How Many #6 THHN Fit in 1" PVC-40?

Maximum #6 THHN conductor count for 1" PVC-40 at the NEC 2023 40% fill cap (3 or more conductors).

In a 1" PVC-40, the NEC 2023 ceiling is 6 #6 THHN conductors. The code permits 40% of the conduit's 0.8320 in² interior to be filled when three or more conductors share the raceway (NEC Chapter 9, Table 1), which leaves 0.3328 in² of usable area; each #6 THHN takes 0.0507 in², so 0.3328 ÷ 0.0507 rounds down to 6. This is a fill limit, not an ampacity rating: every current-carrying conductor counts toward the total — including a neutral that carries current — and once more than three current-carrying conductors share the conduit you must also apply the ampacity adjustment factors in NEC 310.15(C)(1). THHN, THWN-2 and XHHW-2 share the same Table 5 cross-section, so the count is identical; RHH and RHW-2 are larger and fit fewer. On long or multi-bend pulls, plan pulling tension and lubricant even when the fill math says the conductors fit.

FIG. 02

THE MATH IN ONE PASS

CONDUIT
1" PVC-40 (Article 352)
A = 0.8320 in²
NEC Ch.9 Table 4 — 100% interior area
40% allowable = 0.3328 in²
CONDUCTOR
#6 THHN
A₁ = 0.0507 in²
NEC Ch.9 Table 5 — single-conductor cross-section
0.3328 ÷ 0.0507 = 6 max
FIG. 03

STEP UP OR STEP DOWN A SIZE

Trade sizeArea (in²)40% allowed (in²)Max #6 THHN
3/4" PVC-40 (smaller)0.50800.20324
1" PVC-400.83200.33286
1-1/4" PVC-40 (larger)1.45300.581211

All values per NEC 2023 · Chapter 9 · Tables 1, 4 and 5. THHN/THWN-2/XHHW share identical conductor area.

FIG. 04

AT THE LIMIT

Why 6 is the ceiling — the 1" PVC-40 passes at 6 and fails at 7.

5 × #6 THHN
30.5%
WITHIN 40%
5 × 0.0507 = 0.2535 in²
6 × #6 THHN
36.6%
MAX — WITHIN 40%
6 × 0.0507 = 0.3042 in²
7 × #6 THHN
42.7%
OVER 40% — FAILS
7 × 0.0507 = 0.3549 in²

6 conductors = 36.6% fill (within the 40% cap); 7 would be 42.7% — over the limit.

FIG. 05

TRY IT — CHANGE THE COUNT

Preloaded with this combination. Add conductors, switch insulation, or check a different trade size.

NEC 2023 · CH.9
A · CONDUIT TYPE
B · TRADE SIZE
DESCRIPTION
PVC Schedule 40
C · CONDUCTORS
01
RESULT · FILL %
APPROACHING LIMIT
36.6%
OF 40%
ALLOWED
0254075100
CONDUCTORS
6
WIRE AREA
0.304in²
CONDUIT AREA
0.832in²
JAM RISK
LOW
  • Three or more conductors — NEC allows 40% fill.