Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · ARTICLE

What Gauge Wire for a 30-Amp Circuit?

Use 10 AWG copper for 30-amp circuits per NEC 240.4(D). 10 AWG THHN is rated 35A at 75°C, providing 5A margin for the 30A breaker.

·2 MIN READ·EDITORIAL

10 AWG copper is the standard wire gauge for 30-amp circuits, per NEC 240.4(D)(7). 10 AWG THHN has a 90°C ampacity of 40A and a 75°C ampacity of 35A — both above the 30A breaker rating.

NEC reference

Rule Effect
NEC 240.4(D)(7) 10 AWG copper limited to 30A overcurrent protection (small-conductor rule)
NEC Table 310.16 10 AWG @ 90°C = 40A; @ 75°C = 35A; @ 60°C terminals = 30A
NEC 210.21(B) 30A receptacle types: NEMA 6-30, 14-30, L6-30, L14-30

Common 30-amp circuits

  • Electric water heater (4500W typical, 240V) — 30A 2-pole breaker
  • Electric clothes dryer (5500W typical) — 30A 2-pole breaker, neutral required for 120V controls
  • Window/mini-split A/C (large units) — 30A 240V
  • Travel trailer / RV pedestal — 30A TT-30 receptacle
  • Baseboard heat circuit — 30A 240V for ~5500W
  • Level 2 EV charger at 24A continuous — 30A 240V

Conductors per circuit

Circuit type Conductors Wire fill in 3/4" EMT
30A 240V (no neutral): water heater, AC 2 hots + 1 EGC = 3 11.9% fill
30A 240V with neutral (dryer): 2 hots + 1 neutral + 1 EGC = 4 15.8% fill

3/4" EMT fits 10 of 10 AWG THHN. Three full dryer circuits (12 conductors) requires 1" EMT (16 of 10 AWG, 39.0% fill).

Ampacity derating

With 4–6 CCCs in conduit: 40A × 0.80 = 32A — sufficient for 30A breaker. With 7–9 CCCs: 40A × 0.70 = 28Adrops below 30A breaker rating. Either reduce conductor count or upsize to 8 AWG (55A × 0.70 = 38.5A).

Voltage drop at 30A

10 AWG copper: 0.999 Ω/1000 ft. At 30A on 100 ft one-way (240V circuit, 200 ft round trip):

V drop = 200 × 30 × (0.999 / 1000) = 6.0V (2.5% of 240V)

Within 3% — 10 AWG is fine up to ~120 ft for 30A circuits.

Quick reference

  • Wire: 10 AWG copper THHN/THWN-2
  • Breaker: 30A 1-pole or 2-pole (240V)
  • Receptacle: NEMA 6-30 (no neutral), 14-30 (with neutral), L-style for locking applications
  • Conduit minimum: 1/2" EMT for one circuit; 3/4" for two; 1" for three

For specific configurations, run the conduit fill calculator.

FIG. 99

FAQ

10 AWG copper is the standard for 30-amp circuits per NEC 240.4(D)(7). 10 AWG THHN: 40A at 90°C, 35A at 75°C — well above the 30A breaker rating.

METHODOLOGY & SOURCES

This page's figures are transcribed from NEC 2023 (NFPA 70) Chapter 9, Tables 1, 4 and 5, and checked by a version-controlled automated test suite — they are not signed off by a licensed professional. WireFillChart is an independent reference, not affiliated with or endorsed by NFPA. Always verify against the code edition adopted by your local authority having jurisdiction (AHJ).

WireFillChart Editorial Team·EDITORIAL·