How Many 2 AWG THHN Fit in 1-1/4-Inch EMT?
5 conductors of 2 AWG THHN fit in 1-1/4-inch EMT at the NEC fill limit — 38.7% of the conduit's 1.496 in² interior.
5 conductors of 2 AWG THHN fit in a 1-1/4-inch EMT at the NEC fill limit. Maximum fill is 38.7%, under the 40% allowed for three or more conductors per NEC Chapter 9, Table 1.
The math
| Variable | Value | Source |
|---|---|---|
| 2 AWG THHN area | 0.1158 in² | NEC Table 5 |
| 1-1/4" EMT interior | 1.496 in² | NEC Table 4 |
| 40% allowance | 0.5984 in² | NEC Table 1 |
| Max conductors | floor(0.5984 / 0.1158) = 5 | calc |
Practical configurations
- 100A residential service feeder: 2 hots + 1 neutral = 3 conductors → 23.2% fill ✓
- Two parallel 4/0 phases for 200A: Not applicable — 4/0 needs larger conduit
- Sub-panel feeder with 2 hots + 1 neutral + 1 EGC + 1 isolated ground: 5 conductors → at the limit ✓
Next size up
- 1-1/2 EMT fits 7 of 2 AWG THHN at 39.8% fill
- 2-inch EMT fits 11 at 37.9% fill
Ampacity
2 AWG copper THHN: 130A at 90°C, 115A at 75°C, 95A at 60°C terminals. Standard breaker sizes: 100A, 110A, 125A. With 4 CCCs derate by 0.80: 130 × 0.80 = 104A — sufficient for 100A.
For aluminum 2 AWG: 100A at 75°C — the typical sub-feeder. Aluminum area in Table 5 is the same as copper (insulation determines area, not metal). See copper vs aluminum conductor.
FAQ
RELATED TOOLS
This page's figures are transcribed from NEC 2023 (NFPA 70) Chapter 9, Tables 1, 4 and 5, and checked by a version-controlled automated test suite — they are not signed off by a licensed professional. WireFillChart is an independent reference, not affiliated with or endorsed by NFPA. Always verify against the code edition adopted by your local authority having jurisdiction (AHJ).