Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · ARTICLE

What Gauge Wire for a 60-Amp Circuit?

Use 6 AWG copper or 4 AWG aluminum for 60-amp circuits. 6 AWG THHN copper handles 65A at 75°C terminals — adequate for 60A.

·1 MIN READ·EDITORIAL

6 AWG copper is the standard wire gauge for 60-amp circuits at the common 75°C termination rating. 6 AWG THHN delivers 65A at 75°C — 5A margin over the 60A breaker.

NEC reference

Material 90°C 75°C 60°C
6 AWG copper 75A 65A 55A
4 AWG aluminum 65A 55A 50A
3 AWG aluminum 85A 75A 65A

Common 60-amp circuits

  • 60A sub-panel feeder (detached garage, basement workshop, ADU)
  • Tankless electric water heater (mid-size)
  • Heat pump compressor (larger units)
  • EV charger at 48A continuous (60A breaker per NEC 625.42 / 80% continuous rule)
  • Large hot tub / spa (48A or 50A continuous, 60A breaker)

Sub-panel feeder typical configuration

A 60A sub-panel feed uses 4 conductors in a metal raceway:

  • 2 × 6 AWG hot (240V)
  • 1 × 6 AWG neutral (if 120V loads in sub-panel)
  • 1 × 10 AWG EGC (per NEC 250.122)

Conduit fill in 1" EMT: 3 × 0.0507 + 1 × 0.0211 = 0.1732 in² = 20.0% fill

Ampacity derating

With 4–6 CCCs: 75A × 0.80 = 60A — exactly meets 60A breaker, no margin. With 7–9 CCCs: 75A × 0.70 = 52.5Ainsufficient. Upsize to 4 AWG copper (85A × 0.70 = 59.5A — still marginal) or further.

Voltage drop at 60A continuous (EV charger scenario)

6 AWG copper: 0.398 Ω/1000 ft. At 48A continuous on 100 ft one-way (240V):

V drop = 200 × 48 × (0.398 / 1000) = 3.82V (1.6% of 240V)

Within 3%. For 60A circuits ≥ 130 ft, upsize to 4 AWG to keep drop under 3%.

Quick reference

  • Wire: 6 AWG copper THHN/THWN-2 (or 3 AWG aluminum)
  • Breaker: 60A 2-pole
  • EGC: 10 AWG copper per NEC 250.122
  • Conduit: 3/4" or 1" EMT for sub-panel feed
FIG. 99

FAQ

6 AWG copper THHN at 75°C terminals is rated 65A — sufficient for a 60A breaker. 4 AWG aluminum at 75°C is rated 55A; for 60A aluminum, use 3 AWG (75A) or 2 AWG (90A).

METHODOLOGY & SOURCES

This page's figures are transcribed from NEC 2023 (NFPA 70) Chapter 9, Tables 1, 4 and 5, and checked by a version-controlled automated test suite — they are not signed off by a licensed professional. WireFillChart is an independent reference, not affiliated with or endorsed by NFPA. Always verify against the code edition adopted by your local authority having jurisdiction (AHJ).

WireFillChart Editorial Team·EDITORIAL·