WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · ARTICLE

What Gauge Wire for a 40-Amp Circuit?

Use 8 AWG copper for 40-amp circuits. 8 AWG THHN: 55A at 90°C, 50A at 75°C, 40A at 60°C — adequate margin for the 40A breaker.

·2 MIN READ·EDITORIAL

8 AWG copper is the standard wire gauge for 40-amp circuits. 8 AWG THHN delivers 55A at 90°C, dropping to 50A at 75°C terminals and exactly 40A at 60°C terminals — meets the 40A breaker requirement at all common termination ratings.

NEC reference

Rule Effect
NEC Table 310.16 8 AWG copper @ 90°C = 55A; @ 75°C = 50A; @ 60°C = 40A
NEC 110.14(C)(1)(a) 100A or smaller circuits use 60°C column at most terminations
NEC 240.4 No small-conductor rule above 10 AWG — protection follows ampacity

Common 40-amp circuits

  • Electric range (50A more common, but smaller ranges use 40A)
  • Tankless electric water heater (smaller units)
  • Level 2 EV charger at 32A continuous (40A breaker per NEC 625.42)
  • Heat pump outdoor unit (varies by model)
  • Pool pump motor larger sizes

Conductor count + conduit

Circuit Conductors Min EMT
40A 240V (range without neutral): 2 hots + EGC 3 1/2" (16.5% fill)
40A 240V with neutral: 2 hots + 1 N + 1 EGC 4 1/2" (22% fill)
Two 40A circuits sharing EGC 5 3/4" (34.3% fill — at limit per 8 AWG / 3/4 calc)

Ampacity derating

With 4–6 CCCs: 55A × 0.80 = 44A — above 40A breaker, OK. With 7–9 CCCs: 55A × 0.70 = 38.5Abelow 40A breaker. Either reduce CCCs or upsize to 6 AWG (75A × 0.70 = 52.5A).

Voltage drop at 40A

8 AWG copper: 0.628 Ω/1000 ft. At 40A on 100 ft one-way (240V):

V drop = 200 × 40 × (0.628 / 1000) = 5.0V (2.1% of 240V)

Within 3% — 8 AWG is fine to ~140 ft for 40A circuits.

Quick reference

  • Wire: 8 AWG copper THHN/THWN-2 (or 6 AWG aluminum)
  • Breaker: 40A 2-pole
  • Receptacle: NEMA 14-50 / 6-50 (often used for 50A — for 40A, no dedicated receptacle, hardwired)
  • Conduit: 1/2" EMT fits one circuit comfortably
FIG. 99

FAQ

8 AWG copper is the standard for 40A circuits. 8 AWG THHN is rated 55A at 90°C, 50A at 75°C — both well above the 40A breaker rating. At 60°C terminals, 8 AWG is exactly 40A — meets the minimum.