What Gauge Wire for a 200-Amp Service?
Use 2/0 AWG copper or 4/0 AWG aluminum for 200-amp residential service entrance per NEC 310.12 dwelling exception.
For a 200-amp residential service entrance, per NEC 310.12:
- 2/0 AWG copper (175A at 75°C from Table 310.16, allowed for 200A under §310.12 dwelling exception)
- 4/0 AWG aluminum (180A at 75°C, allowed for 200A under §310.12)
For a non-dwelling 200A feeder or downstream sub-panel, use NEC 310.16 directly:
- 3/0 AWG copper (200A at 75°C)
- 250 kcmil aluminum (205A at 75°C)
NEC 310.12 dwelling reduction at 200A
| Standard (310.16, 75°C) | Dwelling (310.12) | Savings |
|---|---|---|
| 3/0 copper | 2/0 copper | 1 trade size smaller |
| 250 kcmil aluminum | 4/0 aluminum | 1 trade size smaller |
The 83% rule applied to 200A = 166A minimum conductor capacity. 2/0 copper at 175A and 4/0 aluminum at 180A both clear that threshold.
Service entrance configuration
A typical 200A residential service includes:
- 2 × 2/0 copper (or 4/0 aluminum) — line 1 and line 2 (hots)
- 1 × 2/0 copper (or 4/0 aluminum) — neutral
- Grounding electrode conductor (GEC) sized separately per NEC 250.66 (4 AWG copper for 200A service)
Conduit fill
200A service entrance conductors in conduit:
| Material | Configuration | Conduit Area | Fill % | Min conduit |
|---|---|---|---|---|
| 2/0 copper THHN × 3 | 3 × 0.2223 = 0.667 in² | 1.668 in² needed @ 40% | 2-inch EMT (3.356 in²) at 19.9% | 2" EMT |
| 4/0 aluminum × 3 | 3 × 0.3237 = 0.971 in² | 2.428 in² needed @ 40% | 2-inch EMT at 28.9% | 2" EMT |
2-inch EMT fits both options easily. 1-1/2" EMT (2.036 in² interior) fits 2/0 copper at 32.8% but is too small for 4/0 aluminum at 47.7%.
Ampacity derating
If service entrance is run with more than 3 current-carrying conductors (rare for 200A residential service), apply NEC 310.15(C)(1):
- 4 CCCs: × 0.80 — 2/0 Cu drops to 140A (insufficient for 200A)
- For shared raceways carrying 200A circuits with other CCCs, upsize one step
Quick reference
- Standard wire: 2/0 copper or 4/0 aluminum (per NEC 310.12 dwelling)
- Standard wire (non-dwelling): 3/0 copper or 250 kcmil aluminum
- Breaker: 200A 2-pole main
- Neutral: Same size as ungrounded conductors (or reduced per NEC 220.61 in some cases)
- GEC: 4 AWG copper to ground rod / Ufer
- Conduit: 2-inch EMT typical for service entrance riser
For larger commercial 200A feeders, see the conduit fill calculator.
FAQ
RELATED TOOLS
This page's figures are transcribed from NEC 2023 (NFPA 70) Chapter 9, Tables 1, 4 and 5, and checked by a version-controlled automated test suite — they are not signed off by a licensed professional. WireFillChart is an independent reference, not affiliated with or endorsed by NFPA. Always verify against the code edition adopted by your local authority having jurisdiction (AHJ).