 in² over 40% — fails 25.9% 70%+ — needs 3/4"

1/2-inch EMT handles 15A and 20A circuits with margin. 3/4-inch EMT for anything 25A and larger.

For the LFNC whip, use 1/2-inch for 14-12 AWG and 3/4-inch for 10-6 AWG.

Special requirements

  • Disconnect within sight: Non-fused pullout (60A typical) NEMA 3R, on exterior wall.
  • Whip to outdoor unit: 4-6 ft of LFNC is the universal standard. Bonding bushings if using LFMC over 6 ft.
  • Indoor unit power: Most single-zone mini-splits power the outdoor unit and use a 14/4 interconnect to the indoor head. Multi-zone systems often power the outdoor unit only.
  • Communication cable: Run separately from line voltage in commercial installs. For residential, the 14/4 shielded cable typically runs alongside the refrigerant line set in the wall sleeve.
  • Drain heater: Cold-climate outdoor units may have a base pan heater drawing 0.5-1A continuous — already included in MCA.
  • Outdoor receptacle: NEC 210.8(F) requires GFCI for outdoor receptacles within sight of HVAC equipment.

Worked example — 18,000 BTU single-zone mini-split, 25 ft from panel

Nameplate: MCA = 14.5A, MOCP = 20A

  • Breaker: 20A 2-pole in main panel
  • Home-run conductors: 12 AWG copper THHN × 2 (L1, L2) + 12 AWG copper EGC
  • Home-run raceway: 1/2" EMT, 25 ft from panel to outdoor disconnect
  • Fill check (home-run): 3 × 0.0133 = 0.0399 in² in 1/2" EMT (0.122 in² 40% limit) = 32.7%, pass.
  • Disconnect: 30A non-fused pullout, NEMA 3R, mounted within 3 ft of condenser.
  • Whip: 4 ft of 1/2" LFNC with 12 AWG conductors + 12 AWG EGC. Fill: 3 × 0.0133 = 0.0399 in² in 1/2" LFNC (~22.9%), pass.
  • Indoor head: Powered from outdoor unit via 14/4 stranded shielded cable per manufacturer.

For a 36,000 BTU multi-zone:

  • Breaker: 40A 2-pole
  • Conductors: 8 AWG copper THHN × 2 + 10 AWG copper EGC in 3/4" EMT
  • Whip: 3/4" LFNC, same 8 AWG conductors + 10 AWG EGC

Cross-check with the Conduit Fill Calculator.

Quick reference

BTU MCA Breaker Copper wire Home-run conduit LFNC whip
9,000 10A 15A 14 AWG × 2 1/2" EMT 1/2"
12,000 13A 15A 14 AWG × 2 1/2" EMT 1/2"
18,000 16A 20A 12 AWG × 2 1/2" EMT 1/2"
24,000 20A 25A 10 AWG × 2 1/2" EMT 3/4" LFNC
36,000 26A 35-40A 8 AWG × 2 3/4" EMT 3/4" LFNC
48,000 30A 50A 6 AWG × 2 3/4" EMT 3/4" LFNC

Related

FIG. 99

FAQ

Yes. NEC 440.14 requires a disconnect within sight from and readily accessible from the outdoor condenser. A 30A or 60A non-fused pullout disconnect mounted on the wall next to the outdoor unit is standard. Some inverter-driven mini-splits include an internal isolator, but a separate field-installed disconnect is still required.

METHODOLOGY & SOURCES

This page's figures are transcribed from NEC 2023 (NFPA 70) Chapter 9, Tables 1, 4 and 5, and checked by a version-controlled automated test suite — they are not signed off by a licensed professional. WireFillChart is an independent reference, not affiliated with or endorsed by NFPA. Always verify against the code edition adopted by your local authority having jurisdiction (AHJ).

WireFillChart Editorial Team·EDITORIAL·