WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · ARTICLE

What Gauge Wire for a 30-Amp Circuit?

Use 10 AWG copper for 30-amp circuits per NEC 240.4(D). 10 AWG THHN is rated 35A at 75°C, providing 5A margin for the 30A breaker.

·2 MIN READ·EDITORIAL

10 AWG copper is the standard wire gauge for 30-amp circuits, per NEC 240.4(D)(7). 10 AWG THHN has a 90°C ampacity of 40A and a 75°C ampacity of 35A — both above the 30A breaker rating.

NEC reference

Rule Effect
NEC 240.4(D)(7) 10 AWG copper limited to 30A overcurrent protection (small-conductor rule)
NEC Table 310.16 10 AWG @ 90°C = 40A; @ 75°C = 35A; @ 60°C terminals = 30A
NEC 210.21(B) 30A receptacle types: NEMA 6-30, 14-30, L6-30, L14-30

Common 30-amp circuits

  • Electric water heater (4500W typical, 240V) — 30A 2-pole breaker
  • Electric clothes dryer (5500W typical) — 30A 2-pole breaker, neutral required for 120V controls
  • Window/mini-split A/C (large units) — 30A 240V
  • Travel trailer / RV pedestal — 30A TT-30 receptacle
  • Baseboard heat circuit — 30A 240V for ~5500W
  • Level 2 EV charger at 24A continuous — 30A 240V

Conductors per circuit

Circuit type Conductors Wire fill in 3/4" EMT
30A 240V (no neutral): water heater, AC 2 hots + 1 EGC = 3 11.9% fill
30A 240V with neutral (dryer): 2 hots + 1 neutral + 1 EGC = 4 15.8% fill

3/4" EMT fits 10 of 10 AWG THHN. Three full dryer circuits (12 conductors) requires 1" EMT (16 of 10 AWG, 39.0% fill).

Ampacity derating

With 4–6 CCCs in conduit: 40A × 0.80 = 32A — sufficient for 30A breaker. With 7–9 CCCs: 40A × 0.70 = 28Adrops below 30A breaker rating. Either reduce conductor count or upsize to 8 AWG (55A × 0.70 = 38.5A).

Voltage drop at 30A

10 AWG copper: 0.999 Ω/1000 ft. At 30A on 100 ft one-way (240V circuit, 200 ft round trip):

V drop = 200 × 30 × (0.999 / 1000) = 6.0V (2.5% of 240V)

Within 3% — 10 AWG is fine up to ~120 ft for 30A circuits.

Quick reference

  • Wire: 10 AWG copper THHN/THWN-2
  • Breaker: 30A 1-pole or 2-pole (240V)
  • Receptacle: NEMA 6-30 (no neutral), 14-30 (with neutral), L-style for locking applications
  • Conduit minimum: 1/2" EMT for one circuit; 3/4" for two; 1" for three

For specific configurations, run the conduit fill calculator.

FIG. 99

FAQ

10 AWG copper is the standard for 30-amp circuits per NEC 240.4(D)(7). 10 AWG THHN: 40A at 90°C, 35A at 75°C — well above the 30A breaker rating.