How Many #8 THHN Fit in 1" PVC-40?
Maximum #8 THHN conductor count for 1" PVC-40 at the NEC 2023 40% fill cap (3 or more conductors).
In a 1" PVC-40, the NEC 2023 ceiling is 9 #8 THHN conductors. The code permits 40% of the conduit's 0.8320 in² interior to be filled when three or more conductors share the raceway (NEC Chapter 9, Table 1), which leaves 0.3328 in² of usable area; each #8 THHN takes 0.0366 in², so 0.3328 ÷ 0.0366 rounds down to 9. This is a fill limit, not an ampacity rating: every current-carrying conductor counts toward the total — including a neutral that carries current — and once more than three current-carrying conductors share the conduit you must also apply the ampacity adjustment factors in NEC 310.15(C)(1). THHN, THWN-2 and XHHW-2 share the same Table 5 cross-section, so the count is identical; RHH and RHW-2 are larger and fit fewer. On long or multi-bend pulls, plan pulling tension and lubricant even when the fill math says the conductors fit.
THE MATH IN ONE PASS
STEP UP OR STEP DOWN A SIZE
| Trade size | Area (in²) | 40% allowed (in²) | Max #8 THHN |
|---|---|---|---|
| 3/4" PVC-40 (smaller) | 0.5080 | 0.2032 | 5 |
| 1" PVC-40 ← | 0.8320 | 0.3328 | 9 |
| 1-1/4" PVC-40 (larger) | 1.4530 | 0.5812 | 16 |
All values per NEC 2023 · Chapter 9 · Tables 1, 4 and 5. THHN/THWN-2/XHHW share identical conductor area.
AT THE LIMIT
Why 9 is the ceiling — the 1" PVC-40 passes at 9 and fails at 10.
9 conductors = 39.6% fill (within the 40% cap); 10 would be 44.0% — over the limit.
TRY IT — CHANGE THE COUNT
Preloaded with this combination. Add conductors, switch insulation, or check a different trade size.
- CONDUCTORS
- 9
- WIRE AREA
- 0.329in²
- CONDUIT AREA
- 0.832in²
- JAM RISK
- LOW
- Three or more conductors — NEC allows 40% fill.