WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · USE CASE

Wire Fill for Detached Garage Sub-Feed

Detached garage feeder wire fill: 60A uses 6 AWG copper in 1-inch PVC, 100A uses 3 AWG in 1-1/4 inch. Separate GES required per NEC 250.32.

·4 MIN READ·EDITORIAL

Wire fill for detached garage sub-feeders is governed by NEC 215, 225, and 250.32. A typical 60A detached garage sub-feed uses 6 AWG copper THHN (4-wire: 2 hots, neutral, EGC) in 1-inch PVC conduit. A 100A sub-feed uses 3 AWG copper in 1-1/4 inch PVC. The garage requires its own grounding electrode system (driven rod or Ufer) per NEC 250.32(A). Voltage drop is the dominant sizing factor on long runs.

Load characteristics

A detached garage typically combines lighting, receptacles, and one or two larger loads:

Use case Calculated load Typical sub-panel
Lighting + few outlets 15-25A 30-60A
Workshop tools, shop vac, small welder 30-50A 60-100A
EV charging + workshop 50-80A 100-125A
Apartment / ADU above garage per NEC 220 100-200A

Most modern garages get 60A or 100A panels for headroom — even small shops accumulate loads (compressor, table saw, dust collector).

NEC code references

  • NEC 215 — feeder requirements
  • NEC 225 — outside branch circuits and feeders
  • NEC 225.30 — number of supplies to a building (generally one feeder per structure)
  • NEC 250.32 — grounding at separate buildings — 4-wire feeder + separate GES
  • NEC 300.5 — burial depths
  • NEC 210.8(A)(2) — GFCI required for garage receptacles
  • NEC 210.52(G) — at least one receptacle in attached and detached garages

Conductor sizing

Use 75°C NEC Table 310.16. Voltage drop on long runs may force you up one or two sizes:

Sub-panel rating Copper THHN/THWN-2 Aluminum XHHW-2
30A 10 AWG 8 AWG
60A 6 AWG 4 AWG
100A 3 AWG 1 AWG
125A 2 AWG 1/0

For runs over 75 ft, calculate voltage drop. Rule of thumb: bump up one gauge per 100 ft for 60A and larger feeders.

Sub-panel Run length Recommended copper
60A up to 75 ft 6 AWG
60A 75-150 ft 4 AWG
100A up to 75 ft 3 AWG
100A 75-150 ft 2 AWG
100A 150-250 ft 1 AWG

Conduit sizing

4-wire feeder (2 hots + neutral + EGC) in PVC Sch 40:

Sub-panel Conductors Total area 1" PVC 1-1/4" PVC
60A 3 × 6 + 1 × 10 EGC 0.1733 in² 20.8% 11.4%
100A 3 × 3 + 1 × 8 EGC 0.3009 in² over 40% — fails 19.7%
125A 3 × 2 + 1 × 6 EGC 0.3719 in² over 40% — fails 24.4%

For 60A use 1-inch PVC. For 100A and larger, 1-1/4 inch PVC minimum.

For aluminum:

Sub-panel Aluminum conductors 1-1/4" PVC 1-1/2" PVC
100A 3 × 1 AWG + 1 × 6 EGC 30.0% 19.5%
200A 3 × 4/0 + 1 × 4 EGC over 40% — fails over 40% — fails (use 2")

Special requirements

  • Separate grounding electrode system: NEC 250.32(A). Drive two 8-ft copper-clad rods 6 ft apart, bond with 6 AWG copper to sub-panel ground bar.
  • Neutral isolated from ground at sub-panel: NEC 250.142(B). Remove the bonding screw or strap.
  • GFCI: All 125V 15A/20A receptacles in the garage per NEC 210.8(A)(2).
  • Disconnect: The sub-panel main breaker (or six-throw rule if MLO) serves as the disconnect for the structure.
  • Wet location: Underground portion is a wet location — use THWN-2 or XHHW-2.
  • Conduit transitions: Use sweep 90s for underground PVC runs, not standard 90s, for easier pulling.

Worked example — 100A garage sub-panel, 120 ft from main house

  • Calculated load: 70A peak (workshop + EV charger)
  • Feeder OCPD: 100A 2-pole breaker in main house panel
  • Voltage drop check at 120 ft: 100A on 3 AWG copper = 4.4V drop (1.8% on 240V) — pass for 3% feeder limit, but tight. Go to 2 AWG for safety.
  • Conductors: 2 AWG copper THHN/THWN-2 × 3 (L1, L2, N) + 8 AWG copper EGC
  • Raceway: 1-1/4" PVC Sch 40, buried 18 inches, with Sch 80 risers above grade
  • Fill check: 3 × 0.1158 + 0.0366 = 0.3840 in² in 1-1/4" PVC Sch 40 = 25.1%, pass.
  • Grounding: Two 8-ft ground rods, 6 AWG copper to ground bar. Bonding screw removed from neutral bar.
  • GFCI: 20A 125V GFCI receptacles throughout garage.

Verify with the Conduit Fill Calculator.

Quick reference

Garage sub-panel Run length Copper feeder EGC PVC conduit
60A <75 ft 6 AWG × 3 10 AWG 1"
60A 75-150 ft 4 AWG × 3 10 AWG 1"
100A <75 ft 3 AWG × 3 8 AWG 1-1/4"
100A 75-150 ft 2 AWG × 3 8 AWG 1-1/4"
100A 150-250 ft 1 AWG × 3 8 AWG 1-1/2"

Related

FIG. 99

FAQ

Yes. NEC 250.32(A) requires a grounding electrode at every separate structure supplied by a feeder or branch circuit, unless it's a single branch circuit. Drive a ground rod (or two) and bond to the sub-panel's ground bar. The EGC from the main panel still runs in the feeder.