WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · ARTICLE

Copper vs Aluminum Conductor — Ampacity, Cost, Code

Aluminum is ~30% cheaper than copper but requires one trade size up to match ampacity.

·3 MIN READ·EDITORIAL

Copper has higher conductivity, smaller cross-section per amp, and broader terminal compatibility. Aluminum is significantly cheaper (per pound and per foot at equal amp rating) but requires careful termination and larger conductors.

NEC ampacity comparison

From Table 310.16 (75°C terminations):

Amp rating Copper Aluminum (AA-8000)
30A 10 AWG 8 AWG
40A 8 AWG 6 AWG
50A 6 AWG 4 AWG
60A 6 AWG 4 AWG
100A 3 AWG 1 AWG
125A 2 AWG 1/0
150A 1 AWG 2/0
175A 1/0 3/0
200A 2/0 4/0

Aluminum requires one to two trade sizes larger than copper for the same ampacity.

NEC 310.12 dwelling reduction

For one-family and two-family dwellings, NEC 310.12 permits smaller conductors for the main service-entrance and main feeder only:

Service rating Standard copper Dwelling copper Standard aluminum Dwelling aluminum
100A 3 AWG 4 AWG 1 AWG 2 AWG
200A 3/0 2/0 250 kcmil 4/0
400A 600 kcmil 400 kcmil 1000 kcmil 600 kcmil

This is the "83% rule" and applies only at the main service point — not downstream sub-panels.

Conduit fill

NEC Table 5 conductor areas are the same for copper and aluminum at the same gauge and insulation. Switching from copper to aluminum doesn't change the fill chart count at the same gauge — but you'll use a larger gauge for aluminum, which DOES change the fill.

Example: 100A service in 1-inch EMT:

Material Gauge Area × 3 conductors Fill %
Copper (4 AWG dwelling) 4 AWG 3 × 0.0824 = 0.247 in² 28.6%
Aluminum (2 AWG dwelling) 2 AWG 3 × 0.1158 = 0.347 in² 40.2% — fails by 0.2%

The aluminum option pushes you over the 40% limit in 1-inch EMT — you'd need 1-1/4 inch.

Termination requirements (NEC 110.14)

  • Copper-only devices: Most modern residential receptacles, switches, and breakers
  • CO/ALR (copper-aluminum revised) devices: Permitted with aluminum 15A/20A branch wire — increasingly rare in new construction
  • Listed for aluminum (CU-AL): Required for aluminum lugs in panels, transformers, and large connectors
  • Anti-oxidant compound: Required on aluminum service-entrance and feeder terminations (NEC 110.14(A) Note)

Cost rough comparison

At 2026 prices (US retail, varies by region):

Gauge Copper THHN $/ft Aluminum THHN $/ft
12 AWG $0.40 n/a (rarely sold in branch sizes)
6 AWG $1.50 $0.65
4 AWG $2.40 $1.10
1/0 $5.50 $2.40
4/0 $11.00 $4.80

Aluminum ~50–60% of copper price at equivalent gauge. After upsizing one trade size for ampacity equivalence, aluminum still saves 20–35%.

Quick reference

  • Branches (15A / 20A): Copper. Aluminum branch wiring is effectively obsolete.
  • Service entrance (100A, 200A, 400A): Aluminum is cost-effective, common in residential.
  • Sub-panel feeders: Aluminum frequently used; verify breaker and lug listings.
  • Long underground runs: Aluminum's weight savings matters; one trade size up offsets the cost difference.
  • Fill chart for either: Same Table 5 area per gauge. Pick the right gauge for the right metal.
FIG. 99

FAQ

Yes when properly sized and terminated. The 1960s-70s aluminum branch-circuit failures were due to terminal incompatibility with the alloy of that era. Modern AA-8000 alloy aluminum, properly terminated with CO/ALR or aluminum-listed devices, is safe and widely used in feeders and services.