Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · ARTICLE

What Gauge Wire for a 50-Amp Circuit?

Use 6 AWG copper for 50-amp circuits at 75°C terminals. 6 AWG THHN: 75A at 90°C, 65A at 75°C, 55A at 60°C terminals.

·2 MIN READ·EDITORIAL

6 AWG copper is the standard wire gauge for 50-amp circuits, providing comfortable margin at the 75°C terminal rating common in residential equipment.

NEC reference

Rule Effect
NEC Table 310.16 6 AWG copper @ 90°C = 75A; @ 75°C = 65A; @ 60°C = 55A
NEC 110.14(C)(1)(a) ≤ 100A circuits use 60°C column at receptacles unless equipment marked otherwise
NEC 210.21(B)(3) 50A receptacles: NEMA 14-50, 6-50, 50-amp locking variants

Common 50-amp circuits

  • Electric range (full-size, 50A 240V with neutral)
  • NEMA 14-50 RV/EV outlet (most common 50A application today)
  • Welder receptacle (NEMA 6-50, no neutral)
  • Pool heater (some models)
  • Spa / hot tub (large units)

Conductor count + conduit

Circuit Conductors Min EMT
50A range (with neutral): 2 hots + N + EGC 4 3/4" (27% fill)
50A EV / welder (no neutral): 2 hots + EGC 3 3/4" (20% fill)
Two 50A circuits sharing EGC 5 1" (29% fill)

Ampacity derating

With 4–6 CCCs: 75A × 0.80 = 60A — comfortably above 50A. With 7–9 CCCs: 75A × 0.70 = 52.5A — still above 50A but tight. With 10+ CCCs: 75A × 0.50 = 37.5Ainsufficient. Upsize to 4 AWG.

Voltage drop at 50A

6 AWG copper: 0.398 Ω/1000 ft. At 50A on 100 ft (240V circuit, 200 ft round-trip):

V drop = 200 × 50 × (0.398 / 1000) = 3.98V (1.7% of 240V)

Within 3% — 6 AWG is fine to ~175 ft for 50A circuits.

Quick reference

  • Wire: 6 AWG copper THHN/THWN-2 (or 4 AWG aluminum)
  • Breaker: 50A 2-pole
  • Receptacle: NEMA 14-50 (4-wire) or 6-50 (3-wire)
  • Conduit: 3/4" EMT fits one circuit; 1" for two

For RV / EV applications running long distances, consider 4 AWG to reduce drop at high continuous current.

FIG. 99

FAQ

6 AWG copper THHN is the standard. Rated 75A at 90°C and 65A at 75°C terminations — well above the 50A breaker rating. Some installs use 8 AWG copper at 90°C (55A), but only if all terminations are rated 90°C — uncommon in residential.

METHODOLOGY & SOURCES

This page's figures are transcribed from NEC 2023 (NFPA 70) Chapter 9, Tables 1, 4 and 5, and checked by a version-controlled automated test suite — they are not signed off by a licensed professional. WireFillChart is an independent reference, not affiliated with or endorsed by NFPA. Always verify against the code edition adopted by your local authority having jurisdiction (AHJ).

WireFillChart Editorial Team·EDITORIAL·