How Many #8 THHN Fit in 3/4" PVC-40?

Maximum #8 THHN conductor count for 3/4" PVC-40 at the NEC 2023 40% fill cap (3 or more conductors).

In a 3/4" PVC-40, the NEC 2023 ceiling is 5 #8 THHN conductors. The code permits 40% of the conduit's 0.5080 in² interior to be filled when three or more conductors share the raceway (NEC Chapter 9, Table 1), which leaves 0.2032 in² of usable area; each #8 THHN takes 0.0366 in², so 0.2032 ÷ 0.0366 rounds down to 5. This is a fill limit, not an ampacity rating: every current-carrying conductor counts toward the total — including a neutral that carries current — and once more than three current-carrying conductors share the conduit you must also apply the ampacity adjustment factors in NEC 310.15(C)(1). THHN, THWN-2 and XHHW-2 share the same Table 5 cross-section, so the count is identical; RHH and RHW-2 are larger and fit fewer. On long or multi-bend pulls, plan pulling tension and lubricant even when the fill math says the conductors fit.

FIG. 02

THE MATH IN ONE PASS

CONDUIT
3/4" PVC-40 (Article 352)
A = 0.5080 in²
NEC Ch.9 Table 4 — 100% interior area
40% allowable = 0.2032 in²
CONDUCTOR
#8 THHN
A₁ = 0.0366 in²
NEC Ch.9 Table 5 — single-conductor cross-section
0.2032 ÷ 0.0366 = 5 max
FIG. 03

STEP UP OR STEP DOWN A SIZE

Trade sizeArea (in²)40% allowed (in²)Max #8 THHN
1/2" PVC-40 (smaller)0.28500.11403
3/4" PVC-400.50800.20325
1" PVC-40 (larger)0.83200.33289

All values per NEC 2023 · Chapter 9 · Tables 1, 4 and 5. THHN/THWN-2/XHHW share identical conductor area.

FIG. 04

AT THE LIMIT

Why 5 is the ceiling — the 3/4" PVC-40 passes at 5 and fails at 6.

4 × #8 THHN
28.8%
WITHIN 40%
4 × 0.0366 = 0.1464 in²
5 × #8 THHN
36.0%
MAX — WITHIN 40%
5 × 0.0366 = 0.1830 in²
6 × #8 THHN
43.2%
OVER 40% — FAILS
6 × 0.0366 = 0.2196 in²

5 conductors = 36.0% fill (within the 40% cap); 6 would be 43.2% — over the limit.

FIG. 05

TRY IT — CHANGE THE COUNT

Preloaded with this combination. Add conductors, switch insulation, or check a different trade size.

NEC 2023 · CH.9
A · CONDUIT TYPE
B · TRADE SIZE
DESCRIPTION
PVC Schedule 40
C · CONDUCTORS
01
RESULT · FILL %
APPROACHING LIMIT
36.0%
OF 40%
ALLOWED
0254075100
CONDUCTORS
5
WIRE AREA
0.183in²
CONDUIT AREA
0.508in²
JAM RISK
LOW
  • Three or more conductors — NEC allows 40% fill.
CONDUIT
PVC40 · 3/4"
CONDUCTOR
8 AWG · THHN
FIG. 06

FREQUENTLY ASKED QUESTIONS

5 conductors, applying the NEC 2023 40% fill rule for 3+ conductors. The conduit's interior area is 0.5080 in² and the allowable conductor area is 0.2032 in² (NEC Ch.9 Table 4, Article 352).