Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · USE CASE

Conduit Fill for Central A/C Disconnect

Central A/C disconnect wire fill: 3-ton uses 10 AWG copper on 30A breaker, 5-ton uses 8 AWG on 40A. NEC Article 440 with MCA/MOCP from nameplate.

·4 MIN READ·EDITORIAL

Wire fill for central A/C disconnect is governed by NEC Article 440 (air conditioning and refrigerating equipment). A typical 3-ton residential central A/C uses a 30A 2-pole breaker, 10 AWG copper THHN to the outdoor disconnect, and a 6-foot LFMC or LFNC whip to the condensing unit. A 5-ton unit usually gets 40-60A breaker and 8 AWG copper. The Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOCP) on the equipment nameplate dictate sizing, not standard motor circuit tables.

Load characteristics

Central A/C condensing units have a compressor (largest motor) and condenser fan (smaller motor):

A/C tonnage Typical MCA Typical MOCP Breaker
2 ton (~24,000 BTU) 13-18A 25-30A 25A or 30A
2.5 ton (~30,000 BTU) 16-22A 30-35A 30A or 35A
3 ton (~36,000 BTU) 18-25A 30-40A 30A or 40A
3.5 ton (~42,000 BTU) 22-28A 35-45A 40A or 45A
4 ton (~48,000 BTU) 25-32A 40-50A 40A or 50A
5 ton (~60,000 BTU) 30-40A 50-60A 50A or 60A

Always confirm with the equipment nameplate — high-efficiency variable-speed units may have lower MCA than older single-stage units of the same tonnage.

NEC code references

  • NEC 440.4 — markings on nameplate (MCA, MOCP)
  • NEC 440.14 — disconnect within sight of motor compressor
  • NEC 440.22 — application of MOCP rules
  • NEC 440.32 — branch-circuit conductors at 125% of largest motor compressor RLA
  • NEC 440.33 — multiple-motor and combination loads
  • NEC 250.122 — equipment grounding conductor sizing

Conductor sizing

Size to MCA on the nameplate. Use 75°C column of NEC 310.16:

MCA Copper THHN Aluminum
up to 15A 14 AWG 12 AWG
up to 20A 12 AWG 10 AWG
up to 25A 10 AWG 8 AWG
up to 35A 8 AWG 6 AWG
up to 50A 6 AWG 4 AWG

EGC per NEC 250.122 sized to MOCP (not MCA):

MOCP Copper EGC
30A 10 AWG
40-60A 10 AWG
100A 8 AWG

Conduit sizing

A/C circuits are typically 3-wire (2 hots + EGC, no neutral). Single-phase 240V hermetic compressors don't need a neutral.

Circuit Conductors Area 1/2" EMT 3/4" EMT
3-ton (30A, 10 AWG) 2 × 10 + 1 × 10 EGC 0.0780 in² 39.6% pass tight 16.5%
4-ton (40A, 8 AWG) 2 × 8 + 1 × 10 EGC 0.0855 in² over 40% — fails 18.1%
5-ton (50A, 6 AWG) 2 × 6 + 1 × 10 EGC 0.1225 in² over 40% — fails 25.9%
5-ton (60A, 6 AWG) 2 × 6 + 1 × 10 EGC 0.1225 in² over 40% — fails 25.9%

3/4-inch EMT or PVC handles essentially all residential central A/C circuits.

The whip from disconnect to condenser is usually 6 ft of liquidtight flexible conduit (LFMC or LFNC). Common sizes:

Whip size Typical for
1/2" LFNC 10 AWG conductors
3/4" LFNC 8 AWG conductors
3/4" LFMC 6 AWG with grounding bushing

LFMC is preferred when used as the EGC; LFNC requires a separate copper EGC inside.

Special requirements

  • Disconnect within sight — NEC 440.14. Mounted on exterior wall within sight of condenser, usually pullout-style with fuse holders.
  • Fused vs non-fused disconnect — NEC doesn't require fuses if the upstream breaker provides protection per nameplate MOCP. Many AHJs prefer non-fused pullout for residential.
  • Outdoor location — Use weather-resistant enclosure, NEMA 3R minimum.
  • Bonding — LFMC requires bonding bushings if used as the EGC over a certain length; separate EGC inside the whip is the safer practice.
  • GFCI for service receptacle — NEC 210.8(F) requires GFCI on outdoor receptacles within sight of HVAC equipment.

Worked example — 3-ton central A/C, 35 ft from main panel

Nameplate: MCA = 22.6A, MOCP = 40A, RLA = 16.5A

  • Breaker: 40A 2-pole in main panel (or 35A if available)
  • Conductors: 10 AWG copper THHN × 2 + 10 AWG copper EGC (MCA of 22.6A requires 25A wire — 10 AWG at 75°C is 35A, fine)
  • Raceway home-run: 3/4" EMT from main panel to outdoor disconnect, 35 ft.
  • Disconnect: 60A non-fused pullout, NEMA 3R, mounted within 3 ft of condenser.
  • Whip: 6 ft of 1/2" LFNC with 10 AWG conductors + separate EGC.
  • Fill check (home-run): 3 × 0.0260 = 0.0780 in² in 3/4" EMT = 16.5%, pass.

For a 5-ton: bump to 8 AWG (some prefer 6 AWG for margin), 50A or 60A breaker, 3/4" EMT.

Quick reference

A/C tonnage Typical MCA Breaker Copper wire Conduit
2 ton 16A 25A 10 AWG 3/4" EMT
3 ton 23A 30A or 40A 10 AWG 3/4" EMT
4 ton 28A 40A 8 AWG 3/4" EMT
5 ton 36A 50-60A 8 AWG or 6 AWG 3/4" EMT

Related

FIG. 99

FAQ

Hermetic compressor motors have high inrush current. NEC 440.22 lets the Maximum Overcurrent Protection (MOCP) be up to 175% (or 225% with adjustment) of rated-load current, while the conductors only need to be sized at 125% of FLA. That's why a 5-ton unit can use 8 AWG copper (50A wire) on a 40-60A breaker.

METHODOLOGY & SOURCES

This page's figures are transcribed from NEC 2023 (NFPA 70) Chapter 9, Tables 1, 4 and 5, and checked by a version-controlled automated test suite — they are not signed off by a licensed professional. WireFillChart is an independent reference, not affiliated with or endorsed by NFPA. Always verify against the code edition adopted by your local authority having jurisdiction (AHJ).

WireFillChart Editorial Team·EDITORIAL·