How Many #12 THHN Fit in 3/4" PVC-40?

Maximum #12 THHN conductor count for 3/4" PVC-40 at the NEC 2023 40% fill cap (3 or more conductors).

In a 3/4" PVC-40, the NEC 2023 ceiling is 15 #12 THHN conductors. The code permits 40% of the conduit's 0.5080 in² interior to be filled when three or more conductors share the raceway (NEC Chapter 9, Table 1), which leaves 0.2032 in² of usable area; each #12 THHN takes 0.0133 in², so 0.2032 ÷ 0.0133 rounds down to 15. This is a fill limit, not an ampacity rating: every current-carrying conductor counts toward the total — including a neutral that carries current — and once more than three current-carrying conductors share the conduit you must also apply the ampacity adjustment factors in NEC 310.15(C)(1). THHN, THWN-2 and XHHW-2 share the same Table 5 cross-section, so the count is identical; RHH and RHW-2 are larger and fit fewer. On long or multi-bend pulls, plan pulling tension and lubricant even when the fill math says the conductors fit.

FIG. 02

THE MATH IN ONE PASS

CONDUIT
3/4" PVC-40 (Article 352)
A = 0.5080 in²
NEC Ch.9 Table 4 — 100% interior area
40% allowable = 0.2032 in²
CONDUCTOR
#12 THHN
A₁ = 0.0133 in²
NEC Ch.9 Table 5 — single-conductor cross-section
0.2032 ÷ 0.0133 = 15 max
FIG. 03

STEP UP OR STEP DOWN A SIZE

Trade sizeArea (in²)40% allowed (in²)Max #12 THHN
1/2" PVC-40 (smaller)0.28500.11408
3/4" PVC-400.50800.203215
1" PVC-40 (larger)0.83200.332825

All values per NEC 2023 · Chapter 9 · Tables 1, 4 and 5. THHN/THWN-2/XHHW share identical conductor area.

FIG. 04

FREQUENTLY ASKED QUESTIONS

15 conductors, applying the NEC 2023 40% fill rule for 3+ conductors. The conduit's interior area is 0.5080 in² and the allowable conductor area is 0.2032 in² (NEC Ch.9 Table 4, Article 352).