WIRE·FILL·CHARTNEC 2023 · CH. 9
DOC · ARTICLE

Stranded vs Solid Wire — When to Use Each

Solid wire is required for 14 AWG and 12 AWG branch circuits in residential receptacles. Stranded wire is required for 8 AWG and larger feeders.

·2 MIN READ·EDITORIAL

Stranded wire is many thin strands twisted together into a single conductor. Solid wire is one continuous round conductor. Both are permitted by NEC; the choice depends on gauge, flexibility needs, and terminal compatibility.

NEC code references

  • NEC 110.14: Conductors must be compatible with terminations.
  • NEC 310.106(C): Sizes 8 AWG and larger must be stranded if used in a raceway (some exceptions).
  • NEC 310.106(D): Stranded conductors must remain stranded — combining strands at a single terminal lug is permitted if the lug is listed for it.

When solid is standard

  • 14 AWG, 12 AWG branch circuits in dwellings: Solid is the dominant SKU for NM-B (Romex) and for THHN sold as branch wire. Receptacles, switches, and back-wire push-in connectors are designed for solid.
  • Grounding electrode conductor (GEC): Solid copper is typical (smaller GEC sizes) for direct attachment to ground rods.
  • Single conductors in short whips to junction boxes: Solid is fine for short, immobile runs.

When stranded is standard

  • 8 AWG and larger feeders: NEC 310.106(C) and manufacturer terminal listings push stranded for ease of handling.
  • Inside flexible conduit (FMC, LFMC): Solid can fatigue at bends; stranded handles flex better.
  • Welding circuits, motor leads, control cables: Always stranded for repeated flex.
  • Industrial machine wiring: Per NEC Article 670 — stranded conductors with proper ferrules.
  • Long pulls through multiple bends: Stranded resists nicks during the pull better than solid.

Terminal compatibility

Most issues arise at terminations. Common rules:

  • Receptacles / switches: Marked CO/ALR (copper/aluminum/rev), CU, or AL. Some accept both solid and stranded; some don't. Check the listing.
  • Wire nuts: Solid + solid is easy. Stranded + stranded needs the right twist. Solid + stranded is fine if the stranded goes in first.
  • Set-screw lugs: Compatible with both. Tighten to manufacturer torque spec.
  • Compression connectors: Match the conductor type (solid vs stranded ferrule).

Fill is the same

NEC Chapter 9 Table 5 doesn't differentiate stranded vs solid:

Gauge / Insulation Area in² (stranded or solid)
14 AWG THHN 0.0097
12 AWG THHN 0.0133
10 AWG THHN 0.0211
8 AWG THHN 0.0366

So your wire fill chart numbers don't change.

Quick reference

  • Solid: 14–12 AWG branch wiring, single short whips, GEC, immobile fixed installs
  • Stranded: 10 AWG up (for flex), 8 AWG and larger (required by listing), motor circuits, control wiring
  • Same fill math: identical Table 5 area regardless of stranding
  • Verify terminal listing for any device accepting your conductor
FIG. 99

FAQ

Yes, but most residential receptacles and switches are designed for solid wire. Stranded requires either a back-wire receptacle with a clamping screw, a pigtail to solid, or a crimped ferrule. NEC permits stranded; manufacturer terminal listings are what matter.

FIG. 98

RELATED TOOLS