How Many 2 AWG THHN Fit in 1-1/4-Inch EMT?

5 conductors of 2 AWG THHN fit in 1-1/4-inch EMT at the NEC fill limit — 38.7% of the conduit's 1.496 in² interior.

·1 MIN READ·EDITORIAL

5 conductors of 2 AWG THHN fit in a 1-1/4-inch EMT at the NEC fill limit. Maximum fill is 38.7%, under the 40% allowed for three or more conductors per NEC Chapter 9, Table 1.

The math

Variable Value Source
2 AWG THHN area 0.1158 in² NEC Table 5
1-1/4" EMT interior 1.496 in² NEC Table 4
40% allowance 0.5984 in² NEC Table 1
Max conductors floor(0.5984 / 0.1158) = 5 calc

Practical configurations

  • 100A residential service feeder: 2 hots + 1 neutral = 3 conductors → 23.2% fill ✓
  • Two parallel 4/0 phases for 200A: Not applicable — 4/0 needs larger conduit
  • Sub-panel feeder with 2 hots + 1 neutral + 1 EGC + 1 isolated ground: 5 conductors → at the limit ✓

Next size up

  • 1-1/2 EMT fits 7 of 2 AWG THHN at 39.8% fill
  • 2-inch EMT fits 11 at 37.9% fill

Ampacity

2 AWG copper THHN: 130A at 90°C, 115A at 75°C, 95A at 60°C terminals. Standard breaker sizes: 100A, 110A, 125A. With 4 CCCs derate by 0.80: 130 × 0.80 = 104A — sufficient for 100A.

For aluminum 2 AWG: 100A at 75°C — the typical sub-feeder. Aluminum area in Table 5 is the same as copper (insulation determines area, not metal). See copper vs aluminum conductor.

FIG. 99

FAQ

5 conductors of 2 AWG THHN fit in 1-1/4-inch EMT at the NEC 40% fill limit. Calculation: 5 × 0.1158 in² = 0.579 in², or 38.7% of EMT's 1.496 in² interior.