WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · USE CASE

Wire Fill for Mini-Split Heat Pump

Mini-split wire fill: 9k-18k BTU uses 14-12 AWG on 15-20A breaker, 24k-36k BTU needs 10-8 AWG on 30-40A. NEC 440 with LFNC whip to outdoor unit.

·5 MIN READ·EDITORIAL

Wire fill for mini-split heat pump circuits is governed by NEC Article 440 (HVAC equipment) and NEC 430 for the motor compressor. A typical 12,000 BTU (1-ton) ductless mini-split uses a 15A 2-pole breaker, 14 AWG copper THHN to an outdoor disconnect, and a short LFNC whip to the condenser. Larger 24,000-36,000 BTU multi-zone systems need 30-40A breakers with 10 or 8 AWG copper. The interconnect cable between outdoor and indoor units is usually a 14/4 stranded shielded cable provided by the installer.

Load characteristics

Mini-splits are highly efficient inverter-driven systems with low FLA but inrush spikes:

Mini-split size Typical MCA MOCP Breaker
9,000 BTU (3/4-ton) 9-12A 15A 15A
12,000 BTU (1-ton) 10-15A 15-20A 15A or 20A
18,000 BTU (1.5-ton) 14-18A 20-25A 20A or 25A
24,000 BTU (2-ton) 18-22A 25-30A 25A or 30A
36,000 BTU (3-ton multi-zone) 22-28A 30-40A 30A or 40A
48,000 BTU (4-ton multi-zone) 25-32A 35-50A 40A or 50A

Always confirm with the unit nameplate — variable-speed inverter systems often have much lower MCA than equivalent-tonnage conventional split systems.

NEC code references

  • NEC 440.4 — nameplate markings (MCA, MOCP)
  • NEC 440.14 — disconnect within sight of outdoor unit
  • NEC 440.22 — branch-circuit overcurrent protection
  • NEC 440.32 — conductor sizing (125% of largest motor RLA)
  • NEC 350 — LFMC (liquidtight flexible metal conduit)
  • NEC 356 — LFNC (liquidtight flexible nonmetallic conduit)

Conductor sizing

Use 75°C column of NEC 310.16, size to MCA:

MCA Copper THHN Aluminum
up to 15A 14 AWG 12 AWG
up to 20A 12 AWG 10 AWG
up to 25A 10 AWG 8 AWG
up to 30A 10 AWG 8 AWG
up to 50A 6 AWG 4 AWG

EGC per NEC 250.122 based on MOCP:

MOCP Copper EGC
15A 14 AWG
20A 12 AWG
30A 10 AWG
40A 10 AWG
50A 10 AWG

Conduit sizing

Mini-split outdoor circuits are 2-wire 240V (no neutral) + EGC. Most installs use:

  • Home-run from panel to outdoor disconnect: EMT, PVC, or NM-B through framing
  • Whip from disconnect to condenser: 4-6 ft of LFNC (most common) or LFMC
Circuit Conductors Area 1/2" EMT 3/4" EMT 1/2" LFNC
15A (14 AWG) 2 × 14 + 1 × 14 EGC 0.0291 in² 14.8% 6.2% 16.7%
20A (12 AWG) 2 × 12 + 1 × 12 EGC 0.0399 in² 20.3% 8.4% 22.9%
30A (10 AWG) 2 × 10 + 1 × 10 EGC 0.0780 in² 39.6% (pass tight) 16.5% 44.7% — needs 3/4"
40A (8 AWG) 2 × 8 + 1 × 10 EGC 0.0855 in² over 40% — fails 18.1% over 40% — fails
50A (6 AWG) 2 × 6 + 1 × 10 EGC 0.1225 in² over 40% — fails 25.9% 70%+ — needs 3/4"

1/2-inch EMT handles 15A and 20A circuits with margin. 3/4-inch EMT for anything 25A and larger.

For the LFNC whip, use 1/2-inch for 14-12 AWG and 3/4-inch for 10-6 AWG.

Special requirements

  • Disconnect within sight: Non-fused pullout (60A typical) NEMA 3R, on exterior wall.
  • Whip to outdoor unit: 4-6 ft of LFNC is the universal standard. Bonding bushings if using LFMC over 6 ft.
  • Indoor unit power: Most single-zone mini-splits power the outdoor unit and use a 14/4 interconnect to the indoor head. Multi-zone systems often power the outdoor unit only.
  • Communication cable: Run separately from line voltage in commercial installs. For residential, the 14/4 shielded cable typically runs alongside the refrigerant line set in the wall sleeve.
  • Drain heater: Cold-climate outdoor units may have a base pan heater drawing 0.5-1A continuous — already included in MCA.
  • Outdoor receptacle: NEC 210.8(F) requires GFCI for outdoor receptacles within sight of HVAC equipment.

Worked example — 18,000 BTU single-zone mini-split, 25 ft from panel

Nameplate: MCA = 14.5A, MOCP = 20A

  • Breaker: 20A 2-pole in main panel
  • Home-run conductors: 12 AWG copper THHN × 2 (L1, L2) + 12 AWG copper EGC
  • Home-run raceway: 1/2" EMT, 25 ft from panel to outdoor disconnect
  • Fill check (home-run): 3 × 0.0133 = 0.0399 in² in 1/2" EMT (0.122 in² 40% limit) = 32.7%, pass.
  • Disconnect: 30A non-fused pullout, NEMA 3R, mounted within 3 ft of condenser.
  • Whip: 4 ft of 1/2" LFNC with 12 AWG conductors + 12 AWG EGC. Fill: 3 × 0.0133 = 0.0399 in² in 1/2" LFNC (~22.9%), pass.
  • Indoor head: Powered from outdoor unit via 14/4 stranded shielded cable per manufacturer.

For a 36,000 BTU multi-zone:

  • Breaker: 40A 2-pole
  • Conductors: 8 AWG copper THHN × 2 + 10 AWG copper EGC in 3/4" EMT
  • Whip: 3/4" LFNC, same 8 AWG conductors + 10 AWG EGC

Cross-check with the Conduit Fill Calculator.

Quick reference

BTU MCA Breaker Copper wire Home-run conduit LFNC whip
9,000 10A 15A 14 AWG × 2 1/2" EMT 1/2"
12,000 13A 15A 14 AWG × 2 1/2" EMT 1/2"
18,000 16A 20A 12 AWG × 2 1/2" EMT 1/2"
24,000 20A 25A 10 AWG × 2 1/2" EMT 3/4" LFNC
36,000 26A 35-40A 8 AWG × 2 3/4" EMT 3/4" LFNC
48,000 30A 50A 6 AWG × 2 3/4" EMT 3/4" LFNC

Related

FIG. 99

FAQ

Yes. NEC 440.14 requires a disconnect within sight from and readily accessible from the outdoor condenser. A 30A or 60A non-fused pullout disconnect mounted on the wall next to the outdoor unit is standard. Some inverter-driven mini-splits include an internal isolator, but a separate field-installed disconnect is still required.