Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · USE CASE

Wire Fill for Detached Garage Sub-Feed

Detached garage feeder wire fill: 60A uses 6 AWG copper in 1-inch PVC, 100A uses 3 AWG in 1-1/4 inch. Separate GES required per NEC 250.32.

·4 MIN READ·EDITORIAL

Wire fill for detached garage sub-feeders is governed by NEC 215, 225, and 250.32. A typical 60A detached garage sub-feed uses 6 AWG copper THHN (4-wire: 2 hots, neutral, EGC) in 1-inch PVC conduit. A 100A sub-feed uses 3 AWG copper in 1-1/4 inch PVC. The garage requires its own grounding electrode system (driven rod or Ufer) per NEC 250.32(A). Voltage drop is the dominant sizing factor on long runs.

Load characteristics

A detached garage typically combines lighting, receptacles, and one or two larger loads:

Use case Calculated load Typical sub-panel
Lighting + few outlets 15-25A 30-60A
Workshop tools, shop vac, small welder 30-50A 60-100A
EV charging + workshop 50-80A 100-125A
Apartment / ADU above garage per NEC 220 100-200A

Most modern garages get 60A or 100A panels for headroom — even small shops accumulate loads (compressor, table saw, dust collector).

NEC code references

  • NEC 215 — feeder requirements
  • NEC 225 — outside branch circuits and feeders
  • NEC 225.30 — number of supplies to a building (generally one feeder per structure)
  • NEC 250.32 — grounding at separate buildings — 4-wire feeder + separate GES
  • NEC 300.5 — burial depths
  • NEC 210.8(A)(2) — GFCI required for garage receptacles
  • NEC 210.52(G) — at least one receptacle in attached and detached garages

Conductor sizing

Use 75°C NEC Table 310.16. Voltage drop on long runs may force you up one or two sizes:

Sub-panel rating Copper THHN/THWN-2 Aluminum XHHW-2
30A 10 AWG 8 AWG
60A 6 AWG 4 AWG
100A 3 AWG 1 AWG
125A 2 AWG 1/0

For runs over 75 ft, calculate voltage drop. Rule of thumb: bump up one gauge per 100 ft for 60A and larger feeders.

Sub-panel Run length Recommended copper
60A up to 75 ft 6 AWG
60A 75-150 ft 4 AWG
100A up to 75 ft 3 AWG
100A 75-150 ft 2 AWG
100A 150-250 ft 1 AWG

Conduit sizing

4-wire feeder (2 hots + neutral + EGC) in PVC Sch 40:

Sub-panel Conductors Total area 1" PVC 1-1/4" PVC
60A 3 × 6 + 1 × 10 EGC 0.1733 in² 20.8% 11.4%
100A 3 × 3 + 1 × 8 EGC 0.3009 in² over 40% — fails 19.7%
125A 3 × 2 + 1 × 6 EGC 0.3719 in² over 40% — fails 24.4%

For 60A use 1-inch PVC. For 100A and larger, 1-1/4 inch PVC minimum.

For aluminum:

Sub-panel Aluminum conductors 1-1/4" PVC 1-1/2" PVC
100A 3 × 1 AWG + 1 × 6 EGC 30.0% 19.5%
200A 3 × 4/0 + 1 × 4 EGC over 40% — fails over 40% — fails (use 2")

Special requirements

  • Separate grounding electrode system: NEC 250.32(A). Drive two 8-ft copper-clad rods 6 ft apart, bond with 6 AWG copper to sub-panel ground bar.
  • Neutral isolated from ground at sub-panel: NEC 250.142(B). Remove the bonding screw or strap.
  • GFCI: All 125V 15A/20A receptacles in the garage per NEC 210.8(A)(2).
  • Disconnect: The sub-panel main breaker (or six-throw rule if MLO) serves as the disconnect for the structure.
  • Wet location: Underground portion is a wet location — use THWN-2 or XHHW-2.
  • Conduit transitions: Use sweep 90s for underground PVC runs, not standard 90s, for easier pulling.

Worked example — 100A garage sub-panel, 120 ft from main house

  • Calculated load: 70A peak (workshop + EV charger)
  • Feeder OCPD: 100A 2-pole breaker in main house panel
  • Voltage drop check at 120 ft: 100A on 3 AWG copper = 4.4V drop (1.8% on 240V) — pass for 3% feeder limit, but tight. Go to 2 AWG for safety.
  • Conductors: 2 AWG copper THHN/THWN-2 × 3 (L1, L2, N) + 8 AWG copper EGC
  • Raceway: 1-1/4" PVC Sch 40, buried 18 inches, with Sch 80 risers above grade
  • Fill check: 3 × 0.1158 + 0.0366 = 0.3840 in² in 1-1/4" PVC Sch 40 = 25.1%, pass.
  • Grounding: Two 8-ft ground rods, 6 AWG copper to ground bar. Bonding screw removed from neutral bar.
  • GFCI: 20A 125V GFCI receptacles throughout garage.

Verify with the Conduit Fill Calculator.

Quick reference

Garage sub-panel Run length Copper feeder EGC PVC conduit
60A <75 ft 6 AWG × 3 10 AWG 1"
60A 75-150 ft 4 AWG × 3 10 AWG 1"
100A <75 ft 3 AWG × 3 8 AWG 1-1/4"
100A 75-150 ft 2 AWG × 3 8 AWG 1-1/4"
100A 150-250 ft 1 AWG × 3 8 AWG 1-1/2"

Related

FIG. 99

FAQ

Yes. NEC 250.32(A) requires a grounding electrode at every separate structure supplied by a feeder or branch circuit, unless it's a single branch circuit. Drive a ground rod (or two) and bond to the sub-panel's ground bar. The EGC from the main panel still runs in the feeder.

METHODOLOGY & SOURCES

This page's figures are transcribed from NEC 2023 (NFPA 70) Chapter 9, Tables 1, 4 and 5, and checked by a version-controlled automated test suite — they are not signed off by a licensed professional. WireFillChart is an independent reference, not affiliated with or endorsed by NFPA. Always verify against the code edition adopted by your local authority having jurisdiction (AHJ).

WireFillChart Editorial Team·EDITORIAL·