WIRE·FILL·CHARTNEC 2023 · CH. 9
FIG. 01 — DIRECT ANSWER

How Many #10 THHN Fit in 1-1/4" EMT?

Maximum #10 THHN conductor count for 1-1/4" EMT at the NEC 2023 40% fill cap (3 or more conductors).

FIG. 02

THE MATH IN ONE PASS

CONDUIT
1-1/4" EMT (Article 358)
A = 1.4960 in²
NEC Ch.9 Table 4 — 100% interior area
40% allowable = 0.5984 in²
CONDUCTOR
#10 THHN
A₁ = 0.0211 in²
NEC Ch.9 Table 5 — single-conductor cross-section
0.5984 ÷ 0.0211 = 28 max
FIG. 03

STEP UP OR STEP DOWN A SIZE

Trade sizeArea (in²)40% allowed (in²)Max #10 THHN
1" EMT (smaller)0.86400.345616
1-1/4" EMT1.49600.598428
1-1/2" EMT (larger)2.03600.814438

All values per NEC 2023 · Chapter 9 · Tables 1, 4 and 5. THHN/THWN-2/XHHW share identical conductor area.

FIG. 04

FREQUENTLY ASKED QUESTIONS

28 conductors, applying the NEC 2023 40% fill rule for 3+ conductors. The conduit's interior area is 1.4960 in² and the allowable conductor area is 0.5984 in² (NEC Ch.9 Table 4, Article 358).