How Many #10 THHN Fit in 1" PVC-40?

Maximum #10 THHN conductor count for 1" PVC-40 at the NEC 2023 40% fill cap (3 or more conductors).

In a 1" PVC-40, the NEC 2023 ceiling is 15 #10 THHN conductors. The code permits 40% of the conduit's 0.8320 in² interior to be filled when three or more conductors share the raceway (NEC Chapter 9, Table 1), which leaves 0.3328 in² of usable area; each #10 THHN takes 0.0211 in², so 0.3328 ÷ 0.0211 rounds down to 15. This is a fill limit, not an ampacity rating: every current-carrying conductor counts toward the total — including a neutral that carries current — and once more than three current-carrying conductors share the conduit you must also apply the ampacity adjustment factors in NEC 310.15(C)(1). THHN, THWN-2 and XHHW-2 share the same Table 5 cross-section, so the count is identical; RHH and RHW-2 are larger and fit fewer. On long or multi-bend pulls, plan pulling tension and lubricant even when the fill math says the conductors fit.

FIG. 02

THE MATH IN ONE PASS

CONDUIT
1" PVC-40 (Article 352)
A = 0.8320 in²
NEC Ch.9 Table 4 — 100% interior area
40% allowable = 0.3328 in²
CONDUCTOR
#10 THHN
A₁ = 0.0211 in²
NEC Ch.9 Table 5 — single-conductor cross-section
0.3328 ÷ 0.0211 = 15 max
FIG. 03

STEP UP OR STEP DOWN A SIZE

Trade sizeArea (in²)40% allowed (in²)Max #10 THHN
3/4" PVC-40 (smaller)0.50800.20329
1" PVC-400.83200.332815
1-1/4" PVC-40 (larger)1.45300.581227

All values per NEC 2023 · Chapter 9 · Tables 1, 4 and 5. THHN/THWN-2/XHHW share identical conductor area.

FIG. 04

FREQUENTLY ASKED QUESTIONS

15 conductors, applying the NEC 2023 40% fill rule for 3+ conductors. The conduit's interior area is 0.8320 in² and the allowable conductor area is 0.3328 in² (NEC Ch.9 Table 4, Article 352).