Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · ARTICLE

What Gauge Wire for a 20-Amp Circuit?

Use 12 AWG copper for 20-amp branch circuits per NEC 240.4(D). 12 AWG THHN handles 25A at 75°C terminals, more than enough for 20A protection.

·2 MIN READ·EDITORIAL

12 AWG copper is the standard wire gauge for 20-amp branch circuits, per NEC 240.4(D)(3). 12 AWG THHN has a 90°C ampacity of 30A but is limited to 20A by the NEC small-conductor protection rule.

NEC reference

Rule Effect
NEC 240.4(D)(5) 12 AWG copper limited to 20A overcurrent protection
NEC Table 310.16 12 AWG @ 90°C = 30A; @ 75°C = 25A; @ 60°C terminals = 20A
NEC 210.11(C)(1) Kitchen small-appliance branch circuits must be 20A
NEC 210.11(C)(3) Bathroom branch circuits must be 20A

Required 20-amp circuits per NEC

  • Kitchen counter receptacles (≥2 branches per NEC 210.11(C)(1))
  • Bathroom receptacles (NEC 210.11(C)(3))
  • Laundry receptacle (NEC 210.11(C)(2))
  • Garage receptacles (NEC 210.52(G))

Optional 20-amp circuits

  • General receptacles in living areas (15A is acceptable; some installers use 20A everywhere)
  • Outdoor receptacles
  • Workshops, basements

Conduit fill for multi-circuit 20A homeruns

12 AWG THHN homerun configurations:

  • 2 circuits (6 conductors): 6 × 0.0133 = 0.0798 in² → 26.3% fill in 1/2" EMT ✓
  • 3 circuits (9 conductors): 9 × 0.0133 = 0.1197 in² → 39.4% fill in 1/2" EMT ✓ (at limit)
  • 4 circuits (12 conductors): 12 × 0.0133 = 0.1596 in² → 52.5% in 1/2" EMT ✗ → 3/4" EMT instead

Ampacity derating

With 4–6 current-carrying conductors in a raceway, NEC 310.15(C)(1) applies 80% derate. 12 AWG THHN: 30A × 0.80 = 24A. Still ≥ 20A breaker rating — compliant.

Push to 7–9 CCCs (70% derate): 30 × 0.70 = 21A. Marginal — verify against terminal temperature rating.

Voltage drop

12 AWG copper resistance: 1.588 Ω/1000 ft. At 20A on a 100 ft one-way run:

V drop = 2 × 100 × 20 × (1.588 / 1000) = 6.35V (5.3% of 120V)

Over the 3% recommendation. For runs >50 ft at 20A on 12 AWG, upsize to 10 AWG.

Quick reference

  • Wire: 12 AWG copper THHN/THWN-2 (or 10 AWG aluminum, rare for branches)
  • Breaker: 20A
  • Receptacle: 20A T-slot (required for 20A circuits per NEC 406)
  • Conduit minimum: 1/2" EMT for up to 3 branches

Use the conduit fill calculator for mixed-gauge runs.

FIG. 99

FAQ

12 AWG copper is the NEC-mandated minimum for 20-amp branch circuits per NEC 240.4(D). 12 AWG THHN is rated 30A at 90°C, 25A at 75°C — well within the 20A breaker rating.

METHODOLOGY & SOURCES

This page's figures are transcribed from NEC 2023 (NFPA 70) Chapter 9, Tables 1, 4 and 5, and checked by a version-controlled automated test suite — they are not signed off by a licensed professional. WireFillChart is an independent reference, not affiliated with or endorsed by NFPA. Always verify against the code edition adopted by your local authority having jurisdiction (AHJ).

WireFillChart Editorial Team·EDITORIAL·