What Gauge Wire for a 20-Amp Circuit?
Use 12 AWG copper for 20-amp branch circuits per NEC 240.4(D). 12 AWG THHN handles 25A at 75°C terminals, more than enough for 20A protection.
12 AWG copper is the standard wire gauge for 20-amp branch circuits, per NEC 240.4(D)(3). 12 AWG THHN has a 90°C ampacity of 30A but is limited to 20A by the NEC small-conductor protection rule.
NEC reference
| Rule | Effect |
|---|---|
| NEC 240.4(D)(5) | 12 AWG copper limited to 20A overcurrent protection |
| NEC Table 310.16 | 12 AWG @ 90°C = 30A; @ 75°C = 25A; @ 60°C terminals = 20A |
| NEC 210.11(C)(1) | Kitchen small-appliance branch circuits must be 20A |
| NEC 210.11(C)(3) | Bathroom branch circuits must be 20A |
Required 20-amp circuits per NEC
- Kitchen counter receptacles (≥2 branches per NEC 210.11(C)(1))
- Bathroom receptacles (NEC 210.11(C)(3))
- Laundry receptacle (NEC 210.11(C)(2))
- Garage receptacles (NEC 210.52(G))
Optional 20-amp circuits
- General receptacles in living areas (15A is acceptable; some installers use 20A everywhere)
- Outdoor receptacles
- Workshops, basements
Conduit fill for multi-circuit 20A homeruns
12 AWG THHN homerun configurations:
- 2 circuits (6 conductors): 6 × 0.0133 = 0.0798 in² → 26.3% fill in 1/2" EMT ✓
- 3 circuits (9 conductors): 9 × 0.0133 = 0.1197 in² → 39.4% fill in 1/2" EMT ✓ (at limit)
- 4 circuits (12 conductors): 12 × 0.0133 = 0.1596 in² → 52.5% in 1/2" EMT ✗ → 3/4" EMT instead
Ampacity derating
With 4–6 current-carrying conductors in a raceway, NEC 310.15(C)(1) applies 80% derate. 12 AWG THHN: 30A × 0.80 = 24A. Still ≥ 20A breaker rating — compliant.
Push to 7–9 CCCs (70% derate): 30 × 0.70 = 21A. Marginal — verify against terminal temperature rating.
Voltage drop
12 AWG copper resistance: 1.588 Ω/1000 ft. At 20A on a 100 ft one-way run:
V drop = 2 × 100 × 20 × (1.588 / 1000) = 6.35V (5.3% of 120V)
Over the 3% recommendation. For runs >50 ft at 20A on 12 AWG, upsize to 10 AWG.
Quick reference
- Wire: 12 AWG copper THHN/THWN-2 (or 10 AWG aluminum, rare for branches)
- Breaker: 20A
- Receptacle: 20A T-slot (required for 20A circuits per NEC 406)
- Conduit minimum: 1/2" EMT for up to 3 branches
Use the conduit fill calculator for mixed-gauge runs.