WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · USE CASE

Conduit Fill for Central A/C Disconnect

Central A/C disconnect wire fill: 3-ton uses 10 AWG copper on 30A breaker, 5-ton uses 8 AWG on 40A. NEC Article 440 with MCA/MOCP from nameplate.

·4 MIN READ·EDITORIAL

Wire fill for central A/C disconnect is governed by NEC Article 440 (air conditioning and refrigerating equipment). A typical 3-ton residential central A/C uses a 30A 2-pole breaker, 10 AWG copper THHN to the outdoor disconnect, and a 6-foot LFMC or LFNC whip to the condensing unit. A 5-ton unit usually gets 40-60A breaker and 8 AWG copper. The Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOCP) on the equipment nameplate dictate sizing, not standard motor circuit tables.

Load characteristics

Central A/C condensing units have a compressor (largest motor) and condenser fan (smaller motor):

A/C tonnage Typical MCA Typical MOCP Breaker
2 ton (~24,000 BTU) 13-18A 25-30A 25A or 30A
2.5 ton (~30,000 BTU) 16-22A 30-35A 30A or 35A
3 ton (~36,000 BTU) 18-25A 30-40A 30A or 40A
3.5 ton (~42,000 BTU) 22-28A 35-45A 40A or 45A
4 ton (~48,000 BTU) 25-32A 40-50A 40A or 50A
5 ton (~60,000 BTU) 30-40A 50-60A 50A or 60A

Always confirm with the equipment nameplate — high-efficiency variable-speed units may have lower MCA than older single-stage units of the same tonnage.

NEC code references

  • NEC 440.4 — markings on nameplate (MCA, MOCP)
  • NEC 440.14 — disconnect within sight of motor compressor
  • NEC 440.22 — application of MOCP rules
  • NEC 440.32 — branch-circuit conductors at 125% of largest motor compressor RLA
  • NEC 440.33 — multiple-motor and combination loads
  • NEC 250.122 — equipment grounding conductor sizing

Conductor sizing

Size to MCA on the nameplate. Use 75°C column of NEC 310.16:

MCA Copper THHN Aluminum
up to 15A 14 AWG 12 AWG
up to 20A 12 AWG 10 AWG
up to 25A 10 AWG 8 AWG
up to 35A 8 AWG 6 AWG
up to 50A 6 AWG 4 AWG

EGC per NEC 250.122 sized to MOCP (not MCA):

MOCP Copper EGC
30A 10 AWG
40-60A 10 AWG
100A 8 AWG

Conduit sizing

A/C circuits are typically 3-wire (2 hots + EGC, no neutral). Single-phase 240V hermetic compressors don't need a neutral.

Circuit Conductors Area 1/2" EMT 3/4" EMT
3-ton (30A, 10 AWG) 2 × 10 + 1 × 10 EGC 0.0780 in² 39.6% pass tight 16.5%
4-ton (40A, 8 AWG) 2 × 8 + 1 × 10 EGC 0.0855 in² over 40% — fails 18.1%
5-ton (50A, 6 AWG) 2 × 6 + 1 × 10 EGC 0.1225 in² over 40% — fails 25.9%
5-ton (60A, 6 AWG) 2 × 6 + 1 × 10 EGC 0.1225 in² over 40% — fails 25.9%

3/4-inch EMT or PVC handles essentially all residential central A/C circuits.

The whip from disconnect to condenser is usually 6 ft of liquidtight flexible conduit (LFMC or LFNC). Common sizes:

Whip size Typical for
1/2" LFNC 10 AWG conductors
3/4" LFNC 8 AWG conductors
3/4" LFMC 6 AWG with grounding bushing

LFMC is preferred when used as the EGC; LFNC requires a separate copper EGC inside.

Special requirements

  • Disconnect within sight — NEC 440.14. Mounted on exterior wall within sight of condenser, usually pullout-style with fuse holders.
  • Fused vs non-fused disconnect — NEC doesn't require fuses if the upstream breaker provides protection per nameplate MOCP. Many AHJs prefer non-fused pullout for residential.
  • Outdoor location — Use weather-resistant enclosure, NEMA 3R minimum.
  • Bonding — LFMC requires bonding bushings if used as the EGC over a certain length; separate EGC inside the whip is the safer practice.
  • GFCI for service receptacle — NEC 210.8(F) requires GFCI on outdoor receptacles within sight of HVAC equipment.

Worked example — 3-ton central A/C, 35 ft from main panel

Nameplate: MCA = 22.6A, MOCP = 40A, RLA = 16.5A

  • Breaker: 40A 2-pole in main panel (or 35A if available)
  • Conductors: 10 AWG copper THHN × 2 + 10 AWG copper EGC (MCA of 22.6A requires 25A wire — 10 AWG at 75°C is 35A, fine)
  • Raceway home-run: 3/4" EMT from main panel to outdoor disconnect, 35 ft.
  • Disconnect: 60A non-fused pullout, NEMA 3R, mounted within 3 ft of condenser.
  • Whip: 6 ft of 1/2" LFNC with 10 AWG conductors + separate EGC.
  • Fill check (home-run): 3 × 0.0260 = 0.0780 in² in 3/4" EMT = 16.5%, pass.

For a 5-ton: bump to 8 AWG (some prefer 6 AWG for margin), 50A or 60A breaker, 3/4" EMT.

Quick reference

A/C tonnage Typical MCA Breaker Copper wire Conduit
2 ton 16A 25A 10 AWG 3/4" EMT
3 ton 23A 30A or 40A 10 AWG 3/4" EMT
4 ton 28A 40A 8 AWG 3/4" EMT
5 ton 36A 50-60A 8 AWG or 6 AWG 3/4" EMT

Related

FIG. 99

FAQ

Hermetic compressor motors have high inrush current. NEC 440.22 lets the Maximum Overcurrent Protection (MOCP) be up to 175% (or 225% with adjustment) of rated-load current, while the conductors only need to be sized at 125% of FLA. That's why a 5-ton unit can use 8 AWG copper (50A wire) on a 40-60A breaker.