Skip to main content
WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · ARTICLE

Stranded vs Solid Wire — When to Use Each

Solid wire is required for 14 AWG and 12 AWG branch circuits in residential receptacles. Stranded wire is required for 8 AWG and larger feeders.

·2 MIN READ·EDITORIAL

Stranded wire is many thin strands twisted together into a single conductor. Solid wire is one continuous round conductor. Both are permitted by NEC; the choice depends on gauge, flexibility needs, and terminal compatibility.

NEC code references

  • NEC 110.14: Conductors must be compatible with terminations.
  • NEC 310.106(C): Sizes 8 AWG and larger must be stranded if used in a raceway (some exceptions).
  • NEC 310.106(D): Stranded conductors must remain stranded — combining strands at a single terminal lug is permitted if the lug is listed for it.

When solid is standard

  • 14 AWG, 12 AWG branch circuits in dwellings: Solid is the dominant SKU for NM-B (Romex) and for THHN sold as branch wire. Receptacles, switches, and back-wire push-in connectors are designed for solid.
  • Grounding electrode conductor (GEC): Solid copper is typical (smaller GEC sizes) for direct attachment to ground rods.
  • Single conductors in short whips to junction boxes: Solid is fine for short, immobile runs.

When stranded is standard

  • 8 AWG and larger feeders: NEC 310.106(C) and manufacturer terminal listings push stranded for ease of handling.
  • Inside flexible conduit (FMC, LFMC): Solid can fatigue at bends; stranded handles flex better.
  • Welding circuits, motor leads, control cables: Always stranded for repeated flex.
  • Industrial machine wiring: Per NEC Article 670 — stranded conductors with proper ferrules.
  • Long pulls through multiple bends: Stranded resists nicks during the pull better than solid.

Terminal compatibility

Most issues arise at terminations. Common rules:

  • Receptacles / switches: Marked CO/ALR (copper/aluminum/rev), CU, or AL. Some accept both solid and stranded; some don't. Check the listing.
  • Wire nuts: Solid + solid is easy. Stranded + stranded needs the right twist. Solid + stranded is fine if the stranded goes in first.
  • Set-screw lugs: Compatible with both. Tighten to manufacturer torque spec.
  • Compression connectors: Match the conductor type (solid vs stranded ferrule).

Fill is the same

NEC Chapter 9 Table 5 doesn't differentiate stranded vs solid:

Gauge / Insulation Area in² (stranded or solid)
14 AWG THHN 0.0097
12 AWG THHN 0.0133
10 AWG THHN 0.0211
8 AWG THHN 0.0366

So your wire fill chart numbers don't change.

Quick reference

  • Solid: 14–12 AWG branch wiring, single short whips, GEC, immobile fixed installs
  • Stranded: 10 AWG up (for flex), 8 AWG and larger (required by listing), motor circuits, control wiring
  • Same fill math: identical Table 5 area regardless of stranding
  • Verify terminal listing for any device accepting your conductor
FIG. 99

FAQ

Yes, but most residential receptacles and switches are designed for solid wire. Stranded requires either a back-wire receptacle with a clamping screw, a pigtail to solid, or a crimped ferrule. NEC permits stranded; manufacturer terminal listings are what matter.

FIG. 98

RELATED TOOLS

METHODOLOGY & SOURCES

This page's figures are transcribed from NEC 2023 (NFPA 70) Chapter 9, Tables 1, 4 and 5, and checked by a version-controlled automated test suite — they are not signed off by a licensed professional. WireFillChart is an independent reference, not affiliated with or endorsed by NFPA. Always verify against the code edition adopted by your local authority having jurisdiction (AHJ).

WireFillChart Editorial Team·EDITORIAL·