WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · ARTICLE

What Gauge Wire for a 50-Amp Circuit?

Use 6 AWG copper for 50-amp circuits at 75°C terminals. 6 AWG THHN: 75A at 90°C, 65A at 75°C, 55A at 60°C terminals.

·2 MIN READ·EDITORIAL

6 AWG copper is the standard wire gauge for 50-amp circuits, providing comfortable margin at the 75°C terminal rating common in residential equipment.

NEC reference

Rule Effect
NEC Table 310.16 6 AWG copper @ 90°C = 75A; @ 75°C = 65A; @ 60°C = 55A
NEC 110.14(C)(1)(a) ≤ 100A circuits use 60°C column at receptacles unless equipment marked otherwise
NEC 210.21(B)(3) 50A receptacles: NEMA 14-50, 6-50, 50-amp locking variants

Common 50-amp circuits

  • Electric range (full-size, 50A 240V with neutral)
  • NEMA 14-50 RV/EV outlet (most common 50A application today)
  • Welder receptacle (NEMA 6-50, no neutral)
  • Pool heater (some models)
  • Spa / hot tub (large units)

Conductor count + conduit

Circuit Conductors Min EMT
50A range (with neutral): 2 hots + N + EGC 4 3/4" (27% fill)
50A EV / welder (no neutral): 2 hots + EGC 3 3/4" (20% fill)
Two 50A circuits sharing EGC 5 1" (29% fill)

Ampacity derating

With 4–6 CCCs: 75A × 0.80 = 60A — comfortably above 50A. With 7–9 CCCs: 75A × 0.70 = 52.5A — still above 50A but tight. With 10+ CCCs: 75A × 0.50 = 37.5Ainsufficient. Upsize to 4 AWG.

Voltage drop at 50A

6 AWG copper: 0.398 Ω/1000 ft. At 50A on 100 ft (240V circuit, 200 ft round-trip):

V drop = 200 × 50 × (0.398 / 1000) = 3.98V (1.7% of 240V)

Within 3% — 6 AWG is fine to ~175 ft for 50A circuits.

Quick reference

  • Wire: 6 AWG copper THHN/THWN-2 (or 4 AWG aluminum)
  • Breaker: 50A 2-pole
  • Receptacle: NEMA 14-50 (4-wire) or 6-50 (3-wire)
  • Conduit: 3/4" EMT fits one circuit; 1" for two

For RV / EV applications running long distances, consider 4 AWG to reduce drop at high continuous current.

FIG. 99

FAQ

6 AWG copper THHN is the standard. Rated 75A at 90°C and 65A at 75°C terminations — well above the 50A breaker rating. Some installs use 8 AWG copper at 90°C (55A), but only if all terminations are rated 90°C — uncommon in residential.