What Size Conduit for a 400-Amp Service?

For 400A residential or light commercial service, typical conduit is 3-inch EMT/IMC/RMC with 600 kcmil copper or 4/0 parallel runs.

·2 MIN READ·EDITORIAL

For a 400-amp service entrance, conduit sizing depends on whether you use single 600 kcmil conductors or parallel 4/0 sets:

Conductor configuration Cu vs Al Conduit per raceway
Single 600 kcmil per phase + neutral Copper 3-inch EMT/IMC/RMC
Single 600 kcmil per phase + neutral Aluminum 3-1/2 inch
2 × parallel 4/0 sets per phase + neutral Copper 3-inch (single raceway with 6 conductors)
2 × parallel 250 kcmil sets per phase + neutral Aluminum 3-inch+

Single 600 kcmil copper THHN for 400A (NEC 310.16)

Variable Value
600 kcmil THHN area 0.8676 in²
3 conductors (no EGC in service entrance) 2.603 in²
40% fill required interior 6.508 in²
3" EMT (8.846 in²) 29.4% fill ✓

Parallel 4/0 copper for 400A (NEC 310.10(H))

Two parallel sets per phase. Each set must be:

  • Identical length, gauge, insulation, terminations
  • ≥ 1/0 minimum gauge

6 phase conductors + 2 parallel neutrals = 8 conductors of 4/0 in the raceway. 8 × 0.3237 = 2.590 in² → 29.3% fill in 3" EMT. Fits.

Aluminum 400A (NEC 310.16, 600 kcmil Al)

600 kcmil aluminum at 75°C = 380A — insufficient for 400A. Step to 700 kcmil aluminum at 75°C = 400A.

700 kcmil aluminum is unusual stocking; many installs use 2 parallel sets of 250 kcmil aluminum instead: 2 × 215A at 75°C = 430A.

Two sets of 250 kcmil aluminum × 3 phases = 6 conductors. 6 × 0.4596 (250 kcmil aluminum THHN) = 2.758 in² → 31.2% fill in 3" EMT.

Underground service lateral

For 400A laterals, the typical setup:

  • 3-1/2 inch PVC Sch 80 above grade for the riser (where exposed to physical damage)
  • 3-inch PVC Sch 40 below grade in trench

If using 600 kcmil aluminum in Sch 80 risers, jump to 4-inch Sch 80 to clear the 40% margin (600 kcmil Al × 3 = 1.379 in² × 3 = 4.137 in² > 40% of 6.442 in² = 2.577 in² — over).

Local AHJ considerations

400A is at the boundary of residential/light commercial. Many AHJs require:

  • Separate raceway per phase (parallel install) for ampacity adjustment relief
  • IMC or RMC for the riser (not EMT) for added physical protection
  • Bonding bushings at every metallic fitting

Quick reference

  • Standard service raceway: 3-inch EMT or IMC for 400A copper
  • Aluminum: 3-1/2 inch or 4-inch
  • Parallel 4/0 Cu: 3-inch EMT (single raceway, 6 conductors)
  • Underground: PVC Sch 80 above, Sch 40 below

For commercial 400A feeders with multiple sets, use the conduit fill calculator.

FIG. 99

FAQ

3-inch EMT or RMC for a 400A service entrance using 600 kcmil copper THHN, or 2 parallel sets of 4/0 copper (per NEC 310.10(H) parallel rules). 3-1/2 inch for 600 kcmil aluminum.