Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · ARTICLE

What Gauge Wire for a 40-Amp Circuit?

Use 8 AWG copper for 40-amp circuits. 8 AWG THHN: 55A at 90°C, 50A at 75°C, 40A at 60°C — adequate margin for the 40A breaker.

·2 MIN READ·EDITORIAL

8 AWG copper is the standard wire gauge for 40-amp circuits. 8 AWG THHN delivers 55A at 90°C, dropping to 50A at 75°C terminals and exactly 40A at 60°C terminals — meets the 40A breaker requirement at all common termination ratings.

NEC reference

Rule Effect
NEC Table 310.16 8 AWG copper @ 90°C = 55A; @ 75°C = 50A; @ 60°C = 40A
NEC 110.14(C)(1)(a) 100A or smaller circuits use 60°C column at most terminations
NEC 240.4 No small-conductor rule above 10 AWG — protection follows ampacity

Common 40-amp circuits

  • Electric range (50A more common, but smaller ranges use 40A)
  • Tankless electric water heater (smaller units)
  • Level 2 EV charger at 32A continuous (40A breaker per NEC 625.42)
  • Heat pump outdoor unit (varies by model)
  • Pool pump motor larger sizes

Conductor count + conduit

Circuit Conductors Min EMT
40A 240V (range without neutral): 2 hots + EGC 3 1/2" (16.5% fill)
40A 240V with neutral: 2 hots + 1 N + 1 EGC 4 1/2" (22% fill)
Two 40A circuits sharing EGC 5 3/4" (34.3% fill — at limit per 8 AWG / 3/4 calc)

Ampacity derating

With 4–6 CCCs: 55A × 0.80 = 44A — above 40A breaker, OK. With 7–9 CCCs: 55A × 0.70 = 38.5Abelow 40A breaker. Either reduce CCCs or upsize to 6 AWG (75A × 0.70 = 52.5A).

Voltage drop at 40A

8 AWG copper: 0.628 Ω/1000 ft. At 40A on 100 ft one-way (240V):

V drop = 200 × 40 × (0.628 / 1000) = 5.0V (2.1% of 240V)

Within 3% — 8 AWG is fine to ~140 ft for 40A circuits.

Quick reference

  • Wire: 8 AWG copper THHN/THWN-2 (or 6 AWG aluminum)
  • Breaker: 40A 2-pole
  • Receptacle: NEMA 14-50 / 6-50 (often used for 50A — for 40A, no dedicated receptacle, hardwired)
  • Conduit: 1/2" EMT fits one circuit comfortably
FIG. 99

FAQ

8 AWG copper is the standard for 40A circuits. 8 AWG THHN is rated 55A at 90°C, 50A at 75°C — both well above the 40A breaker rating. At 60°C terminals, 8 AWG is exactly 40A — meets the minimum.

METHODOLOGY & SOURCES

This page's figures are transcribed from NEC 2023 (NFPA 70) Chapter 9, Tables 1, 4 and 5, and checked by a version-controlled automated test suite — they are not signed off by a licensed professional. WireFillChart is an independent reference, not affiliated with or endorsed by NFPA. Always verify against the code edition adopted by your local authority having jurisdiction (AHJ).

WireFillChart Editorial Team·EDITORIAL·